DMS-PS1-CM-C [MURATA]

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors; 0-5V和0-10V输入3.5位, LED显示屏过程控制监视器
DMS-PS1-CM-C
型号: DMS-PS1-CM-C
厂家: muRata    muRata
描述:

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors
0-5V和0-10V输入3.5位, LED显示屏过程控制监视器

监视器
文件: 总4页 (文件大小:213K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
DMS-20PC-0/5 Series  
0-5V and 0-10V Input 3½ Digit, LED  
Display Process Control Monitors  
DATEL's DMS-20PC-0/5 Series are the world's smallest, full-featured, 0-5V input  
process control monitors. Their large, easy-to-read, 0.37"/9.4mm LED displays are  
available in a choice of 4 LED color/intensity options: standard red, standard green,  
super-bright red, and low-power red. Two power supply input ranges are also available:  
the industry-standard +5V and a wide-range +5V to +40V (which typically draws 9mA at  
+24V).  
Gain (span) and offset (zero) adjustments are performed with on-board, precision,  
20-turn potentiometers. All decimal-point and range-change selections are made on an  
8-position, vibration-resistant, gold-plated DIP switch. Unlike competitive meters, there  
are no jumpers or solder gaps to open or close, and to further enhance reliability, the  
entire assembly utilizes 100% soldered connections. Both power-supply and input-signal  
connections are made via reliable screw-type terminal blocks.  
FEATURES  
N
Accepts 0-5V and 0-10V inputs  
N
Large, easy-to-read, 0.37"/9.4mm LED display  
N
Choice of 5 LED power/color options  
N
High input impedance, 100kΩ  
N
+5V to +40V model draws 9mA typ.  
N
Miniature size: 1.38" x 1.25" x 0.95"  
N
High-quality, 20-turn, span (gain) and zero (offset)  
adjustments  
The DMS-20PC-0/5's DIP switch and potentiometers accommodate hundreds of input-  
voltage/output-reading combinations. This practically eliminates the need for more costly,  
long-lead-time, factory "specials" in applications which use several different-range meters.  
A supplied bezel assembly––featuring metal fasteners and a rubber gasket––simplifies  
panel mounting and also provides excellent resistance to environmental dust and moisture.  
All these outstanding features combine to make the DMS-20PC-0/5 the perfect meter for  
prototype and OEM, 0-5V input, process control monitoring.  
N
DIP-switch selectable range and decimal points  
N
Vibration-resistant package; Reliable screw-terminal  
input connections  
N
Hundreds of different input/readout combinations  
SIMPLIFIED SCHEMATIC DIAGRAM  
DMS-20PC-0/5  
3½ Digit  
DATA  
A/D Converter  
–5V +5V  
DP1 DP2 DP3  
N.C.  
R3  
R7  
Zero  
Adjust  
Gain  
Adjust  
ON  
DIP Switches  
1
4
2
3
5
6
7
8
N.C.  
+5V  
–5V  
DC/DC  
Converter  
Band-Gap  
Reference  
Circuit  
1
2
1
2
TB1  
TB2  
+
+
+5V  
–5V  
HI LO  
Signal Input  
+V –V  
Power Supply Input  
For full details go to  
www.murata-ps.com/rohs  
Figure 1. DMS-20PC-0/5 simplified schematic  
www.murata-ps.com  
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000  
MPM_DMS20pc_5V.B04 Page 1 of 4  
DMS-20PC-0/5 Series  
0-5V and 0-10V Input 3½ Digit, LED  
Display Process Control Monitors  
Performance/Functional Specifications  
Typical at TA = +25°C, unless otherwise noted.  
TECHNICAL NOTES  
1. Input Configuration: The DMS-20PC-0/5 has its input low terminal  
(TB1 "LO") internally connected to the power supply ground terminal  
(TB2 "–V"). This connection effectively places the meter's input in a  
single-ended configuration. In some applications, single-ended inputs  
