G3DZ-F4B [OMRON]

Easy-to-use, Space-saving Terminal Relay with Four-point Output; 易于使用,节省空间的终端继电器,具有四个输出点
G3DZ-F4B
型号: G3DZ-F4B
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Easy-to-use, Space-saving Terminal Relay with Four-point Output
易于使用,节省空间的终端继电器,具有四个输出点

继电器
文件: 总8页 (文件大小:76K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
G6D-F4B/G3DZ-F4B  
Terminal Relay  
Easy-to-use, Space-saving Terminal  
Relay with Four-point Output  
Almost the same size as PYF Socket: 31 x 35 x  
68 mm (W x H x D)  
Each terminal circuit (with coil or contact) is  
independent from one another.  
Short Bar ensures easy connection of common and  
adjacent terminals.  
Provided with a terminal cover that prevents  
electric-shock accidents.  
Relay and MOS FET relay models are available.  
LED operation indicator.  
Built-in diode absorbs coil surge.  
Mounts either on DIN track or screws.  
Tool for easy mounting or removal of Relays  
provided.  
Ordering Information  
Model Number Legend:  
G6D/G3DZ-jj  
1
2
1. Terminal Form  
2. Number of Relays Mounted  
4B:  
F:  
Flat type  
4
Output  
Relay output  
Contact configuration  
Terminals  
Rated coil voltage  
Model  
SPST-NO   
4
Phillips head screw  
terminal  
G6D-F4B  
12 VDC  
24 VDC  
12 VDC  
24 VDC  
Power MOS FET relay  
output  
G3DZ-F4B  
Note: When ordering add the rated coil voltage to the model number  
.
Example: G6D-F4B 24 VDC  
Rated coil voltage  
Accessories (Order Separately)  
Replacement Relays  
Applicable  
G6D-F4B  
Terminal Relay  
Rated voltage  
Model  
G6D-1A (see note)  
12 VDC  
24 VDC  
12 VDC  
24 VDC  
12 VDC  
24 VDC  
G6D-1A-AP (see note)  
G3DZ-2R6PL  
G3DZ-F4B  
Note: Error rate (P level) for the G6D-1A is 5 V at 10 mA and that for the G6D-1A-AP is 5 V at 1 mA.  
Short Bar  
Applicable  
G6D-F4B  
G3DZ-F4B  
Terminal Relay  
Model  
G6D-4-SB  
1
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
Specifications  
Ratings  
Coil Ratings (per G6D Relay)  
Rated voltage  
Rated current  
Coil resistance  
Must operate  
voltage  
Must release  
voltage  
Max. voltage  
130%  
Power  
consumption  
70% max.  
(see note 1)  
10% min.  
Approx. 200 mW  
12 VDC  
24 VDC  
18.7 mA  
10.5 mA  
720  
2,880  
Note: 1. The must operate voltage is 75% or less of the rated voltage if the Relay is mounted upside down.  
2. Rated current and coil resistance were measured at a coil temperature of 23°C with a tolerance of ±10%.  
3. Operating characteristics were measured at a coil temperature of 23°C.  
4. The maximum allowable voltage is the maximum value of the allowable voltage range for the relay coil operating power supply.  
There is no continuous allowance.  
5. The rated current includes the terminal’s LED current.  
Contact Ratings (per G6D Relay)  
Item  
Resistive load (cosφ = 1)  
Rated load  
3 A at 250 VAC, 3 A at 30 VDC  
Rated carry current  
5 A  
Max. switching voltage  
250 VAC, 30 VDC  
5 A  
Max. switching current  
Max. permissible capacity (reference value)  
Error rate (reference value) (see note)  
1,250 VA, 150 W  
5 VDC, 1 mA  
Note: This value is for a switching frequency of 120 times per minute.  
Power MOS FET Relay Specifications  
Input (per G3DZ Power MOS FET Relay)  
Rated voltage  
Operating voltage  
Must operate  
voltage level  
Must release  
voltage level  
Input impedance  
Rated current  
1 VDC min.  
12 VDC  
24 VDC  
9.6 to 14.4 VDC  
19.2 to 28.8 VDC  
9.6 VDC max.  
19.2 VDC max.  
2 k±20%  
4 k±20%  
8.0 mA±20%  
8.2 mA±20%  
Note: The rated current includes the terminal’s LED current.  
Output (per G3DZ Power MOS FET Relay)  
Load voltage  
Load current  
100 to 0.3 A  
Inrush current  
3 to 264 VAC  
3 to 125 VDC  
µ
6 A (10 ms)  
2
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
Characteristics  
G6D-F4B  
Item  
Relay output  
Contact resistance (see note 2)  
Must operate time (see note 3)  
Release time (see note 3)  
Insulation resistance  
100 mmax.  
10 ms max.  
10 ms max.  
1,000 Mmin. (at 500 VDC)  
Dielectric strength  
2,000 VAC, 50/60 Hz for 1 min between coil and contacts.  
750 VAC, 50/60 Hz for 1 min between contacts of same polarity  
Impulse withstand voltage (between 4,000 V (1.2  
coil and contacts)  
 
