• 2 and 3-phase operation
Features
• Input voltage range: 320 – 575VAC
• Output trim range: 22.5 – 29.5VDC
• High electrical strength; high reliability
• Permanent overload and short-circuit protection
• Parallel operation capability
AC/DC Converter
DIN-Rail
Series
REDIN120/3AC
• International safety certification listing
Description
120 Watt
The REDIN/3AC is a series of rugged DIN rail power supplies for two and three-phase mains
operation from 320 to 575Vac without the need of a neutral connection. Four versions with a
maximum current limited output deliver 5A, 10A, 20A or 40A without derating up to +55°C. The output
can be grounded via a third common output terminal.The LED signal on the front panel indicates that the
output voltage remains within the wide adjustable range from 22.5 to 29.5Vdc. The units are covered by
international safety certificates and are intended for worldwide use. In power-hungry applications, the
units can be connected in parallel with no need for additional components.
3 Phase
DIN-Rail
Power Supply
Selection Guide
Part
nom. Input
Voltage Range
[VAC]
Output
Voltage
[VDC]
Output
Adjustability
[VDC]
Rated
Current
[A]
Efficiency (1)
typ.
Number
[%]
REDIN120-24/3AC
400 - 500
24
22.5 - 29.5
5
89
Notes:
Note1: Efficiency is tested at nominal input and full load at +25°C ambient
Model Numbering
REDIN120-24/3AC
Output Voltage
nom. Output Power
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
E196683
E470721
BASIC CHARACTERISTICS
UL60950-1 certified
Parameter
Condition
Min.
Typ.
Max.
UL508 certified
3 phase operation
2 phase operation
320VAC
360VAC
400VAC
400VAC
575VAC
575VAC
EN60950-1 certified
Input Voltage Range
CSA C22.2 No. 60950-01 certified
EN55011 compliant
400VAC
500VAC
3 x 300mA
3 x 300mA
3 phase operation
2 phase operation
EN50121-4 compliant
CSA C22.2 No.107 certified
EN61000-6-2 compliant
EN61000-6-3 compliant
Input Current
400VAC
500VAC
2 x 650mA
2 x 500mA
Inrush Current
15A
Return Voltage Immunity
No Load Power Consumption
Input Frequency Range
Output Voltage Trimming
Minimum Load
24Vout
35VDC
4W
65Hz
45Hz
22.5VDC
0%
29.5VDC
Start-up time
2/3 phase operation, 400VAC
1s
Rise time
2ms
400VAC
480VAC
20ms
30ms
Hold-up time
Output Ripple & Noise
measured at 20MHz BW
30mVp-p
continued on next page
www.recom-power.com
REV.: 0/2018
PDR-1
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
Efficiency vs. Load @ 3 Phase Operation
Power Dissipation vs. Load @ 3 Phase Operation
100
90
80
70
60
50
40
30
20
10
0
20
18
16
14
12
10
8
6
360V
400V
480V
4
360V
400V
480V
2
0
0
10 20 30 40 50 60 70 80 90 100
0
10 20 30 40 50 60 70 80 90 100
Output Load [%]
Output Load [%]
REGULATION
Parameter
Condition
Value
Output Accuracy
Line Regulation
Load Regulation
1.0% max.
0.1% typ.
10% change in input voltage
10% - 100% load
1.0% typꢀ 2.0% max.
25% load step change
recovery time
200mV typ.
50ms typ.
Transient Response
Accuracy vs. Load
1.0
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1.0
0
10 20 30 40 50 60 70 80 90 100
Output Load [%]
www.recom-power.com
REV.: 0/2018
PDR-2
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
PROTECTIONS
Parameter
Type
Value
Input Fuse
internal
F4A, fast blow
3x 6A (charactersitics B)
3x 10A (charactersitics B)
3x 16A (charactersitics B)
Recommended backup fuse for mains protection
Short Circuit Protection (SCP)
Over Voltage Protection (OVP)
Over Voltage Category (OVC)
Over Temperature Protection (OTP)
Over Current Protection (OCP)
Power OK LED
below 100mΩ
>120% typ. power limiting
>145% typ. auto recovery
OVC II
refer to note 2
>120% typ. auto recovery
Vout >21.5V
“DC OK” Light green
Class of Equipment
Class I
I/P to O/P
O/P to PE
4242VDC
Isolation Voltage
tested for 1 minute
2348VDC
Isolation Resistance
Insultaion Grade
10MΩ min.
reinforced
Notes:
Note2: Under thermal overload conditions, the device does not switch offꢀ instead, the output current is limited as much as necessary to
return internal operating temperatures to safe limits. After the device cools down, full output capacity is automatically restored.
