DMS-PS1-CM-C [MURATA]
0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors; 0-5V和0-10V输入3.5位, LED显示屏过程控制监视器型号: | DMS-PS1-CM-C |
厂家: | muRata |
描述: | 0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors |
文件: | 总4页 (文件大小:213K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
DMS-20PC-0/5 Series
0-5V and 0-10V Input 3½ Digit, LED
Display Process Control Monitors
DATEL's DMS-20PC-0/5 Series are the world's smallest, full-featured, 0-5V input
process control monitors. Their large, easy-to-read, 0.37"/9.4mm LED displays are
available in a choice of 4 LED color/intensity options: standard red, standard green,
super-bright red, and low-power red. Two power supply input ranges are also available:
the industry-standard +5V and a wide-range +5V to +40V (which typically draws 9mA at
+24V).
Gain (span) and offset (zero) adjustments are performed with on-board, precision,
20-turn potentiometers. All decimal-point and range-change selections are made on an
8-position, vibration-resistant, gold-plated DIP switch. Unlike competitive meters, there
are no jumpers or solder gaps to open or close, and to further enhance reliability, the
entire assembly utilizes 100% soldered connections. Both power-supply and input-signal
connections are made via reliable screw-type terminal blocks.
FEATURES
N
Accepts 0-5V and 0-10V inputs
N
Large, easy-to-read, 0.37"/9.4mm LED display
N
Choice of 5 LED power/color options
N
High input impedance, 100kΩ
N
+5V to +40V model draws 9mA typ.
N
Miniature size: 1.38" x 1.25" x 0.95"
N
High-quality, 20-turn, span (gain) and zero (offset)
adjustments
The DMS-20PC-0/5's DIP switch and potentiometers accommodate hundreds of input-
voltage/output-reading combinations. This practically eliminates the need for more costly,
long-lead-time, factory "specials" in applications which use several different-range meters.
A supplied bezel assembly––featuring metal fasteners and a rubber gasket––simplifies
panel mounting and also provides excellent resistance to environmental dust and moisture.
All these outstanding features combine to make the DMS-20PC-0/5 the perfect meter for
prototype and OEM, 0-5V input, process control monitoring.
N
DIP-switch selectable range and decimal points
N
Vibration-resistant package; Reliable screw-terminal
input connections
N
Hundreds of different input/readout combinations
SIMPLIFIED SCHEMATIC DIAGRAM
DMS-20PC-0/5
3½ Digit
DATA
A/D Converter
–5V +5V
DP1 DP2 DP3
N.C.
R3
R7
Zero
Adjust
Gain
Adjust
ON
DIP Switches
1
4
2
3
5
6
7
8
N.C.
+5V
–5V
DC/DC
Converter
Band-Gap
Reference
Circuit
1
2
1
2
TB1
TB2
+
–
+
–
+5V
–5V
HI LO
Signal Input
+V –V
Power Supply Input
For full details go to
www.murata-ps.com/rohs
Figure 1. DMS-20PC-0/5 simplified schematic
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
MPM_DMS20pc_5V.B04 Page 1 of 4
DMS-20PC-0/5 Series
0-5V and 0-10V Input 3½ Digit, LED
Display Process Control Monitors
Performance/Functional Specifications
Typical at TA = +25°C, unless otherwise noted.
TECHNICAL NOTES
1. Input Configuration: The DMS-20PC-0/5 has its input low terminal
(TB1 "LO") internally connected to the power supply ground terminal
(TB2 "–V"). This connection effectively places the meter's input in a
single-ended configuration. In some applications, single-ended inputs
can cause ground-loop induced errors (the meter's display becomes
unstable or bounces). This occurs because the LED drive currents
flow through both the –V terminal and the signal LO terminal.
Inputs
Min.
4.9
100
–
Typ.
5.0
–
Max.