50 µs)  
Vibration resistance  
Destruction:10 to 55 Hz, 1.5-mm double amplitude  
Malfunction:10 to 55 Hz, 1.5-mm double amplitude  
2
Shock resistance  
Life expectancy  
Destruction:500 m/s  
2
Malfunction:100 m/s  
Mechanical:20,000,000 operations min. (at 18,000 operations/hr)  
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)  
100,000 operations min. (3 A at 30 VDC, resistive load) (at 1,800 operations /hr)  
Ambient temperature  
Operating: –25°C to 55  
°
C (with no icing)  
C (with no icing)  
Storage: –25°C to 55  
°
Ambient humidity  
Weight  
Operating: 45% to 85%  
Approx. 65 g  
Note: 1. The above values are initial values.  
2. Measurement condition: 1 A at 5 VDC  
3. Ambient temperature condition: 23°C  
G3DZ-F4B  
Power MOS FET relay output  
Item  
Must operate time  
10 ms max.  
15 ms max.  
Release time  
Output ON-resistance  
Leakage current at OFF state  
Insulation resistance  
Dielectric strength  
2.4  
10  
max.  
A max. (at 125 VDC)  
min. (at 500 VDC)  
µ
100 M  
2,000 VAC, 50/60 Hz for 1 min between input and output terminals  
10 to 55 Hz, 1.5-mm double amplitude  
Vibration resistance  
2
Shock resistance  
500 m/s  
Ambient temperature  
Operating: –25°C to 55  
°
C (with no icing)  
C (with no icing)  
Storage: –25°C to 55  
°
Ambient humidity  
Weight  
Operating: 45% to 85%  
Approx. 65 g  
3
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
Engineering Data  
G6D-F4B  
Max. Switching Capacity  
Life Expectancy  
250 VAC/30 VDC resistive load  
AC resistive load  
DC resistive load  
Switching current (A)  
Switching voltage (V)  
G3DZ-F4B  
Load Current vs. Ambient Temperature  
Characteristics  
Inrush Current Resistivity  
Non-repetitive (Keep the inrush current to half the rated value  
if it occurs repetitively.)  
Energizing time (ms)  
Ambient temperature (°C)  
4
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
Dimensions  
Note: All units are in millimeters unless otherwise indicated.  
G6D-F4B  
G3DZ-F4B  
Mounting Dimensions  
16, M3 Phillips  
head screws  
Two, 4 dia. or M3.5 holes  
Terminal Arrangement/  
Internal Connections  
(Top View)  
Input side  
68 max.  
Output side  
31 max.  
35 max.  
Note: Make sure that the polarity  
of the coil is correct.  
Accessories  
G6D-4-SB Short Bar  
Applicable  
model  
Model  
G6D-4-SB  
G6D-F4B  
G3DZ-F4B  
5
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
Precautions  
Wiring  
Coil Voltage  
Be sure to turn OFF the power when wiring the Unit and do not touch  
the charged terminals of the Unit. Otherwise, an electric shock may  
result.  
Make sure not to impose voltage exceeding the permissible voltage  
on the coil continuously  
Do not connect any inductive load in parallel to the coil input as  
.
Do not apply overvoltage to the input terminals. Otherwise, the Unit  
may malfunction or burn.  
shown in the following example or power supply with a surge volt  
age. Otherwise, the surge absorption diode will be damaged.  
-
Relay Models  
Do not connect the Unit to loads exceeding the rated switching ca  
Do Not Use the Following Circuit  
-
pacity (switching voltage or current). Otherwise, faulty insulation,  
contact weld, or faulty contact of Relays, or damage to Relays may  
result, or the Relays may malfunction or burn.  
The life of Relays varies with the switching condition. Test the  
Relays under the actual operating conditions before using the  
Coil surge  
absorption  
diode  
Inductive load  
G6D coil  
Relays within the permissible switching frequency. The use of dete  
-
riorated Relays may result in the faulty insulation of the Relays or  
cause the Relays to burn.  
Do not use the Unit in locations with inflammable gas. Otherwise, a  
fire or explosion due to the heat of the Relays or sparks from the  