ENVIRONMENTAL
Parameter
Condition
Value
Operating Temperature Range
Maximum Case Temperature
Temperature Coefficient
Operating Altitude
Operating Humidity
IP Rating
without derating (@ natural convection 0.1m/s) (see graph)
-25°C to +55°C
+105°C
0.05%/°C
2000m
non-condensing at 25°C
according to EN50187
5%-95% RH max.
IP20
Pollution Degree
Shock
PD2
30G in all directions
Vibration
<15Hz, amplitute 2.5mm 15Hz to 150Hz, 2.3G, 90min.
+25°C
according to IEC61709
+55°C
500 x 103 hours
60 x 103 hours
MTBF
Derating Graph
(@ Chamber and natural convection 0.1m/s)
100
93.8
80
62.5
60
40
24Vout
22.5Vout
29.5Vout
20
0
-25 -20
0
20
40
55 60 70 80
Ambient Temperature [°C]
www.recom-power.com
REV.: 0/2018
PDR-3
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
SAFETY AND CERTIFICATIONS
Certificate Type
Report / File Number
Standard
UL60950-1, 1st Edition: 2007
CSA C22.2 No. 60950-1, 1st Edition: 2006
Information Technology Equipment, General Requirements for Safety
E196683
UL508, 17th-Edition
CSA C22.2 No. 107.1-01, 3rd-Edition
Industrial Control Equipment
E470721
Information Technology Equipment - General Requirments for Safety (LVD)
EN60950-1:2006+A2:2013
TP TC 004/2011
EAC
RU-AT.37.02367
RoHs2
RoHs 2011/65/EU
EMC Compliance
Report / Condition
Standard / Criterion
Industrial, scientific and medical equipment – Radio frequency distur-
bance characteristics – Limits and methods of measurement
EN55011:1989 + A2:2002, Class B
Air 2, 4, 8kV
Contact 2, 4, 6, 8kV
ESD Electrostatic discharge immunity test
EN61000-4-2:1995 + A1:2001, Criteria A
EN61000-4-3:2002 + A1:2006, Criteria A
Radiated, radio-frequency, electromagnetic field immunity test
10V/m (80 - 3000MHz)
AC Power Port: 4kV
PE 4kV
Fast Transient and Burst Immunity
EN61000-4-4:1995 + A2:2004, Criteria A
DC Power Port 2kV
AC Power Port: L-N 0.5, 1, 2kV
L-PE 4kV
DC Power Port 0.5, 1, 2kV
AC Power Port 10V
Surge Immunity
EN61000-4-5:1995 + A1:2006, Criteria A, B (L-PE)
EN61000-4-6:1996 + A1:2001, Criteria A
Immunity to conducted disturbances, induced by radio-frequency fields
DC Power Port 10V
Voltage Dips >95%
Voltage Dips 60%
Voltage Dips 30%
EN61000-4-11:2004, Criteria A
EN61000-4-11:2004, Criteria B
EN61000-4-11:2004, Criteria B
EN61000-4-11:2004, Criteria B
Voltage Dips and Interruptions
Voltage Interruptions > 95%
Limits of Harmonic Current Emissions
Limits of Voltage Fluctuations & Flicker
EN61000-3-2:2000, Class A
EN61000-3-3:1995 + A1:2001
Railway applications – Electromagnetic compatibility Part 4: Emission
and immunity of the signalling and telecommunications apparatus
EN50121-4:2006
EMC Compliance (Generic Standards)
Report / Condition
Standard / Criterion
Generic standards - Immunity standard for industrial environments
EN61000-6-2:2005
Generic standards - Emission standard for residential, commercial and
light-industrial environments
EN61000-6-3:2007 + A1:2011
DIMENSION and PHYSICAL CHARACTERISTICS
Parameter
Type
Value
case
cover
steel sheet, zinc-plated
aluminium
Material
Unit Dimension (LxWxH)
Unit Weight
115.0 x 40.0 x 130.0mm
600g typ.
continued on next page
REV.: 0/2018
www.recom-power.com
PDR-4
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
Dimension Drawing (mm)
-V
-V
-V
+V
+V
DC OK LED
VAdj.