5.1
Units
Volts
kΩ
Full Scale Input Range ~
Input Impedence
140
40
–
Volts
Overvoltage Protection
Performance
Sampling Rate
2.5 reading per second
0.05%FS 1 Count
If suspected ground-loop errors are encountered, and the input signal
LO terminal is externally connected to –V somewhere else in the
system, try removing the connection to TB1 "LO". Inputs which have
no ground-return connection to –V (commonly referred to as "floating
inputs") must have their most negative potential tied to TB1 "LO".
Please consult DATEL for more information.
Accuracy (1 minute warm-up):
Temperature Drift (0 to +60°C)
Power Supply Requirements
DMS-20PC-0/5-5RS (@90mA max.)
–
0.15
0.3
Cnts/°C
+4.75
+5.00
+5.00
+5.00
+5.00
–
+5.25 Volts
+5.25 Volts
+5.25 Volts
+5.25 Volts
+40.0 Volts
DMS-20PC-0/5-5GS (@120mA max.) +4.75
Applications which require electrical isolation between the input
signal source and the system power supply must use a separate
transformer-isolated supply to power the meter.
DMS-20PC-0/5-5RL (@15mA max.)
DMS-20PC-0/5-5RH (@90mA max.)
+4.75
+4.75
DMS-20PC-0/5-24RS (@15mA max.) +4.75
2. Panel Mounting: In most standard through-the-panel installations,
the DMS-20PC-0/5 must be secured to the panel with DMS-BZL4
bezel assemblies (see the Mechanical Specifications section for more
information).
Display
Display Type and Size
Polarity Indication
3½ digit, 0.37"/9.4mm high LED
"–" for negative VIN
Overrange Indication
"–1_ _ _" for negative inputs
"1_ _ _" for positive inputs
Physical/Environmental
Operating Temperature
Storage Temperature
Humidity (non-condensing)
Case Material
0
–20
0
–
–
–
+60
+75
95
°C
°C
%
OPERATING AND SETUP INSTRUCTIONS
As shipped, the DMS-20PC-0/5 is factory calibrated to read "000" for
a 0.0V input and "1999" for a 5.0V input. The following worst-case
procedure assumes the DMS-20PC-0/5 is completely mis-adjusted, i.e.,
both potentiometers and the DIP switches are randomly set.
Polycarbonate
Weight
0.6 ounces (17 grams)
1. Set R7 (full scale span/gain adjust) and R3 (zero/offset adjust) fully
clockwise, roughly 22 turns, and place SW1-SW8 to OFF (down
position).
~ The DMS-20PC-0/5 can also be used in most 0-10V applications. See the section
on 0-10V inputs for more information. See Note 3 on Table 1.
INPUT LO (TB1 "–LO") is internally connected to the power return (TB2 "–V").
Overvoltage specifications apply to the INPUT HI (TB1 "+HI") connection.
2. Select DIP switch setting #1 in Table 1.
3. Apply a precision 0.0V input and adjust R3 until the meter's display
reads "000".
4. Apply a precision 5.0V input and adjust R7 until the meter's display
reads "1999". Repeat steps 3 and 4 to make sure the adjustments
do not affect one another.
Ordering Information
DMS-20PC-0/5-5RS-C +5V supply, standard-intensity red LED's
DMS-20PC-0/5-5GS-C +5V supply, standard-intensity green LED's
DMS-20PC-0/5-5BS-C +5V supply, bright blue LED's
DMS-20PC-0/5-5RL-C +5V supply, low-power red LED's
DMS-20PC-0/5-5RH-C +5V supply, high-intensity red LED's
DMS-20PC-0/5-24RL-C +5V to +40V supply, low-power red LED's
5. Select the appropriate decimal point by setting SW6, SW7 or SW8 to
ON (DP1, DP2 or DP3 respectively).
NOTE: The "000" to "1999" display readings referred to in the
instructions above are for illustrative purposes only. If other display
readings such as "000" to "1200" are desired, refer to the DIP-
Switch Settings Tables for SW1-SW4 settings. (SW5 is reserved for
future use, it has no affect on display operation.) The initial setting
of R3 and R7 fully clockwise is recommended in the adjustment
procedure for all the following examples.
