REDIN45-12 [RECOM]

45 Watt DIN-Rail Power Supply;
REDIN45-12
型号: REDIN45-12
厂家: RECOM INTERNATIONAL POWER    RECOM INTERNATIONAL POWER
描述:

45 Watt DIN-Rail Power Supply

文件: 总6页 (文件大小:621K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
• Universal AC Input (85-264VAC)  
• Long 7 Year Warranty  
• Protections: SCP, OVP, OCP, OTP  
• 100% Full Load burn-in test  
Features  
AC/DC Converter  
• DC OK Indicator LED with Relay Contacts  
• cooling by free air convection, 5000m operation  
• UL, CSA & CE certified with CB Report  
REDIN45  
45 Watt  
DIN-Rail  
Power  
Supply  
Description  
This DIN-rail mounted power supply uses high reliability components to give a long, trouble-free life.The  
power supply can be end mounted to save space or side mounted for use in low-profile cabinets. Relay  
contacts simplify DC OK monitoring and the units can deliver 60W start-up power. The REDIN series is  
fully certified for industrial use and carries a 7-year warranty.  
Selection Guide  
Part  
Number  
Input  
Output  
Output  
Rated  
Efficiency  
typ.  
Max.  
Capacitive Load  
(µF)  
Voltage Range Voltage Trimming Voltage Current  
(VAC)  
85-264  
85-264  
(VDC)  
12  
24  
(VDC)  
12-15  
24-28  
(A)  
3.75  
1.875  
(%)  
85  
86  
REDIN45-12  
REDIN45-24  
18800  
4700  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
BASIC CHARACTERISTICS  
Parameter  
Condition  
Min.  
Typ.  
Max.  
Input Voltage Range  
all operating conditions  
85VAC  
264VAC  
300VAC  
375VDC  
max. Input Voltage  
max. 1 second  
Output Voltage Adjustment  
(Factory Setting) (1)  
12Vout  
24Vout  
12-15VDC (12V 5ꢀ)  
24-28VDC (24V 5ꢀ)  
full load, 115VAC  
full load, 230VAC  
1.35A  
0.75A  
Input Current  
E224736  
cold start at 25°C, 115VAC  
cold start at 25°C, 230VAC  
40A  
60A  
Inrush Current  
standard (with Relay)  
/NR option (no Relay)  
<1000mW  
<500mW  
No Load Power Consumption  
Start Up time  
Rise time  
cold start, 230VAC  
cold start, 230VAC  
500ms  
20ms  
1000ms  
CB-Report  
UL-60950-1 Certified  
UL-508 Certified  
IEC-60950-1 Certified  
EN-60715 Compliant  
EN-50022 Compliant  
CSA C22.2 No. 60950-1-07 Certified  
full load, 115VAC  
full load, 230VAC  
20ms  
50ms  
Hold-up time  
Input Frequency Range  
Operating Frequency Range  
Efficiency  
47Hz  
63Hz  
65kHz  
see Selection Guide  
12Vout  
24Vout  
60mVp-p  
75mVp-p  
Output Ripple and Noise(2)  
Over Load  
all operating conditions  
140ꢀ for 5 seconds max.  
Notes:  
Note1: For more details refer to Vadj. Derating Graph  
Note2: Ripple and Noise are measured at 20MHz bandwidth by using a 12” twisted pair-wire terminated with 0.1µF &  
47µF parallel capacitor.  
continued on next page  
Refer to Applications Notes  
www.recom-power.com  
REV.: 3/2016  
PA-1  
REDIN45  
AC/DC Converter  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
Series  
Efficiency vs. Load  
REDIN45-12  
REDIN45-24  
90  
90  
80  
70  
60  
50  
80  
70  
60  
50  
40  
40  
30  
20  
10  
0
85VAC  
85VAC  
30  
20  
10  
0
115VAC  
230VAC  
264VAC  
115VAC  
230VAC  
264VAC  
3
3.75  
1.5 1.875  
0
1
2
0
0.5  
1
Load (A)  
Load (A)  
Vadj. Derating  
100  
80  
45W max.  
Vadj.  
12  
(24)  
15  
(28)  
Output Voltage (V)  
REGULATION  
Parameter  
Condition  
Value  