11.5
L1
L2
L3
11.2
115.0
120.3
27.2
40.0
Terminals and Wiring
Screw Connector
Type
Solid Wire
Stranded Wire(3)
0.2 - 2.5mm2
0.2 - 2.5mm2
AWG 24-14
AWG 16-12
9mm
Notes:
Note3: The use of sleeve or ferrule terminations is recommended
American Wire Gauge Input
Amerivan Wire Gauge Output
Wire Stripping Length
Screwdriver (slotted / cross)
3.5mm
Recommended tightening torque 0.4Nm-0.5Nm
Tolerance: X.X 0.5mm
www.recom-power.com
REV.: 0/2018
PDR-5
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
INSTALLATION and APPLICATION
Mounting Instruction (4)
1
Mounting
Releasing
2
2
„Click“
1
Mounting Multiple Power Supplies (5)
please mind a gap of 50mm in vertical direction
-V
-V
-V
-V
-V
-V
-V
-V
-V
+V
+V
+V
+V
+V
+V
DC OK LED
VAdj.
DC OK LED
VAdj.
DC OK LED
VAdj.
L1
L2
L3
L1
L2
L3
L1
L2
L3
no gap necessary between modules
Notes:
Note4: The power supply unit can be snapped onto all DIN Rails in according with EN60715 and has to be mounted vertically
Note5: To guarantee sufficient convection, it is recommended to mint a 50.0 mm gap in vertical direction
www.recom-power.com
REV.: 0/2018
PDR-6
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
2 Phase and 3 Phase Operation
3 Phase
2 Phase
L1 L2 L3 PE
L1 L2 L3 PE
+V
-V
+V
-V
~
~
~
+V
-V
Parallel Operation and Phase Redundancy
L1 L2 L3 PE
Parallel Operation
1) Adjust each power supply to the exact same output voltage with same
load and cooling conditions.
~
2) Use the same wire length for each power supply (star connection) and
energize all units at the same time to avoid triggering overload protection.
3) To prevent high reverse currents in the event of a secondary output
fault, it is recommended to install a protective circuit at the output of each
device when more than two power supplies are connected in parallel
(e.g. decoupling diode or DC fuse).
Load:
90% of n x INom
+V
~
~
-V
For n parallel connected devices, the output current can be increased
to 90% of n x Inom. A maximum of 5 devices can be connected in parallel.
L1 L2 L3 PE
+V -V
~
~
Phase redundancy
1) If any single phase fails, operation is still guaranteed.
Max. load
120W
www.recom-power.com
REV.: 0/2018
PDR-7
REDIN120/3AC
AC/DC Converter
Series
Specifications (measured @ Ta= 25°C, nom.Vin, full load and after warm-up unless otherwise stated)
Block Diagramm
L1
+V
-V
F4A
Input
Filter
Output
Filter
Power Stage
Protection
L2
L3
LED
OTP
Shut-
Down
Output
Voltage
Vadj.
Regulation
OVP
OCP
Limit
Shut-
Down
PACKAGING INFORMATION
Parameter
Type
Value
155.0 x 170.0 x 52.0mm
1pcs
Packaging Dimension (LxWxH)
Packaging Quantity
cardboard box
Storage Temperature Range
Storage Humidity
-40°C to +85°C
non-condensing
5% - 95% RH max.
The product information and specifications may be subject to changes even without prior written notice.The product has been designed for various applications; its suitability lies in the responsibility of each customer. The
products are not authorized for use in safety-critical applications without RECOM’s explicit written consent. A safety-critical application is an application where a failure may reasonably be expected to endanger or cause
loss of life, inflict bodily harm or damage property. The applicant shall indemnify and hold harmless RECOM, its affiliated companies and its representatives against any damage claims in connection with the unauthorized
use of RECOM products in such safety-critical applications.
www.recom-power.com
REV.: 0/2018
PDR-8
相关型号:
©2020 ICPDF网 联系我们和版权申明