DMS-PS1-CM-C
DMS-PS4-CM-C
DMS-PS7-CM-C
+5V/1.0A AC/DC power supply module
+24V/0.45A AC/DC power supply module
+24V/0.7A AC/DC power supply module
DMS-20-CP
Panel cutout punch
Note: A DMS-BZL4 bezel assembly with a sealing gasket is supplied with each meter.
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
MPM_DMS20pc_5V.B04 Page 2 of 4
DMS-20PC-0/5 Series
0-5V and 0-10V Input 3½ Digit, LED
Display Process Control Monitors
4. Desired display readings are:
ON
Examples (0-5V Inputs)
1.0V input = "000"
6.0V input = "090"
1. Desired display readings are:
ON
1
4
2
3
5
6
7
8
0.0V input = "0.00"
5.0V input = "6.00"
Even though this input is positioned between +1.0V and +6.0V,
it still meets the 5V full scale input range listed in the Functional
1
3
4
6
7
8
2
5
Use DIP-switch setting #3 in Table 1 and enable decimal point DP2
via SW7. Apply 0.0V and adjust R3 so the display reads "0.00".
Apply 5.0V and adjust R7 so the display reads "6.00".
Specifications section. Use DIP-switch setting #8 in Table 1. Apply
1.0V and adjust R3 so the display reads "000". Apply 6.0V and adjust
R7 so the display reads "090". With this type of input, it is advisable
to recheck both input levels to be sure the potentiometer settings do
not affect one another.
2. Desired display readings are:
ON
0.0V input = "000"
5.0V input = "800"
1
2
3
4
5
6
7
8
0-10V Inputs
Use DIP-switch setting #2 in Table 1. Apply 0.0V and adjust R3 so
the display reads "000". Apply 5.0V and adjust R7 so the display
reads "800". For these display readings, no decimal points are
used. Set SW6, SW7 and SW8 to OFF.
While the DMS-20PC-0/5 is optimized for operation with 0-5V inputs,
its versatile input stage can also accommodate most 0-10V applica-
tions. The meter's zero/offset potentiometer (R3) has enough adjust-
ment range to produce a "000" display reading with input signal levels
between –0.1V and +1.0V. Table 2. summarizes the available ranges
when the DMS-20PC-0/5 is used with 0-10V inputs.
3. Desired display readings are:
ON
0.0V input = ".000"
5.0V input = ".250"
1
4
6
7
8
2
3
5
Example (0-10V Inputs)
Use DIP-switch setting #5 in Table 1 and enable decimal point DP1
via SW6. Apply 0.0V and adjust R3 so the display reads "000". Apply
5.0V and adjust R7 so the display reads ".250".
ON
1. Desired display readings are:
0.0V input = "000"
1
4
2
3
5
6
7
8
10.0V input = "500"
Table 1. 0-5V DIP-Switch Settings
Use DIP switch setting #4 in Table 2. Apply 0.0V and adjust R3 so
the display reads "000". Apply 10.0V and adjust R7 so the display
reads "500".
Display Reading
SW1
SW2
SW3
SW4
0.0V Input
1. 000
5.0V Input
1200-1999
700-1200
400-700
300-400
190-300
120-190
100-150
90-140
Off
On
Off
Off
Off
Off
Off
On
Off
Off
On
Off
On
Off
On
On
Off
Off
Off
On
On
On
On
On
Off
Off
Off
Off
Off
On
On
On
Table 2. 0-10V DIP-Switch Settings
2. 000
3. 000
4. 000
5. 000
6. 000
7. 000
8. 000
Display Reading
SW1
SW2
SW3
SW4
0.0V Input
1. 000
2. 000
3. 000
4. 000
5. 000
6. 000
7. 000
10.0V Input
1400-1999
800-1400
600-800
380-600
240-380
200-300
180-280
On
Off
Off
Off
Off
Off
On
Off
On
Off
On
Off
On
On
Off
Off
On
On
On
On
On
Off
Off
Off
Off
On
On
On
The DMS-20PC-0/5 is optimized for handling 5V signal ranges that are
positioned between –0.1V and +6.0V. As such, input ranges can be anywhere
between –0.1V to +4.9V and +1.0V to +6.0V as long as their full range is
5 Volts. The meter's zero/offset potentiometer (R3) has enough adjustment
range to produce a "000" display reading for input signal levels between
–0.1V and +1.0V.
