REDIN240-3AC [RECOM]

240 Watt 3 Phase DIN-Rail Power Supply;
REDIN240-3AC
型号: REDIN240-3AC
厂家: RECOM INTERNATIONAL POWER    RECOM INTERNATIONAL POWER
描述:

240 Watt 3 Phase DIN-Rail Power Supply

文件: 总8页 (文件大小:617K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
• 2 and 3-phase operation  
Features  
• Input voltage range: 320 – 575VAC  
• Output trim range: 22.5 – 29.5VDC  
• High electrical strength; high reliability  
• Permanent overload and short-circuit protection  
• Parallel operation capability  
AC/DC Converter  
DIN-Rail  
Series  
REDIN240/3AC  
• International safety certification listing  
Description  
240 Watt  
The REDIN/3AC is a series of rugged DIN rail power supplies for two and three-phase mains  
operation from 320 to 575Vac without the need of a neutral connection. Four versions with a  
maximum current limited output deliver 5A, 10A, 20A or 40A without derating up to +55°C. The output  
3 Phase  
can be grounded via a third common output terminal.The LED signal on the front panel indicates that the DIN-Rail  
output voltage remains within the wide adjustable range from 22.5 to 29.5Vdc. The units are covered by  
international safety certificates and are intended for worldwide use. In power-hungry applications, the  
Power Supply  
units can be connected in parallel with no need for additional components.  
Selection Guide  
Part  
nom. Input  
Voltage Range  
[VAC]  
Output  
Voltage  
[VDC]  
Output  
Adjustability  
[VDC]  
Rated  
Current  
[A]  
Efficiency (1)  
typ.  
Number  
[%]  
REDIN240-24/3AC  
400-500  
24  
22.5-29.5  
10  
88.5  
Notes:  
Note1: Efficiency is tested at nominal input and full load at +25°C ambient  
Model Numbering  
REDIN240-__/3AC  
nom. Output Power  
Output Voltage  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
BASIC CHARACTERISTICS  
Parameter  
E196683  
E470721  
Condition  
Min.  
Typ.  
Max.  
3 phase operation  
2 phase operation  
320VAC  
360VAC  
400VAC  
400VAC  
575VAC  
575VAC  
UL60950-1 certified  
Input Voltage Range  
UL508 certified  
EN60950-1 certified  
CSA C22.2 No. 60950-01 certified  
EN55011 compliant  
EN50121-4 compliant  
CSA C22.2 No.107 certified  
EN61000-6-2 compliant  
EN61000-6-3 compliant  
3 phase  
operation  
400VAC  
500VAC  
3 x 600mA  
3 x 500mA  
Input Current  
2 phase  
operation  
400VAC  
500VAC  
2 x 700mA  
2 x 600mA  
Inrush Current  
15A  
Powerfactor  
0.59  
Return Voltage Immunity  
No Load Power Consumption  
Input Frequency Range  
Output Voltage Trimming  
Minimum Load  
24 Vout  
35VDC  
7.5W  
65Hz  
AC Input  
45Hz  
22.5VDC  
0%  
29.5VDC  
Start-up time  
2/3 phase operation, 400VAC  
1s  
Rise time  
2ms  
400VAC  
480VAC  
20ms  
25ms  
Hold-up time  
Output Ripple & Noise  
measured at 20MHz BW  
30mVp-p  
continued on next page  
www.recom-power.com  
REV.: 0/2018  
PDR-1  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
Efficiency vs. Load @ 3 Phase Operation  
Power Dissipation vs. Load @ 3 Phase Operation  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
35  
30  
25  
20  
15  
10  
5
360V  
400V  
480V  
360V  
400V  
480V  
0
0
10 20 30 40 50 60 70 80 90 100  
0
10 20 30 40 50 60 70 80 90 100  
Output Load [%]  
Output Load [%]  
REGULATION  
Parameter  
Condition  
Value  
Output Accuracy  
Line Regulation  
Load Regulation  
1.0% max.  
0.1% typ.  
10% change in input voltage  
10% - 100% load  
1.0% typꢀ 2.0% max.  
25% load step change  
recovery time  
200mV typ.  
50ms typ.  
Transient Response  
Accuracy vs. Load  
1.0  
0.8  
0.6  
0.4  
0.2  
0
-0.2  
-0.4  
-0.6  
-0.8  
-1.0  
0
10 20 30 40 50 60 70 80 90 100  
Output Load [%]  
www.recom-power.com  
REV.: 0/2018  
PDR-2  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
PROTECTIONS  
Parameter  
Type  
Value  
Input Fuse  
internal  
F4A, fast blow  
3x 6A (charactersitics B)  
3x 10A (charactersitics B)  
3x 16A (charactersitics B)  
Recommended backup fuse for mains protection  
Short Circuit Protection (SCP)  
Over Voltage Protection (OVP)  
Over Voltage Category (OVC)  
