REDIN480 [RECOM]

480 Watt DIN-Rail Power Supply;
REDIN480
型号: REDIN480
厂家: RECOM INTERNATIONAL POWER    RECOM INTERNATIONAL POWER
描述:

480 Watt DIN-Rail Power Supply

文件: 总7页 (文件大小:551K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
• Universal AC Input (85-264VAC)  
• Protections: SCP, OVP, OLP, OTP  
• DC OK Indicator LED With Relay Contacts  
• 150% (720W) Peak Load Capacity  
• Built-in Active PFC, PF>0.95  
Features  
AC/DC Converter  
DIN Rail  
Series  
• High Effciency Up To 93.8%  
REDIN480  
480 Watt  
DIN-Rail  
Description  
These DIN-rail mounted power supplies have a robust case, 4mm screw terminal connectors and use  
high reliability components to give a long, trouble-free life. The REDIN480 can be end mounted to save  
rail space or side mounted for use in low-profile cabinets. The units can deliver up to 150% start-up  
power and allow n+1 parallel operation to increase the continuous output current or for supply redun-  
dancy. Relay contacts simplify DC OK monitoring. The REDIN480 series is designed for demanding  
commercial and industrial applications with UL508, UL60950, IEC60950 CB report and CE (LVD + EMC  
+ RoHS) certifications. They come with a full 5-year warranty.  
Power  
Supply  
Selection Guide  
Part  
nom. Input  
Voltage Range  
[VAC]  
Output  
Voltage  
[VDC]  
Output  
Adjustability  
[VDC]  
Rated  
Current  
[A]  
Efficiency  
typ.  
Number  
[%]  
REDIN480-24  
REDIN480-48  
100-240  
100-240  
24  
48  
24-28  
48-56  
20  
10  
93.8  
93.5  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
BASIC CHARACTERISTICS  
Parameter  
Condition  
Min.  
Typ.  
Max.  
Input Voltage Range  
85VAC  
264VAC  
Absolute Maximum Input  
Voltage  
max. 3s  
300VAC  
full load, 115VAC  
full load, 230VAC  
4.59A  
2.36A  
7.0A  
3.5A  
Input Current  
Inrush Current  
cold start at 25°C, 115VAC  
cold start at 25°C, 230VAC  
6.8A  
13A  
20A  
40A  
E224736  
UL60950-1 Certified  
UL508 Certified  
IEC/EN60950-1 Certified  
85-264VAC  
230VAC  
3.85W  
2.85W  
5W  
4W  
No Load Power Consumption  
Input Frequency Range  
Power Factor  
47Hz  
63Hz  
115VAC  
230VAC  
0.99  
0.95  
115VAC  
24Vout  
1.6s  
1.3s  
230VAC  
3s  
3s  
Start-up time  
115VAC  
48Vout  
1.5s  
1.3s  
230VAC  
24Vout  
230VAC  
48Vout  
20ms  
20ms  
21ms  
22ms  
31ms  
49ms  
Hold-up time  
Rise time  
24Vout  
230VAC  
48Vout  
100ms  
100ms  
0 - 70°C  
24Vout  
-25°C  
240mVp-p  
480mVp-p  
Ripple & Noise (1)  
-25 - 70°C  
48Vout  
480mVp-p  
Notes:  
Note1: Measured at 20MHz bandwidth by using a 12” twisted pair-wire terminated  
with a 0.1µF & 10µF parallel capacitor.  
continued on next page  
www.recom-power.com  
REV.: 0/2017  
PDR-1  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
REDIN480-24  
Efficiency vs Load  
Power Dissipation vs Load  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
60  
50  
40  
30  
20  
10  
0
115VAC  
230VAC  
115VAC  
230VAC  
0
5
10  
15  
20  
0
5
10  
15  
20  
Load Current [A]  
Load Current [A]  
Input Current vs Load  
Power Factor vs Load over Vin  
1.2  
1.0  
0.8  
0.6  
0.4  
0.2  
0
5
4.5  
4
3.5  
3
2.5  
2
1.5  
1
115VAC  
230VAC  
Iin 115VAC [A]  
Iin 230VAC [A]  
0.5  
0
0
20  
40  
60  
80  
100  
0
5
10  
15  
20  
Load Current [A]  
Load Current [%]  
REGULATION  
Parameter  
Condition  
Value  
24Vout  
48Vout  
0.6% typ. / 3.0% max.  
0.5% typ. / 3.0% max.  
Output Accuracy  
Line Regulation  
Load Regulation  
24Vout, 48Vout  
0.1% typ. / 0.5% max.  
0.3% typ. / 1.0% max.  
2.0% typ. / 5.0% max.  
0% to 100% load  
Transient Response  
100Hz & 1kHz, 50% duty, 25% load step change  
PDR-2  
REV.: 0/2017  
www.recom-power.com  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
PROTECTION  
Parameter  
Input Fuse  
Condition  
