G3DZ-F4B [OMRON]
Easy-to-use, Space-saving Terminal Relay with Four-point Output; 易于使用,节省空间的终端继电器,具有四个输出点型号: | G3DZ-F4B |
厂家: | OMRON ELECTRONICS LLC |
描述: | Easy-to-use, Space-saving Terminal Relay with Four-point Output |
文件: | 总8页 (文件大小:76K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
G6D-F4B/G3DZ-F4B
Terminal Relay
Easy-to-use, Space-saving Terminal
Relay with Four-point Output
Almost the same size as PYF Socket: 31 x 35 x
68 mm (W x H x D)
Each terminal circuit (with coil or contact) is
independent from one another.
Short Bar ensures easy connection of common and
adjacent terminals.
Provided with a terminal cover that prevents
electric-shock accidents.
Relay and MOS FET relay models are available.
LED operation indicator.
Built-in diode absorbs coil surge.
Mounts either on DIN track or screws.
Tool for easy mounting or removal of Relays
provided.
Ordering Information
Model Number Legend:
G6D/G3DZ-jj
1
2
1. Terminal Form
2. Number of Relays Mounted
4B:
F:
Flat type
4
Output
Relay output
Contact configuration
Terminals
Rated coil voltage
Model
SPST-NO
4
Phillips head screw
terminal
G6D-F4B
12 VDC
24 VDC
12 VDC
24 VDC
Power MOS FET relay
output
G3DZ-F4B
Note: When ordering add the rated coil voltage to the model number
.
Example: G6D-F4B 24 VDC
Rated coil voltage
Accessories (Order Separately)
Replacement Relays
Applicable
G6D-F4B
Terminal Relay
Rated voltage
Model
G6D-1A (see note)
12 VDC
24 VDC
12 VDC
24 VDC
12 VDC
24 VDC
G6D-1A-AP (see note)
G3DZ-2R6PL
G3DZ-F4B
Note: Error rate (P level) for the G6D-1A is 5 V at 10 mA and that for the G6D-1A-AP is 5 V at 1 mA.
Short Bar
Applicable
G6D-F4B
G3DZ-F4B
Terminal Relay
Model
G6D-4-SB
1
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
Specifications
Ratings
Coil Ratings (per G6D Relay)
Rated voltage
Rated current
Coil resistance
Must operate
voltage
Must release
voltage
Max. voltage
130%
Power
consumption
70% max.
(see note 1)
10% min.
Approx. 200 mW
12 VDC
24 VDC
18.7 mA
10.5 mA
720
Ω
2,880
Ω
Note: 1. The must operate voltage is 75% or less of the rated voltage if the Relay is mounted upside down.
2. Rated current and coil resistance were measured at a coil temperature of 23°C with a tolerance of ±10%.
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The maximum allowable voltage is the maximum value of the allowable voltage range for the relay coil operating power supply.
There is no continuous allowance.
5. The rated current includes the terminal’s LED current.
Contact Ratings (per G6D Relay)
Item
Resistive load (cosφ = 1)
Rated load
3 A at 250 VAC, 3 A at 30 VDC
Rated carry current
5 A
Max. switching voltage
250 VAC, 30 VDC
5 A
Max. switching current
Max. permissible capacity (reference value)
Error rate (reference value) (see note)
1,250 VA, 150 W
5 VDC, 1 mA
Note: This value is for a switching frequency of 120 times per minute.
Power MOS FET Relay Specifications
Input (per G3DZ Power MOS FET Relay)
Rated voltage
Operating voltage
Must operate
voltage level
Must release
voltage level
Input impedance
Rated current
1 VDC min.
12 VDC
24 VDC
9.6 to 14.4 VDC
19.2 to 28.8 VDC
9.6 VDC max.
19.2 VDC max.
2 kΩ±20%
4 kΩ±20%
8.0 mA±20%
8.2 mA±20%
Note: The rated current includes the terminal’s LED current.
Output (per G3DZ Power MOS FET Relay)
Load voltage
Load current
100 to 0.3 A
Inrush current
3 to 264 VAC
3 to 125 VDC
µ
6 A (10 ms)
2
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
Characteristics
G6D-F4B
Item
Relay output
Contact resistance (see note 2)
Must operate time (see note 3)
Release time (see note 3)
Insulation resistance
100 mΩ max.
10 ms max.
10 ms max.
1,000 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between coil and contacts.
750 VAC, 50/60 Hz for 1 min between contacts of same polarity
Impulse withstand voltage (between 4,000 V (1.2
coil and contacts)
50 µs)
Vibration resistance
Destruction:10 to 55 Hz, 1.5-mm double amplitude
Malfunction:10 to 55 Hz, 1.5-mm double amplitude
2
Shock resistance
Life expectancy
Destruction:500 m/s
2
Malfunction:100 m/s
Mechanical:20,000,000 operations min. (at 18,000 operations/hr)
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load)
100,000 operations min. (3 A at 30 VDC, resistive load) (at 1,800 operations /hr)
Ambient temperature
Operating: –25°C to 55
°
C (with no icing)
C (with no icing)
Storage: –25°C to 55
°
Ambient humidity
Weight
Operating: 45% to 85%
Approx. 65 g
Note: 1. The above values are initial values.
2. Measurement condition: 1 A at 5 VDC
3. Ambient temperature condition: 23°C
G3DZ-F4B
Power MOS FET relay output
Item
Must operate time
10 ms max.
15 ms max.
Release time
Output ON-resistance
Leakage current at OFF state
Insulation resistance
Dielectric strength
2.4
10
Ω
max.
