REDIN120 [RECOM]

DC OK Indicator LED with Relay Contacts;
REDIN120
型号: REDIN120
厂家: RECOM INTERNATIONAL POWER    RECOM INTERNATIONAL POWER
描述:

DC OK Indicator LED with Relay Contacts

文件: 总8页 (文件大小:2646K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
• Universal AC Input (85-264VAC)  
• Protections: SCP, OVP, OLP, OTP  
• DC OK Indicator LED with Relay Contacts  
• 150% (180W) peak load capacity  
• Built-in active PFC,PF>0,95  
Features  
AC/DC Converter  
DIN Rail  
Series  
• High effciency up to 92.5%  
REDIN120  
120 Watt  
DIN-Rail  
Description  
These DIN-rail mounted power supplies have a robust case, 4mm screw terminal connectors and use  
high reliability components to give a long, trouble-free life. The REDIN120 can be end mounted to  
save rail space or side mounted for use in low-profile cabinets. The units can deliver up to 150%  
start-up power and allow n+1 parallel operation to increase the continuous output current or for supply  
redundancy. Relay contacts simplify DC OK monitoring. The REDIN120 series is designed for  
demanding commercial and industrial applications with UL508, UL60950, IEC60950 CB report and  
CE (LVD + EMC + RoHS) certifications. They come with a full 5-year warranty.  
Power  
Supply  
Selection Guide  
Part  
Number  
nom. Input  
Voltage Range  
Output  
Voltage  
Output  
Adjustability  
Rated  
Current  
Efficiency  
typ.  
230VAC full load  
[%]  
[VAC]  
[VDC]  
12  
24  
[VDC]  
12-14  
24-28  
48-56  
[A]  
8.33  
5
REDIN120-12  
REDIN120-24  
REDIN120-48  
100-240  
100-240  
100-240  
89.5  
91.5  
92.5  
48  
2.5  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
BASIC CHARACTERISTICS  
Parameter  
Condition  
Min.  
Typ.  
Max.  
Input Voltage Range  
85VAC  
264VAC  
Absolute Maximum Input  
Voltage  
300VAC  
375VDC  
max. 3s  
115VAC, full load  
230VAC, full load  
12Vout  
1.5A  
0.65A  
Input Current  
18V  
35V  
65V  
40A  
60A  
Return Voltage Immunity  
24Vout  
48Vout  
E224736  
115VAC, cold start  
230VAC, cold start  
Inrush Current  
115VAC  
230VAC  
1.5W  
1.2W  
3W  
3W  
No Load Power Consumption  
UL60950-1 Certified  
UL508 Certified  
IEC/EN60950-1 Certified  
Input Frequency Range  
Output Voltage Trimming  
47Hz  
63Hz  
+16.67%  
115VAC  
230VAC  
0.99  
0.95  
Power Factor  
Start-up time  
Hold-up time  
115VAC, full load  
230VAC, full load  
500ms  
250ms  
115VAC, full load  
230VAC, full load  
20ms  
20ms  
40ms  
40ms  
0 - 70°C  
-25°C  
100mVp-p  
200mVp-p  
12Vout  
24Vout  
Ripple and Noise(1)  
0 - 70°C  
-25°C  
120mVp-p  
240mVp-p  
-25°C - 70°C 48Vout  
240mVp-p  
Notes:  
Note1: Measured at 20MHz bandwidth by using a 12” twisted pair-wire terminated  
with a 0.1µF & 10µF parallel capacitor.  
continued on next page  
www.recom-power.com  
REV.: 0/2016  
PDR-1  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
REDIN120-12  
Efficiency vs. Load  
Power Dissipation vs Load  
25  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
20  
15  
10  
5
115VAC  
230VAC  
264VAC  
115VAC  
230VAC  
0
0
0
2
4
6
8
2
4
6
8
Load Current [A]  
Load Current [A]  
Power Factor vs Load over Vin  
Input Current vs Load  