Line Regulation  
Load Regulation  
Transient Response(3)  
0.1 typ. / 1ꢀ max.  
0.1 typ. / 1ꢀ max.  
12Vout (step load change: 1.875A - 3.75A)  
24Vout (step load change: 0.937A - 1.875A)  
5ꢀ typ.  
5ꢀ typ.  
Dwell Time  
Slew Rate  
100Hz & 1kHz 50ꢀ duty  
0.5A / µs  
Notes:  
Note3:  
Transient Response + E-CAP loading 3300µF. Other specs with resistive load only.  
PROTECTION  
Parameter  
Input Fuse  
Condition  
Value  
T2.5A, slow blow type  
Short Circuit Protection (SCP)  
Hiccup  
auto-recovery after fault condition  
12Vout  
24Vout  
18VDC max., shut-down latch-off o/p voltage, re-power on to recover  
35VDC max., shut-down latch-off o/p voltage, re-power on to recover  
Over Voltage Protection (OVP)  
Over Current Protection (OCP)  
150ꢀ typ., auto-recovery after fault condition  
Over Temperature Protection (OTP)  
detect on inside ambient  
105°C 5ꢀ, shut-down latch-off o/p voltage, re-power on to recover  
I/P to O/P  
I/P to FG  
O/P to FG  
3.75kVAC / 1 minute  
1.88kVAC / 1 minute  
0.5kVAC / 1 minute  
100MW min.  
Isolation Voltage  
Isolation Resistance  
Leakage Current  
500VDC, 70ꢀ RH, I/P to O/P; I/P to FG; O/P to FG  
240VAC  
<1.0mA  
Relay Contacts  
LED/Relay  
1A, 30VDC / 120VAC  
ON if Vout = 11-16V (12V) / 22-30V (24V)  
Power OK LED  
PA-2  
REV.: 3/2016  
www.recom-power.com  
REDIN45  
AC/DC Converter  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
Series  
ENVIRONMENTAL  
Parameter  
Condition  
with derating  
Value  
-20°C to +70°C (see graph)  
20ꢀ - 90ꢀRH  
Operating Temperature Range  
Operating Humidity  
Vibration  
non-condensing  
10-500Hz 2G, 60min.  
10G / 11ms, along X, Y and Z axis  
5000m  
Shock  
3 times each axis  
see derating graph  
Altitude  
MTBF (+25°C)  
Design Lifetime (+40°C)  
MIL-HDBK-217F, 115VAC, 60Hz, 75ꢀ load  
200 x 10³ hours  
87.6 x 10³ hours  
Derating Graph  
Vin 100VAC  
Vin > 100VAC  
100  
90  
100  
24VDC  
24VDC  
12VDC  
90  
80  
80  
12VDC  
70  
70  
60  
50  
40  
60  
50  
40  
30  
20  
10  
0
30  
20  
10  
0
-20  
-10  
10  
30  
50  
70  
-20  
-10  
10  
30  
50  
70  
Temperature (°C)  
Temperature (°C)  
Typical Characteristics  
REDIN45-12  
REDIN45-24  
35°C  
50°C  
35°C  
5000  
4000  
3000  
5000  
4000  
3000  
40°C  
(45W)  
(45W)  
2000  
2000  
20  
40  
60  
80  
100  
20  
40  
60  
80  
100  
www.recom-power.com  
REV.: 3/2016  
PA-3  
REDIN45  
AC/DC Converter  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
Series  
SAFETY AND CERTIFICATIONS  
Certificate Type (Safety)  
UL General Safety  
Report / File Number  
Standard  
UL-60950-1, 2nd Edition  
UL-1310  
E224736  
CSA General Safety  
C22.2 No. 60950-1-07, 2nd Edition  
Industrial Control Equipment  
General Use Power Supplies  
UL-508  
C22.2 No. 107.1  
E470721  
IEC/EN General Safety  
E224736  
E224736  
IEC/EN-60950-1, 2nd Edition  
GB 4943.1-2011  
Chinese Safety Standard  
EMC Compliance  
Report / Condition  
Standard / Criterion  
EN-55022, Class B  
EN-55024, Class B  
FCC15, Class B  
EMI Standard  
Report: HA150146  
ESD  
8kV Contact & Air Discharge  
10V/m, 80-3000MHz, 80ꢀ AM at 1kHz  
Level 2  
2kV / L-N, 4kV / L, N-FG  
10Vrms, 0.15-80MHz, 80ꢀ AM at 1kHz  
EN-61000-4-2, Criteria A  
EN-61000-4-3, Criteria A  
EN-61000-4-4, Criteria A  