Value  
T10A, slow blow type  
Hiccup Mode  
Short Circuit Protection (SCP)  
24Vout  
48Vout  
29-33VDC, constant voltage auto recovery  
58-63VDC, constant voltage auto recovery  
Over Voltage Protection (OVP)  
Over Voltage Category (OVC)  
Over Load Protection (OLP)  
OVC II  
Limit the current by constant power circuit  
115 5°C , detect on Heat-sink of power transistor; shut down  
O/P, auto recovery after temperature goes down  
3.0KVAC / 15mA max.  
Over Temperature Protection (OTP)  
I/P to O/P  
I/P to PE  
O/P to PE  
Isolation Voltage  
tested for 1 minute  
2.5KVAC / 15mA max.  
0.5kVAC / 20mA max.  
Isolation Resistance  
Insulation Grade  
10MW min.  
Reinforced  
I/P to O/P  
I/P to PE  
0.25mA max.  
3.5mA max.  
Leakage Current  
ON (green)  
OFF (red)  
Vout up to 90% of rated Vout  
Vout down to 80% of rated Vout  
Power OK LED  
Relay Contact Rating  
Max. 30V/1A or 60V/0.3 or 30VAC/0.3A Resitive Load  
Overload Capability  
y
Time (x) [s]  
Pout (y) [%]  
150  
3
8
135  
100  
45  
125  
0
x
Time [s]  
60  
ENVIRONMENTAL  
Parameter  
Operating Temperature Range (2)  
Temperature Coefficient  
Operating Humidity  
IP Rating  
Condition  
with derating  
Value  
-25°C to +70°C  
0.03%/°C  
non-condensing  
20% - 90% RH  
IP X0  
Pollution Degree (PD)  
Shock  
PD2  
10-500Hz 2G, 60min.  
Vibration  
10G /11ms, along x,y and z axis  
300 x 10³ hours  
MTBF  
MIL-HDBK-217F G.B., full load, 25°C  
continued on next page  
REV.: 0/2017  
www.recom-power.com  
PDR-3  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
Thermal Derating  
100  
80  
60  
40  
Pout 115VAC cont.  
Pout 230VAC cont.  
20  
0
-25-20 -10  
0
10  
20  
30 40  
50 60  
70 80  
Ambient Temperature [°C]  
SAFETY AND CERTIFICATIONS  
Certificate Type  
Report / File Number  
Standard  
UL60950-1, 2nd Edition, 2014  
CSA C22.2 No. 60950-1-07, 2nd Edition, 2014  
Information Technology Equipment, General Requirements for Safety  
E224736 A52  
UL508, 17th Edition, 2013  
CSA C22.2 No. 107.1-01, 3rd Edition, 2011  
IEC60950-1, 2nd Edition:2005, +AM1:2009 + AM2:2013  
EN60950-1:2006+ A11:2009 + A1:2010 + A12:2011 +  
A2:2013  
Industrial Control Equipment  
E470721 Vol3 Sec1  
16BAS06033 11  
Information Technology Equipment - General Requirments for Safety  
(CB Scheme)  
RoHs 2  
RoHs 2011/65/EU  
EMC Compliance  
Report / Condition  
Standard / Criterion  
Information technology equipment - Radio disturbance characteristics -  
Limits and methods of measurement  
EN55022:2010 + AC:2011, Class B  
Information technology equipment - Immunity characteristics - Limits  
and methods of measurement  
EN55024:2010 + A1:2015  
47 CFR FCC Part 15, Subpart B, 2016  
ANSI C63.4, 2014  
Limitations on the amount of electromagnetic intererence allowed from  
digital and electronic devices  
Methods of Measurement of Radio-Noise Emissions from Low-Voltage  
Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz  
ESD Electrostatic discharge immunity test  
Air 8kV, Contact 4kV  
3V/m  
EN61000-4-2, Criteria B  
EN61000-4-3, Criteria A  
EN61000-4-4, Criteria B  
Radiated, radio-frequency, electromagnetic field immunity test  
Fast Transient and Burst Immunity  
AC Power Port: 1kV  
AC Power Port L-N 1kV,  
L-PE + N-PE 2kV  
Surge Immunity  
EN61000-4-5, Criteria B  
Immunity to conducted disturbances, induced by radio-frequency fields  
Power Magnetic Field Immunity  
AC Power Port 3V  
50Hz, 1A/m  
EN61000-4-6, Criteria A  
EN61000-4-8, Criteria A  
Voltage Dips >95%  
Voltage Dips 30%  
Voltage Interruptions >95%  
EN61000-4-11, Criteria B  
EN61000-4-11, Criteria C  
EN61000-4-11, Criteria C  
Voltage Dips and Interruptions  
Limits of Harmonic Current Emissions  
Voltage Fluctuations & Flicker  
EN61000-3-2:2014, Criteria A  