1
0.9  
0.8  
0.7  
0.6  
0.5  
0.4  
0.3  
0.2  
0.1  
0
1.4  
1.2  
1
0.8  
0.6  
0.4  
0.2  
0
115VAC  
230VAC  
Iin 115VAC [A]  
Iin 230VAC [A]  
0
1
2
3
4
5
6
7
8
0
1
2
3
4
5
6
7
8
Load Current [A]  
Load Current [A]  
REDIN120-24  
Efficiency vs. Load  
Power Dissipation vs Load  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
25  
20  
15  
10  
5
115VAC  
230VAC  
264VAC  
115VAC  
230VAC  
0
0
0
0
1
2
3
4
5
1
3
4
5
2
Load Current [A]  
Load Current [A]  
Power Factor vs Load over Vin  
Input Current vs Load  
1.4  
1.2  
1
1
0.9  
0.8  
0.7  
0.6  
0.5  
0.4  
0.3  
0.2  
0.1  
0
0.8  
0.6  
0.4  
0.2  
115VAC  
230VAC  
Iin 115VAC [A]  
Iin 230VAC [A]  
0
0
0
1
2
3
4
5
1
2
3
4
5
Load Current [A]  
continued on next page  
REV.: 0/2016  
Load Current [A]  
PDR-2  
www.recom-power.com  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
REDIN120-48  
Efficiency vs. Load  
Power Dissipation vs Load  
25  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
20  
15  
10  
5
115VAC  
230VAC  
264VAC  
115VAC  
230VAC  
0
0
0.5  
1
1.5  
2
2.5  
0
0.5  
1
1.5  
2
2.5  
Load Current [A]  
Load Current [A]  
Input Current vs Load  
Power Factor vs Load over Vin  
1
0.9  
0.8  
0.7  
0.6  
0.5  
0.4  
0.3  
0.2  
0.1  
0
1.4  
1.2  
1
0.8  
0.6  
0.4  
0.2  
0
115VAC  
230VAC  
Iin 115VAC [A]  
Iin 230VAC [A]  
0
0.5  
1
1.5  
2
2.5  
0
0.5  
1
1.5  
2
2.5  
Load Current [A]  
Load Current [A]  
REGULATION  
Parameter  
Condition  
Value  
Output Accuracy  
Line Regulation  
Load Regulation  
0.25% typ. ꢀ 1% max.  
0.1% typ. ꢀ 0.5% max.  
0.25% typ. ꢀ 1.0% max.  
1% typ. ꢀ 5% max.  
0% to 100% load  
Transient Response  
100Hz & 1kHz, 50% duty  
PROTECTION  
Parameter  
Input Fuse  
Condition  
internal  
Value  
T5A, slow blow type  
Short Circuit Protection (SCP)  
Hiccup Mode (current limit)  
12Vout  
24Vout  
48Vout  
15-18VDC, Hiccup Mode  
29-33VDC, Hiccup Mode  
58-65VDC, Hiccup Mode  
Over Voltage Protection (OVP)  
Over Voltage Category (OVC)  
Over Load Protection (OLP)  
OVC II  
Constant power (current limit)  
100 5°C, detect on Heat-sink of power transistorꢁ shut down  
OꢀP, auto recovery after temperature goes down  
Vout up to 90% of rated Vout  
Over Temperature Protection (OTP)  
ON (green)  
OFF (red)  
Power OK LED  
Vout down to 80% of rated Vout  
Relay Contact Rating  
Max. 30Vꢀ1A or 60Vꢀ0.3 or 30VACꢀ0.3A Resitive Load  
continued on next page  
REV.: 0/2016  
www.recom-power.com  
PDR-3  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
IꢀP to OꢀP  
IꢀP to PE  
OꢀP to PE  
3.0kVAC ꢀ 1minute  
2.5kVAC ꢀ 1minute  
0.5kVAC ꢀ 1minute  
10MW min.  
Isolation Voltage  
Isolation Resistance  
Leakage Current  
IꢀP to OꢀP  
IꢀP to PE, 240VAC 50Hz  
0.1mA typ. ꢀ 0.25mA max.  
1.0mA max.  
Overload Capability  
y
Time (x) [s]  
Pout (y) [%]  
180  
1
4
150  
7
140  
100  
45  
120  
0
x
60  
Time [s]  
ENVIRONMENTAL  
Parameter  
Condition  
Value  
Operating Temperature Range  
Temperature Coefficient  
Operating Altitude  
Operating Humidity  
IP Rating  
with derating  
-25°C to +70°C  
0.03%ꢀ°C  
3000m  
non-condensing  
20% - 90% RH  
IP20  
Pollution Degree (PD)  