EN-61000-4-5, Criteria A  
EN-61000-4-6, Criteria A  
EN-61000-4-8, Criteria A  
EN-61000-4-11, Criteria A  
EN-61000-4-11, Criteria B  
EN-61000-4-11, Criteria B  
EN-61000-3-2  
Radiated Immunity  
Fast Transient  
Surge  
Conducted Immunity  
Power frequency magnetic field immunity test  
Noise Immunity  
40ꢀ reduction, 200ms  
70ꢀ reduction, 500ms  
90ꢀ reduction, 5s  
Harmonic Immunity  
Voltage Flicker  
not applicable input below 75W  
EN-61000-3-3  
DIMENSION and PHYSICAL CHARACTERISTICS  
Parameter  
Case Material  
Type  
Value  
UL94V-0 plastic  
45.1 x 92.0 x 101.2mm  
332g  
Paclage Dimension (WxHxD)  
Package Weight  
Dimension Drawing (mm)  
1±1.ꢀ  
+V -V  
DC OK  
DC OK  
TRIM  
Front Side  
FG N  
L
45.1  
continued on next page  
REV.: 3/2016  
PA-4  
www.recom-power.com  
REDIN45  
AC/DC Converter  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
Series  
Dimension Drawing (mm)  
DIN-RAIL mounting bracket  
(75mm) included  
7.5±±.ꢀ  
75±±.ꢁ  
6.ꢁ±±.ꢀ  
ꢁ5±±.1  
ꢀ5.±  
1±±.±5  
18±±.ꢀ  
ꢀ5.±  
INSTALLATION  
END MOUNTING  
SIDE MOUNTING  
+V -V  
DC OK  
Front Side  
FG N  
L
End Latch  
Release  
Side Latch  
Release  
Tolerance: ±±.5ꢂꢂ  
Mounting Instruction  
Releasing  
Mounting  
1
Front Side  
2
FG  
N L  
2
„Click“  
1
continued on next page  
REV.: 3/2016  
www.recom-power.com  
PA-5  
REDIN45  
AC/DC Converter  
Specifications (measured at T = 25°C, 230VAC, full load and after warm up)  
A
Series  
Mounting Multiple Power Supplies  
FG N  
L
FG N  
L
FG N L  
0mm  
0mm  
no spacers between  
supplies required  
Functional Diagram  
T2.5A  
+V  
L
Input  
Filter  
Output  
Filter  
Power Stage  
Protection  
N
-V  
E
DC  
OK  
Relay  
OTP  
Shut-  
Down  
LED  
OVP  
Shut-  
Down  
Outoput  
Voltage  
Regulation  
OCP  
Limit  
Vadj.  
PACKAGING INFORMATION  
Parameter  
Type  
Value  
Packaging Dimension (LxWxH)  
Packaging Quantity  
Cardboard Box  
310 x 285 x 252mm  
30pcs  
Storage Temperature Range  
Storage Humidity  
-30°C to +85°C  
10ꢀ - 90ꢀ RH  
The product information and specifications are subject to change without prior notice. RECOM products are not authorized for use in safety-critical applications (such as life support) without RECOM’s explicit written  
consent. A safety-critical application is defined as an application where a failure of a RECOM product may reasonably be expected to endanger or cause loss of life, inflict bodily harm or damage property. The buyer  
shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized use of RECOM products in such safety-critical applications.  
PA-6  
REV.: 3/2016  
www.recom-power.com  

相关型号:

REDIN45-24

45 Watt DIN-Rail Power Supply
RECOM

REDIN480

480 Watt DIN-Rail Power Supply
RECOM

REDIN480-24

480 Watt DIN-Rail Power Supply
RECOM

REDIN480-24/3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-3AC

480 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN480-48

480 Watt DIN-Rail Power Supply
RECOM

REDIN60

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-12

60 Watt DIN-Rail Power Supply
RECOM

REDIN60-24

60 Watt DIN-Rail Power Supply
RECOM

REDIN960-24/3AC

960 Watt 3 Phase DIN-Rail Power Supply
RECOM

REDIN960-3AC

960 Watt 3 Phase DIN-Rail Power Supply
RECOM

REE-0505S

LOW COST 1W CONVERTER
RECOM