Over Temperature Protection (OTP)  
Over Current Protection (OCP)  
Power OK LED  
below 100mΩ  
>120% typ. power limiting  
>145% typ. auto recovery  
OVC II  
refer to note 2  
>120% typ. auto recovery  
Vout >21.5V  
“DC OK” Light green  
Class of Equipment  
Class I  
I/P to O/P  
O/P to PE  
4242VDC  
Isolation Voltage  
tested for 1 minute  
2300VDC  
Isolation Resistance  
Insulation Grade  
10Mmin.  
reinforced  
Notes:  
Note2: Under thermal overload conditions, the device does not switch offꢀ instead, the output current is limited as much as necessary to  
return internal operating temperatures to safe limits. After the device cools down, full output capacity is automatically restored.  
ENVIRONMENTAL  
Parameter  
Condition  
Value  
Operating Temperature Range  
Maximum Case Temperature  
Temperature Coefficient  
Operating Altitude  
Operating Humidity  
IP Rating  
without derating @ natural convection 0.1m/s (see graph)  
-25°C to +55°C  
+105°C  
0.05%/°C  
2000m  
non-condensing at 25°C  
according to EN50178  
5%-95% RH max.  
IP20  
Pollution Degree  
Shock  
PD2  
30G in all directions  
Vibration  
<15Hz, amplitute 2.5mm 15Hz to 150Hz, 2.3G, 90min.  
+25°C  
according to IEC61709  
+55°C  
500 x 103 hours  
60 x 103 hours  
MTBF  
Derating Graph  
(@ Chamber and natural convection 0.1m/s)  
100  
93.8  
80  
62.5  
60  
40  
24Vout  
22.5Vout  
29.5Vout  
20  
0
-25 -20  
0
20  
40  
55 60 70 80  
Ambient Temperature [°C]  
www.recom-power.com  
REV.: 0/2018  
PDR-3  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
SAFETY AND CERTIFICATIONS  
Certificate Type  
Report / File Number  
Standard  
UL60950-1, 1st Edition: 2007  
CSA C22.2 No. 60950-1, 1st Edition: 2006  
Information Technology Equipment, General Requirements for Safety  
E196683  
UL508, 17th-Edition  
CSA C22.2 No. 107.1-01, 3rd-Edition  
Industrial Control Equipment  
E470721  
Information Technology Equipment - General Requirments for Safety (LVD)  
EN60950-1:2006+A2:2013  
TP TC 004/2011  
EAC  
RU-AT.37.02367  
RoHs2  
RoHs 2011/65/EU  
EMC Compliance  
Report / Condition  
Standard / Criterion  
Industrial, scientific and medical equipment – Radio frequency distur-  
bance characteristics – Limits and methods of measurement  
EN55011:1989 + A2:2002, Class B  
Air 2, 4, 8kV  
Contact 2, 4, 6, 8kV  
ESD Electrostatic discharge immunity test  
EN61000-4-2:1995 + A1:1998, Criteria A  
EN61000-4-3:2002 + A1:2002, Criteria A  
Radiated, radio-frequency, electromagnetic field immunity test  
10V/m (80 - 3000MHz)  
AC Power Port: 4kV  
PE 4kV  
Fast Transient and Burst Immunity  
EN61000-4-4:1995 + A2:2001, Criteria A  
DC Power Port 2kV  
AC Power Port: L-N 0.5, 1, 2kV  
L-PE 4kV  
DC Power Port 0.5, 1, 2kV  
AC Power Port 10V  
Surge Immunity  
EN61000-4-5:1995 + A1:2001, Criteria A  
EN61000-4-6:1996 + A1:2001, Criteria A  
Immunity to conducted disturbances, induced by radio-frequency fields  
DC Power Port 10V  
Voltage Dips and Interruptions  
Voltage Dips and Interruptions  
Voltage Dips and Interruptions  
Voltage Dips and Interruptions  
Voltage Dips >95%  
Voltage Dips 60%  
Voltage Dips 30%  
EN61000-4-11:1994, Criteria A  
EN61000-4-11:1994, Criteria B  
EN61000-4-11:1994, Criteria A  
EN61000-4-11:1994, Criteria B  
Voltage Interruptions > 95%  
Limits of Harmonic Current Emissions  
Limits of Voltage Fluctuations & Flicker  
EN61000-3-2:2000, Class A  
EN61000-3-3:1995 + A1:2001  
Railway applications – Electromagnetic compatibility Part 4: Emission  
and immunity of the signalling and telecommunications apparatus  
EN50121-4:2006  
EMC Compliance (Generic Standards)  
Report / Condition  
Standard / Criterion  
Generic standards - Immunity standard for industrial environments  
EN61000-6-2:2005  
Generic standards - Emission standard for residential, commercial and  
light-industrial environments  
EN61000-6-3:2007 + A1:2011  
DIMENSION and PHYSICAL CHARACTERISTICS  
Parameter  
Type  
Value  
cover  
case  
steel sheet, zinc-plated  
aluminium  
Material  
Unit Dimension (LxWxH)  