Shock  
PD2  
10-500Hz 2G, 60min.  
Vibration  
10G ꢀ11ms, along x,y and z axis  
300 x 10³ hours  
MTBF  
MIL-HDBK-217F, full load, 25°C  
Derating Graph  
100  
80  
60  
40  
20  
0
Pout 115VAC cont.  
Pout 230VAC cont.  
-25 -20 -10  
0
10  
20  
30  
40  
50  
60  
70  
80  
Ambient Temperature [°C]  
continued on next page  
REV.: 0/2016  
PDR-4  
www.recom-power.com  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
SAFETY AND CERTIFICATIONS  
Certificate Type  
Report / File Number  
Standard  
UL60950-1, 2nd Edition, 2014  
CSA C22.2 No. 60950-1-07, 2nd Edition, 2014  
Information Technology Equipment, General Requirements for Safety  
E224736  
UL508, 17th Edition, 2013  
CSA C22.2 No. 107.1-01, 3rd Edition, 2011  
IEC60950-1, 2nd Edition 2005, +AM1:2009 + AM2:2013  
EN60950-1:2006, + A11:2009 + A1:2010 + A12:2011  
+ A2:2013  
Industrial Control Equipment  
E470721  
SA1508106S 001 +  
SA1508106S 002  
Information Technology Equipment - General Requirments for Safety  
EMC Compliance  
Report / Condition  
Standard / Criterion  
Information technology equipment - Radio disturbance characteristics -  
Limits and methods of measurement  
EN55022, Class B, 2010  
Information technology equipment - Immunity characteristics - Limits and  
methods of measurement  
EN55024, Class B, 2010  
Limitations on the amount of electromagnetic intererence allowed from  
digital and electronic devices  
47 CFR FCC Part 15, Subpart B: 2014  
Methods of Measurement of Radio-Noise Emissions from Low-Voltage  
Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz  
ANSI C63.4: 2014  
ESD Electrostatic discharge immunity test  
Radiated, radio-frequency, electromagnetic field immunity test  
Fast Transient and Burst Immunity  
Air 8kV, Contact 4kV  
EN61000-4-2, Criteria B, 2009  
EN61000-4-3, Criteria A, 2006  
EN61000-4-4, Criteria B, 2012  
EN61000-4-5, Criteria B, 2014  
EN61000-4-6, Criteria A, 2014  
EN61000-4-8, Criteria A, 2010  
3Vꢀm  
AC Power Port: L+N+PE 1kV  
AC Power Port L-N 1kV, L-PE + N-PE 2kV  
AC Power Port 3V  
Surge Immunity  
Immunity to conducted disturbances, induced by radio-frequency fields  
Power Magnetic Field Immunity  
50Hz, 1Aꢀm  
Voltage Dips >95%  
Voltage Dips 30%  
Voltage Interruptions >95%  
EN61000-4-11, Criteria B, 2004  
EN61000-4-11, Criteria C, 2004  
EN61000-4-11, Criteria C, 2004  
Voltage Dips and Interruptions  
Limits of Harmonic Current Emissions  
Voltage Fluctuations & Flicker  
EN61000-3-2, Criteria A, 2014  
EN61000-3-3, Clause 5: 2013  
DIMENSION and PHYSICAL CHARACTERISTICS  
Parameter  
Type  
Value  
Case  
Cover  
Aluminium  
Nickel plated steel  
Material  
Package Dimension (LxWxH)  
Package Weight  
without mounting clip  
114.5 x 33.0 x 124.4mm  
590g typ.  
continued on next page  
www.recom-power.com  
REV.: 0/2016  
PDR-5  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
Dimension Drawing (mm)  
DC OK -V +V  
10.3  
Vadj.  
DC OK LED  
Parallel Use  
Single Use  
55.0  
28.4  
N
L
PE  
33.0  
114.5  
124.0  
43.0  
41.5  
Terminals and Wiring  
Screw Connector  
2.5-6mm2  
Type  
Solid Wire  
Stranded Wire  
2.5-4mm2  
American Wire Gauge (AWG)  
