REDIN480 [RECOM]
480 Watt DIN-Rail Power Supply;型号: | REDIN480 |
厂家: | RECOM INTERNATIONAL POWER |
描述: | 480 Watt DIN-Rail Power Supply |
文件: | 总7页 (文件大小:551K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
• Universal AC Input (85-264VAC)
• Protections: SCP, OVP, OLP, OTP
• DC OK Indicator LED With Relay Contacts
• 150% (720W) Peak Load Capacity
• Built-in Active PFC, PF>0.95
Features
AC/DC Converter
DIN Rail
Series
• High Effciency Up To 93.8%
REDIN480
480 Watt
DIN-Rail
Description
These DIN-rail mounted power supplies have a robust case, 4mm screw terminal connectors and use
high reliability components to give a long, trouble-free life. The REDIN480 can be end mounted to save
rail space or side mounted for use in low-profile cabinets. The units can deliver up to 150% start-up
power and allow n+1 parallel operation to increase the continuous output current or for supply redun-
dancy. Relay contacts simplify DC OK monitoring. The REDIN480 series is designed for demanding
commercial and industrial applications with UL508, UL60950, IEC60950 CB report and CE (LVD + EMC
+ RoHS) certifications. They come with a full 5-year warranty.
Power
Supply
Selection Guide
Part
nom. Input
Voltage Range
[VAC]
Output
Voltage
[VDC]
Output
Adjustability
[VDC]
Rated
Current
[A]
Efficiency
typ.
Number
[%]
REDIN480-24
REDIN480-48
100-240
100-240
24
48
24-28
48-56
20
10
93.8
93.5
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
BASIC CHARACTERISTICS
Parameter
Condition
Min.
Typ.
Max.
Input Voltage Range
85VAC
264VAC
Absolute Maximum Input
Voltage
max. 3s
300VAC
full load, 115VAC
full load, 230VAC
4.59A
2.36A
7.0A
3.5A
Input Current
Inrush Current
cold start at 25°C, 115VAC
cold start at 25°C, 230VAC
6.8A
13A
20A
40A
E224736
UL60950-1 Certified
UL508 Certified
IEC/EN60950-1 Certified
85-264VAC
230VAC
3.85W
2.85W
5W
4W
No Load Power Consumption
Input Frequency Range
Power Factor
47Hz
63Hz
115VAC
230VAC
0.99
0.95
115VAC
24Vout
1.6s
1.3s
230VAC
3s
3s
Start-up time
115VAC
48Vout
1.5s
1.3s
230VAC
24Vout
230VAC
48Vout
20ms
20ms
21ms
22ms
31ms
49ms
Hold-up time
Rise time
24Vout
230VAC
48Vout
100ms
100ms
0 - 70°C
24Vout
-25°C
240mVp-p
480mVp-p
Ripple & Noise (1)
-25 - 70°C
48Vout
480mVp-p
Notes:
Note1: Measured at 20MHz bandwidth by using a 12” twisted pair-wire terminated
with a 0.1µF & 10µF parallel capacitor.
continued on next page
www.recom-power.com
REV.: 0/2017
PDR-1
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
REDIN480-24
Efficiency vs Load
Power Dissipation vs Load
100
90
80
70
60
50
40
30
20
10
0
60
50
40
30
20
10
0
115VAC
230VAC
115VAC
230VAC
0
5
10
15
20
0
5
10
15
20
Load Current [A]
Load Current [A]
Input Current vs Load
Power Factor vs Load over Vin
1.2
1.0
0.8
0.6
0.4
0.2
0
5
4.5
4
3.5
3
2.5
2
1.5
1
115VAC
230VAC
Iin 115VAC [A]
Iin 230VAC [A]
0.5
0
0
20
40
60
80
100
0
5
10
15
20
Load Current [A]
Load Current [%]
REGULATION
Parameter
Condition
Value
24Vout
48Vout
0.6% typ. / 3.0% max.
0.5% typ. / 3.0% max.
Output Accuracy
Line Regulation
Load Regulation
24Vout, 48Vout
0.1% typ. / 0.5% max.
0.3% typ. / 1.0% max.