Please note the DMS-20PC digital panel meter from which the DMS-20PC-0/5
is derived has an accuracy specification of 2 counts (max.). Thus, it may not
always be possible to obtain the exact desired display readings.
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
MPM_DMS20pc_5V.B04 Page 3 of 4
DMS-20PC-0/5 Series
0-5V and 0-10V Input 3½ Digit, LED
Display Process Control Monitors
MECHANICAL SPECIFICATIONS
TOLERANCES:
2 PL DEC 0.02 ( 0.51)
3 PL DEC 0.010 ( 0.254)
18 to 26 AWG (Solid or stranded)
0.20" (5.08mm)
WIRE SIZE:
STRIPPING LENGTH:
0.95
(24.1)
A
U N S I D E M A
0.040
(1.02)
5 / 0 - C
S - M 2 D 0 P
®
®
0.44
(11.2)
TYP.
0.040
(1.02)
1.30
(33.0)
0.040
(1.02)
0.80
(20.3)
Back View
0.88
(22.4)
1
1.38
(35.1)
12
ON
DIP
Switches
1.25
1
2
3
4
5
6
7
8
(31.8)
Front View
Zero/Offset
Adjust
+
–
+
–
R3
R7
+
+
–
–
Gain/Span
Adjust
TB1
TB2
Signal Power
Input Input
DP1
DP2
DP3
(SW6) (SW7) (SW8)
BEZEL INSTALLATION AND RECOMMENDED DRILL AND PANEL CUTOUT
0.187
(4.75)
#2-56 INSERT
0.156 (3.96) DEEP
BEZEL INSTALLATION
1.280
(32.51)
FRONT VIEW
PANEL
®
®
1.826 (46.38)
0.116 (2.95)
INTERNAL CORNER RADII:
0.032 (0.81) MAX.
GASKET
1.07
(27.18)
0.838
(21.29)
BEZEL
PANEL CUTOUT
0.145 (3.68)
1.336 (33.93)
1.626 (41.30)
0.093 (2.362) DIA
(4 REQUIRED)
USA:
Mansfield (MA), Tel: (508) 339-3000, email: sales@murata-ps.com
Toronto, Tel: (866) 740-1232, email: toronto@murata-ps.com
Milton Keynes, Tel: +44 (0)1908 615232, email: mk@murata-ps.com
Canada:
UK:
Murata Power Solutions, Inc.
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.
Tel: (508) 339-3000 (800) 233-2765 Fax: (508) 339-6356
www.murata-ps.com email: sales@murata-ps.com ISO 9001 and 14001 REGISTERED
11/25/08
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without
France:
Germany:
Japan:
Montigny Le Bretonneux, Tel: +33 (0)1 34 60 01 01, email: france@murata-ps.com
München, Tel: +49 (0)89-544334-0, email: munich@murata-ps.com
Tokyo, Tel: 3-3779-1031, email: sales_tokyo@murata-ps.com
Osaka, Tel: 6-6354-2025, email: sales_osaka@murata-ps.com
China:
Shanghai, Tel: +86 215 027 3678, email: shanghai@murata-ps.com
Guangzhou, Tel: +86 208 221 8066, email: guangzhou@murata-ps.com
notice.
© 2008 Murata Power Solutions, Inc.
Singapore: Parkway Centre, Tel: +65 6348 9096, email: singapore@murata-ps.com
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000
MPM_DMS20pc_5V.B04 Page 4 of 4
相关型号:
DMS-PS10-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS2-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS3-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS4-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS5-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS6-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS7-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
DMS-PS8-CM
High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA
©2020 ICPDF网 联系我们和版权申明