Wire Stripping Length  
AWG10-16  
8mm  
Screwdriver (slotted ꢀ cross)  
3.5mm  
Recommended tightening torque 0.5Nm-0.8Nm  
Tolerance: X.X 0.5mm  
X.XX 0.25mm  
PDR-6  
REV.: 0/2016  
www.recom-power.com  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
INSTALLATION and APPLICATION  
Mounting Instruction  
Mounting  
Releasing  
1
Vadj.  
DC OK LED  
Parallel Use  
Single Use  
2
2
„Click“  
1
Mounting Multiple Power Supplies  
Vadj.  
Vadj.  
Vadj.  
DC OK LED  
DC OK LED  
DC OK LED  
Parallel Use  
Single Use  
Parallel Use  
Single Use  
Parallel Use  
Single Use  
15mm  
15mm  
leave 15mm gap between supplies  
15mm Minimum Abstand  
www.recom-power.com  
REV.: 0/2016  
PDR-7  
REDIN120  
AC/DC Converter  
Specifications (measured @ t = 25°C, rated Vin, rated load and after warm up)  
a
Series  
Parallel Operation  
L1 L2 L3 N PE  
L N PE  
+
-
~
~
~
+
+V  
-V  
DC  
OK  
~
~
~
-
+
+
+V  
-V  
DC  
OK  
Load  
-
-
+
-
+V  
-V  
DC  
OK  
DC OK  
Single Operation:  
1) Make sure that the front panel switch is set to “single Use.”  
2) The output voltage can be increased by trim pot to compensate any cable losses.  
Parallel Operation:  
1) Make sure that the front panel switch is set to “single Use” on each power supply.  
2) Adjust each power supply to the exact same output voltage with same load and cooling conditions.  
3) Set the front panel switches to “Parallel Use.” Use the same wire length for each power supply (star connection) and energize all units at the  
same time to avoid triggering overload protection.  
Derate the maximum output power to 90% of nominal ratings.  
For operation with more than three power supplies in parallel or series operation, please contact RECOM technical support for advice.  
Application Circuit  
T5A  
+V  
-V  
L
Input  
Filter  
Output  
Filter  
Power Stage  
Protection  
N
E
DC  
OK  
Relay  
OTP  
Shut-  
Down  
LED  
Vadj.  
OVP  
Shut-  
Down  
Output  
Voltage  
Regulation  
OCP  
Limit  
Single /  
Parallel  
PACKAGKING INFORMATION  
Parameter  
Type  
Value  
140.0 x 50.0 x 142.0mm  
1pcs.  
Packaging Dimension (LxWxH)  
Packaging Quantity  
cardboard box  
cardboard box  
Storage Temperature Range  
Storage Humidity  
-40°C to +85°C  
5% - 95% RH  
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit written  
consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer  
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.  
PDR-8  
REV.: 0/2016  
www.recom-power.com  

相关型号:

REDIN120-12

DC OK Indicator LED with Relay Contacts
RECOM

REDIN120-24

DC OK Indicator LED with Relay Contacts
RECOM

REDIN120-24/3AC

120 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN120-3AC

120 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN120-48

DC OK Indicator LED with Relay Contacts
RECOM

REDIN240

Universal AC Input
RECOM

REDIN240-24

Universal AC Input
RECOM

REDIN240-24/3AC

240 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN240-3AC

240 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN240-48

Universal AC Input
RECOM

REDIN45

45 Watt DIN-Rail Power Supply
RECOM

REDIN45-12

45 Watt DIN-Rail Power Supply
RECOM