2.0% typ. / 5.0% max.
0% to 100% load
Transient Response
100Hz & 1kHz, 50% duty, 25% load step change
PDR-2
REV.: 0/2017
www.recom-power.com
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
PROTECTION
Parameter
Input Fuse
Condition
Value
T10A, slow blow type
Hiccup Mode
Short Circuit Protection (SCP)
24Vout
48Vout
29-33VDC, constant voltage auto recovery
58-63VDC, constant voltage auto recovery
Over Voltage Protection (OVP)
Over Voltage Category (OVC)
Over Load Protection (OLP)
OVC II
Limit the current by constant power circuit
115 5°C , detect on Heat-sink of power transistor; shut down
O/P, auto recovery after temperature goes down
3.0KVAC / 15mA max.
Over Temperature Protection (OTP)
I/P to O/P
I/P to PE
O/P to PE
Isolation Voltage
tested for 1 minute
2.5KVAC / 15mA max.
0.5kVAC / 20mA max.
Isolation Resistance
Insulation Grade
10MW min.
Reinforced
I/P to O/P
I/P to PE
0.25mA max.
3.5mA max.
Leakage Current
ON (green)
OFF (red)
Vout up to 90% of rated Vout
Vout down to 80% of rated Vout
Power OK LED
Relay Contact Rating
Max. 30V/1A or 60V/0.3 or 30VAC/0.3A Resitive Load
Overload Capability
y
Time (x) [s]
Pout (y) [%]
150
3
8
135
100
45
125
0
x
Time [s]
60
ENVIRONMENTAL
Parameter
Operating Temperature Range (2)
Temperature Coefficient
Operating Humidity
IP Rating
Condition
with derating
Value
-25°C to +70°C
0.03%/°C
non-condensing
20% - 90% RH
IP X0
Pollution Degree (PD)
Shock
PD2
10-500Hz 2G, 60min.
Vibration
10G /11ms, along x,y and z axis
300 x 10³ hours
MTBF
MIL-HDBK-217F G.B., full load, 25°C
continued on next page
REV.: 0/2017
www.recom-power.com
PDR-3
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
Thermal Derating
100
80
60
40
Pout 115VAC cont.
Pout 230VAC cont.
20
0
-25-20 -10
0
10
20
30 40
50 60
70 80
Ambient Temperature [°C]
SAFETY AND CERTIFICATIONS
Certificate Type
Report / File Number
Standard
UL60950-1, 2nd Edition, 2014
CSA C22.2 No. 60950-1-07, 2nd Edition, 2014
Information Technology Equipment, General Requirements for Safety
E224736 A52
UL508, 17th Edition, 2013
CSA C22.2 No. 107.1-01, 3rd Edition, 2011
IEC60950-1, 2nd Edition:2005, +AM1:2009 + AM2:2013
EN60950-1:2006+ A11:2009 + A1:2010 + A12:2011 +
A2:2013
Industrial Control Equipment
E470721 Vol3 Sec1
16BAS06033 11
Information Technology Equipment - General Requirments for Safety
(CB Scheme)
RoHs 2
RoHs 2011/65/EU
EMC Compliance
Report / Condition
Standard / Criterion
Information technology equipment - Radio disturbance characteristics -
Limits and methods of measurement
EN55022:2010 + AC:2011, Class B
Information technology equipment - Immunity characteristics - Limits
and methods of measurement
EN55024:2010 + A1:2015
47 CFR FCC Part 15, Subpart B, 2016
ANSI C63.4, 2014
Limitations on the amount of electromagnetic intererence allowed from
digital and electronic devices
Methods of Measurement of Radio-Noise Emissions from Low-Voltage
Electrical and Electronic Equipment in the Range of 9 kHz to 40 GHz
ESD Electrostatic discharge immunity test
Air 8kV, Contact 4kV
3V/m
EN61000-4-2, Criteria B
EN61000-4-3, Criteria A
EN61000-4-4, Criteria B
Radiated, radio-frequency, electromagnetic field immunity test
Fast Transient and Burst Immunity
AC Power Port: 1kV
AC Power Port L-N 1kV,
L-PE + N-PE 2kV
Surge Immunity
EN61000-4-5, Criteria B
Immunity to conducted disturbances, induced by radio-frequency fields
Power Magnetic Field Immunity
AC Power Port 3V
50Hz, 1A/m
EN61000-4-6, Criteria A
EN61000-4-8, Criteria A
Voltage Dips >95%
Voltage Dips 30%
Voltage Interruptions >95%
EN61000-4-11, Criteria B
EN61000-4-11, Criteria C
EN61000-4-11, Criteria C
Voltage Dips and Interruptions
Limits of Harmonic Current Emissions
Voltage Fluctuations & Flicker
EN61000-3-2:2014, Criteria A
EN61000-3-3:2013
PDR-4
REV.: 0/2017
www.recom-power.com
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
DIMENSION and PHYSICAL CHARACTERISTICS
Parameter
Type
Value
Case
Cover
Aluminium
Nickel plated steel
Material
Package Dimension (LxWxH)
Package Weight
122.3 x 71.0 x 124.2mm
1.185kg typ.