EN61000-3-3:2013  
PDR-4  
REV.: 0/2017  
www.recom-power.com  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
DIMENSION and PHYSICAL CHARACTERISTICS  
Parameter  
Type  
Value  
Case  
Cover  
Aluminium  
Nickel plated steel  
Material  
Package Dimension (LxWxH)  
Package Weight  
122.3 x 71.0 x 124.2mm  
1.185kg typ.  
Dimension Drawing (mm)  
38.0  
DC OK +V +V -V -V  
10.5  
Vadj.  
DC OK LED  
Parallel Use  
Single Use  
6.85  
PE  
N
L
19.0  
71.0  
122.3  
132.8  
54.10  
58.3  
Terminals and Wiring  
Screw Connector  
Type  
Solid Wire  
1-6mm2  
1-4mm2  
AWG17-10  
8mm  
Stranded Wire  
American Wire Gauge  
Wire Stripping Length  
Screwdriver (slotted / cross)  
3.5mm  
Recommended tightening torque 0.5Nm-0.8Nm  
Tolerance: X.X 0.5mm  
X.XX 0.25mm  
www.recom-power.com  
REV.: 0/2017  
PDR-5  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
INSTALLATION  
Mounting Instruction  
Mounting  
Releasing  
1
DC OK +V +V -V -V  
Vadj.  
DC OK LED  
Parallel Use  
Single Use  
N
PE  
L
2
2
„Click“  
1
Mounting Multiple Power Supplies  
DC OK +V +V -V -V  
DC OK +V +V -V -V  
DC OK +V +V -V -V  
Vadj.  
Vadj.  
Vadj.  
DC OK LED  
DC OK LED  
DC OK LED  
Parallel Use  
Single Use  
Parallel Use  
Single Use  
Parallel Use  
Single Use  
N
L
PE  
N
L
PE  
PE  
N
L
20mm  
20mm  
leave 20mm gap between supplies  
PDR-6  
REV.: 0/2017  
www.recom-power.com  
REDIN480  
AC/DC Converter  
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)  
Series  
Parallel Operation & Phase Redundancy  
L1 L2 L3 N PE  
L N PE  
+
-
~
~
~
+
+V  
-V  
DC  
OK  
~
~
~
-
+
+
-
+V  
-V  
DC  
OK  
Load  
-
+
-
+V  
-V  
DC  
OK  
DC OK  
Single Operation:  
1) Make sure that the front panel switch is set to “single Use.”  
2) The output voltage can be increased by trim pot to compensate any cable losses.  
Parallel Operation:  
1) Make sure that the front panel switch is set to “single Use” on each power supply.  
2) Adjust each power supply to the exact same output voltage with same load and cooling conditions.  
3) Set the front panel switches to “Parallel Use.” Use the same wire length for each power supply (star connection) and energize all units at the  
same time to avoid triggering overload protection.  
Derate the maximum output power to 90% of nominal ratings.  
For operation with more than three power supplies in parallel or series operation, please contact RECOM technical support for advice.  
Application Circuit  
T10A  
+V  
-V  
L
Input  
Filter  
Output  
Filter  
Power Stage  
Protection  
N
PE  
DC  
OK  
Relay  
OTP  
Shut-  
Down  
LED  
Vadj.  
OVP  
Shut-  
Down  
Output  
Voltage  
Regulation  
OCP  
Limit  
Single /  
Parallel  
PACKAGKING INFORMATION  
Parameter  
Type  
Value  
140.0 x 88.0 x 142.0mm  
1pcs  
Packaging Dimension (LxWxH)  
Packaging Quantity  
cardboard box  
cardboard box  
Storage Temperature Range  
Storage Humidity  
-40°C to +85°C  
5% - 95% RH  
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit written  
consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer  
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.  
www.recom-power.com  
REV.: 0/2017  
PDR-7  

相关型号:

REDIN480-24

480 Watt DIN-Rail Power Supply
RECOM

REDIN480-24/3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-48

480 Watt DIN-Rail Power Supply
RECOM

REDIN60

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-12

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-24

60 Watt DIN-Rail Power Supply
RECOM

REDIN960-24/3AC

960 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN960-3AC

960 Watt 3 Phase DIN-Rail Power Supply
RECOM

REE-0505S

LOW COST 1W CONVERTER
RECOM

REE10

AC plate-mounted axials
EBMPAPST

REE100

Potentiometer, Wire Wound, 12.5W, 100ohm, 10% +/-Tol
OHMITE