A max. (at 125 VDC)
min. (at 500 VDC)
µ
100 M
Ω
2,000 VAC, 50/60 Hz for 1 min between input and output terminals
10 to 55 Hz, 1.5-mm double amplitude
Vibration resistance
2
Shock resistance
500 m/s
Ambient temperature
Operating: –25°C to 55
°
C (with no icing)
C (with no icing)
Storage: –25°C to 55
°
Ambient humidity
Weight
Operating: 45% to 85%
Approx. 65 g
3
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
Engineering Data
G6D-F4B
Max. Switching Capacity
Life Expectancy
250 VAC/30 VDC resistive load
AC resistive load
DC resistive load
Switching current (A)
Switching voltage (V)
G3DZ-F4B
Load Current vs. Ambient Temperature
Characteristics
Inrush Current Resistivity
Non-repetitive (Keep the inrush current to half the rated value
if it occurs repetitively.)
Energizing time (ms)
Ambient temperature (°C)
4
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
Dimensions
Note: All units are in millimeters unless otherwise indicated.
G6D-F4B
G3DZ-F4B
Mounting Dimensions
16, M3 Phillips
head screws
Two, 4 dia. or M3.5 holes
Terminal Arrangement/
Internal Connections
(Top View)
Input side
68 max.
Output side
31 max.
35 max.
Note: Make sure that the polarity
of the coil is correct.
Accessories
G6D-4-SB Short Bar
Applicable
model
Model
G6D-4-SB
G6D-F4B
G3DZ-F4B
5
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
Precautions
Wiring
Coil Voltage
Be sure to turn OFF the power when wiring the Unit and do not touch
the charged terminals of the Unit. Otherwise, an electric shock may
result.
Make sure not to impose voltage exceeding the permissible voltage
on the coil continuously
Do not connect any inductive load in parallel to the coil input as
.
Do not apply overvoltage to the input terminals. Otherwise, the Unit
may malfunction or burn.
shown in the following example or power supply with a surge volt
age. Otherwise, the surge absorption diode will be damaged.
-
Relay Models
Do not connect the Unit to loads exceeding the rated switching ca
Do Not Use the Following Circuit
-
pacity (switching voltage or current). Otherwise, faulty insulation,
contact weld, or faulty contact of Relays, or damage to Relays may
result, or the Relays may malfunction or burn.
The life of Relays varies with the switching condition. Test the
Relays under the actual operating conditions before using the
Coil surge
absorption
diode
Inductive load
G6D coil
Relays within the permissible switching frequency. The use of dete
-
riorated Relays may result in the faulty insulation of the Relays or
cause the Relays to burn.
Do not use the Unit in locations with inflammable gas. Otherwise, a
fire or explosion due to the heat of the Relays or sparks from the
Relays may result when they are switched.
Handling
Do not drop, shock, or vibrate the Unit excessively. Otherwise, dam
age to the Unit may result or the Unit may malfunction.
-
SSR Output (Power MOS FET Relay Model)
Do not connect the Unit to loads consuming a total current exceed
-
Make sure that all the Relays are properly mounted before use.
ing the rated output current of the Unit. Otherwise, the output ele-
ment of the Unit may be damaged and a short or open-circuit mal
function may result.
-
Screw Tightening Torque
Tighten each terminal screw to a torque of 0.78 to 1.18N
S
m.
m.
If the Unit is connected to a DC inductive load, connect a diode to the
Unit to protect the Unit from counter-electromotive voltage, other-
Tighten each mounting screw to a torque of 0.59 to 0.98 N
S
wise the counter-electromotive voltage may damage the output ele
ment and a short or open-circuit malfunction may result.
-
Installation Environment
Do not install the Unit in the following locations. Otherwise, damage
to the Unit may result or the Unit may malfunction.
Correct Use
Mounting
When mounting two or more Units, reduce the current and ON duty
and provide an appropriate distance between the Units so that the
ambient temperature will not exceed 55°C.
Locations with direct sunlight.
Locations with an ambient temperature range not within –25°C to
55°C.
Locations with rapid temperature changes resulting in condensa-
tion or locations with relative humidity ranges not within 45% to
85%.
Relay Replacement
Use the Relay Removal Tool provided with the Unit to dismount a
Relay.
Locations with corrosive or inflammable gas.
Locations with excessive dust, salinity, or metal powder
.
Be sure to turn OFF the power to the Unit before replacing a Relay
When mounting a Relay, insert the Relay vertically so that the relay
terminals will come in contact with the socket contact pins properly
.
Locations with vibration or shock affecting the Unit.
Locations with water, oil, or chemical sprayed on the Unit.
.
Do not mount Relays that are different to one another in voltage.
Disassembly, Repair, and Modification
Do not disassemble, repair, or modify the Unit. Otherwise, an elec
-
Wiring
tric shock may result or the Unit may malfunction.
Pay utmost attention not to make mistakes with the polarity of the
input terminals.
6
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
7
G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J115-E1-1
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
Industrial Control Components Division
28th Fl., Crystal Tower Bldg.,
1-2-27, Shiromi, Chuo-ku,
Printed in Japan
0799-1M (0799)
Osaka 540-6028 Japan
a
Phone: (81)6-6949-6025 Fax: (81)6-6949-6029
8
相关型号:
G3DZ2R6PLDC12
SSR Identical to the G6D in Size with a Maximum AC/DC Switching Current of 0.6 A
OMRON
©2020 ICPDF网 联系我们和版权申明