Relays may result when they are switched.  
Handling  
Do not drop, shock, or vibrate the Unit excessively. Otherwise, dam  
age to the Unit may result or the Unit may malfunction.  
-
SSR Output (Power MOS FET Relay Model)  
Do not connect the Unit to loads consuming a total current exceed  
-
Make sure that all the Relays are properly mounted before use.  
ing the rated output current of the Unit. Otherwise, the output ele-  
ment of the Unit may be damaged and a short or open-circuit mal  
function may result.  
-
Screw Tightening Torque  
Tighten each terminal screw to a torque of 0.78 to 1.18N  
S
m.  
m.  
If the Unit is connected to a DC inductive load, connect a diode to the  
Unit to protect the Unit from counter-electromotive voltage, other-  
Tighten each mounting screw to a torque of 0.59 to 0.98 N  
S
wise the counter-electromotive voltage may damage the output ele  
ment and a short or open-circuit malfunction may result.  
-
Installation Environment  
Do not install the Unit in the following locations. Otherwise, damage  
to the Unit may result or the Unit may malfunction.  
Correct Use  
Mounting  
When mounting two or more Units, reduce the current and ON duty  
and provide an appropriate distance between the Units so that the  
ambient temperature will not exceed 55°C.  
Locations with direct sunlight.  
Locations with an ambient temperature range not within –25°C to  
55°C.  
Locations with rapid temperature changes resulting in condensa-  
tion or locations with relative humidity ranges not within 45% to  
85%.  
Relay Replacement  
Use the Relay Removal Tool provided with the Unit to dismount a  
Relay.  
Locations with corrosive or inflammable gas.  
Locations with excessive dust, salinity, or metal powder  
.
Be sure to turn OFF the power to the Unit before replacing a Relay  
When mounting a Relay, insert the Relay vertically so that the relay  
terminals will come in contact with the socket contact pins properly  
.
Locations with vibration or shock affecting the Unit.  
Locations with water, oil, or chemical sprayed on the Unit.  
.
Do not mount Relays that are different to one another in voltage.  
Disassembly, Repair, and Modification  
Do not disassemble, repair, or modify the Unit. Otherwise, an elec  
-
Wiring  
tric shock may result or the Unit may malfunction.  
Pay utmost attention not to make mistakes with the polarity of the  
input terminals.  
6
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
7
G6D-F4B/G3DZ-F4B  
G6D-F4B/G3DZ-F4B  
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.  
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.  
Cat. No. J115-E1-1  
In the interest of product improvement, specifications are subject to change without notice.  
OMRON Corporation  
Industrial Automation Company  
Industrial Control Components Division  
28th Fl., Crystal Tower Bldg.,  
1-2-27, Shiromi, Chuo-ku,  
Printed in Japan  
0799-1M (0799)  
Osaka 540-6028 Japan  
a
Phone: (81)6-6949-6025 Fax: (81)6-6949-6029  
8

相关型号:

G3DZ-F4B12VDC

Power/Signal Relay
OMRON

G3DZ-F4B24VDC

Power/Signal Relay
OMRON

G3DZ2R6PLDC12

SSR Identical to the G6D in Size with a Maximum AC/DC Switching Current of 0.6 A
OMRON

G3F-202SN-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3F-203S-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3F-203SL-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3F-203SLN-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3F-203SN-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3FD-102S-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3FD-102SN-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3FD-X03S-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON

G3FD-X03SN-VD

International Standards for G3F Series, Same Profile as MY Power Relays
OMRON