Unit Weight  
153.2 x 60.0 x 130.0mm  
1100g typ.  
continued on next page  
REV.: 0/2018  
www.recom-power.com  
PDR-4  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
Dimension Drawing (mm)  
DC OK LED  
VAdj.  
L1  
+V  
+V  
-V  
L2  
L3  
-V  
-V  
12.1  
11.3  
153.2  
160.0  
50.5  
60.0  
Terminals and Wiring  
Type  
Solid Wire  
Stranded Wire(3)  
Screw Connector  
0.2 - 2.5mm2  
0.2 - 2.5mm2  
AWG 24-14  
AWG 16-12  
9mm  
Notes:  
Note3: The use of sleeve or ferrule terminations is recommended  
American Wire Gauge Input  
Amerivan Wire Gauge Output  
Wire Stripping Length  
Screwdriver (slotted / cross)  
3.5mm  
Recommended tightening torque 0.4Nm-0.5Nm  
Tolerance: X.X 0.5mm  
www.recom-power.com  
REV.: 0/2018  
PDR-5  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
INSTALLATION and APPLICATION  
Mounting Instruction (4)  
Mounting  
1
Releasing  
2
2
„Click“  
1
Mounting Multiple Power Supplies (5)  
please mind a gap of 50mm in vertical direction  
DC OK LED  
VAdj.  
DC OK LED  
VAdj.  
L1  
L1  
L2  
L3  
+V  
+V  
-V  
+V  
+V  
-V  
-V  
-V  
L2  
L3  
-V  
-V  
no gap necessary between modules  
Notes:  
Note4: The power supply unit can be snapped onto all DIN Rails in according with EN60715 and has to be mounted vertically  
Note5: To guarantee sufficient convection, it is recommended to mint a 50.0 mm gap in vertical direction  
www.recom-power.com  
REV.: 0/2018  
PDR-6  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
2 Phase and 3 Phase Operation  
3 Phase  
2 Phase  
L1 L2 L3 PE  
L1 L2 L3 PE  
+V  
-V  
+V  
-V  
~
~
~
+V  
-V  
Parallel Operation and Phase Redundancy  
L1 L2 L3 PE  
Parallel Operation  
~
1) Adjust each power supply to the exact same output voltage with same  
load and cooling conditions.  
2) Use the same wire length for each power supply (star connection) and  
energize all units at the same time to avoid triggering overload protection.  
3) To prevent high reverse currents in the event of a secondary output  
fault, it is recommended to install a protective circuit at the output of each  
device when more than two power supplies are connected in parallel  
(e.g. decoupling diode or DC fuse).  
+V  
~
Load:  
90% of n x INom  
-V  
~
For n parallel connected devices, the output current can be increased  
to 90% of n x Inom. A maximum of 5 devices can be connected in parallel.  
L1 L2 L3 PE  
+V -V  
~
~
Phase redundancy  
1) If any single phase fails, operation is still guaranteed.  
Max. load  
120W  
www.recom-power.com  
REV.: 0/2018  
PDR-7  
REDIN240/3AC  
AC/DC Converter  
Series  
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)  
Block Diagramm  
L1  
+V  
-V  
F4A  
Input  
Filter  
Output  
Filter  
Power Stage  
Protection  
L2  
L3  
LED  
OTP  
Shut-  
Down  
Output  
Voltage  
Vadj.  
Regulation  
OVP  
OCP  
Limit  
Shut-  
Down  
PACKAGING INFORMATION  
Parameter  
Type  
Value  
189.0 x 166.0 x 70.0mm  
1 pcs  
Packaging Dimension (LxWxH)  
Packaging Quantity  
cardboard box  
Storage Temperature Range  
Storage Humidity  
-40°C to +85°C  
95% RH max.  
non-condensing  
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The  
products are not authorized for use in safety-critical applications without RECOM’s explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause  
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized  
use of RECOM products in such safety-critical applications.  
www.recom-power.com  
REV.: 0/2018  
PDR-8  

相关型号:

REDIN240-48

Universal AC Input
RECOM

REDIN45

45 Watt DIN-Rail Power Supply
RECOM

REDIN45-12

45 Watt DIN-Rail Power Supply
RECOM

REDIN45-24

45 Watt DIN-Rail Power Supply
RECOM

REDIN480

480 Watt DIN-Rail Power Supply
RECOM

REDIN480-24

480 Watt DIN-Rail Power Supply
RECOM

REDIN480-24/3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-48

480 Watt DIN-Rail Power Supply
RECOM

REDIN60

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-12

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-24

60 Watt DIN-Rail Power Supply
RECOM