Dimension Drawing (mm)
38.0
DC OK +V +V -V -V
10.5
Vadj.
DC OK LED
Parallel Use
Single Use
6.85
PE
N
L
19.0
71.0
122.3
132.8
54.10
58.3
Terminals and Wiring
Screw Connector
Type
Solid Wire
1-6mm2
1-4mm2
AWG17-10
8mm
Stranded Wire
American Wire Gauge
Wire Stripping Length
Screwdriver (slotted / cross)
3.5mm
Recommended tightening torque 0.5Nm-0.8Nm
Tolerance: X.X 0.5mm
X.XX 0.25mm
www.recom-power.com
REV.: 0/2017
PDR-5
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
INSTALLATION
Mounting Instruction
Mounting
Releasing
1
DC OK +V +V -V -V
Vadj.
DC OK LED
Parallel Use
Single Use
N
PE
L
2
2
„Click“
1
Mounting Multiple Power Supplies
DC OK +V +V -V -V
DC OK +V +V -V -V
DC OK +V +V -V -V
Vadj.
Vadj.
Vadj.
DC OK LED
DC OK LED
DC OK LED
Parallel Use
Single Use
Parallel Use
Single Use
Parallel Use
Single Use
N
L
PE
N
L
PE
PE
N
L
20mm
20mm
leave 20mm gap between supplies
PDR-6
REV.: 0/2017
www.recom-power.com
REDIN480
AC/DC Converter
Specifications (measured @ ta = 25°C, rated Vin, rated load and after warm up)
Series
Parallel Operation & Phase Redundancy
L1 L2 L3 N PE
L N PE
+
-
~
~
~
+
+V
-V
DC
OK
~
~
~
-
+
+
-
+V
-V
DC
OK
Load
-
+
-
+V
-V
DC
OK
DC OK
Single Operation:
1) Make sure that the front panel switch is set to “single Use.”
2) The output voltage can be increased by trim pot to compensate any cable losses.
Parallel Operation:
1) Make sure that the front panel switch is set to “single Use” on each power supply.
2) Adjust each power supply to the exact same output voltage with same load and cooling conditions.
3) Set the front panel switches to “Parallel Use.” Use the same wire length for each power supply (star connection) and energize all units at the
same time to avoid triggering overload protection.
Derate the maximum output power to 90% of nominal ratings.
For operation with more than three power supplies in parallel or series operation, please contact RECOM technical support for advice.
Application Circuit
T10A
+V
-V
L
Input
Filter
Output
Filter
Power Stage
Protection
N
PE
DC
OK
Relay
OTP
Shut-
Down
LED
Vadj.
OVP
Shut-
Down
Output
Voltage
Regulation
OCP
Limit
Single /
Parallel
PACKAGKING INFORMATION
Parameter
Type
Value
140.0 x 88.0 x 142.0mm
1pcs
Packaging Dimension (LxWxH)
Packaging Quantity
cardboard box
cardboard box
Storage Temperature Range
Storage Humidity
-40°C to +85°C
5% - 95% RH
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit written
consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.
www.recom-power.com
REV.: 0/2017
PDR-7