can cause ground-loop induced errors (the meter's display becomes  
unstable or bounces). This occurs because the LED drive currents  
flow through both the –V terminal and the signal LO terminal.  
Inputs  
Min.  
4.9  
100  
Typ.  
5.0  
Max.  
5.1  
Units  
Volts  
kΩ  
Full Scale Input Range ~  
Input Impedence  
140  
40  
Volts  
Overvoltage Protection   
Performance  
Sampling Rate  
2.5 reading per second  
0.05%FS 1 Count  
If suspected ground-loop errors are encountered, and the input signal  
LO terminal is externally connected to –V somewhere else in the  
system, try removing the connection to TB1 "LO". Inputs which have  
no ground-return connection to –V (commonly referred to as "floating  
inputs") must have their most negative potential tied to TB1 "LO".  
Please consult DATEL for more information.  
Accuracy (1 minute warm-up):  
Temperature Drift (0 to +60°C)  
Power Supply Requirements  
DMS-20PC-0/5-5RS (@90mA max.)  
0.15  
0.3  
Cnts/°C  
+4.75  
+5.00  
+5.00  
+5.00  
+5.00  
+5.25 Volts  
+5.25 Volts  
+5.25 Volts  
+5.25 Volts  
+40.0 Volts  
DMS-20PC-0/5-5GS (@120mA max.) +4.75  
Applications which require electrical isolation between the input  
signal source and the system power supply must use a separate  
transformer-isolated supply to power the meter.  
DMS-20PC-0/5-5RL (@15mA max.)  
DMS-20PC-0/5-5RH (@90mA max.)  
+4.75  
+4.75  
DMS-20PC-0/5-24RS (@15mA max.) +4.75  
2. Panel Mounting: In most standard through-the-panel installations,  
the DMS-20PC-0/5 must be secured to the panel with DMS-BZL4  
bezel assemblies (see the Mechanical Specifications section for more  
information).  
Display  
Display Type and Size  
Polarity Indication  
3½ digit, 0.37"/9.4mm high LED  
"–" for negative VIN  
Overrange Indication  
"–1_ _ _" for negative inputs  
"1_ _ _" for positive inputs  
Physical/Environmental  
Operating Temperature  
Storage Temperature  
Humidity (non-condensing)  
Case Material  
0
–20  
0
+60  
+75  
95  
°C  
°C  
%
OPERATING AND SETUP INSTRUCTIONS  
As shipped, the DMS-20PC-0/5 is factory calibrated to read "000" for  
a 0.0V input and "1999" for a 5.0V input. The following worst-case  
procedure assumes the DMS-20PC-0/5 is completely mis-adjusted, i.e.,  
both potentiometers and the DIP switches are randomly set.  
Polycarbonate  
Weight  
0.6 ounces (17 grams)  
1. Set R7 (full scale span/gain adjust) and R3 (zero/offset adjust) fully  
clockwise, roughly 22 turns, and place SW1-SW8 to OFF (down  
position).  
~ The DMS-20PC-0/5 can also be used in most 0-10V applications. See the section  
on 0-10V inputs for more information. See Note 3 on Table 1.  
 INPUT LO (TB1 "–LO") is internally connected to the power return (TB2 "–V").  
Overvoltage specifications apply to the INPUT HI (TB1 "+HI") connection.  
2. Select DIP switch setting #1 in Table 1.  
3. Apply a precision 0.0V input and adjust R3 until the meter's display  
reads "000".  
4. Apply a precision 5.0V input and adjust R7 until the meter's display  
reads "1999". Repeat steps 3 and 4 to make sure the adjustments  
do not affect one another.  
Ordering Information  
DMS-20PC-0/5-5RS-C +5V supply, standard-intensity red LED's  
DMS-20PC-0/5-5GS-C +5V supply, standard-intensity green LED's  
DMS-20PC-0/5-5BS-C +5V supply, bright blue LED's  
DMS-20PC-0/5-5RL-C +5V supply, low-power red LED's  
DMS-20PC-0/5-5RH-C +5V supply, high-intensity red LED's  
DMS-20PC-0/5-24RL-C +5V to +40V supply, low-power red LED's  
5. Select the appropriate decimal point by setting SW6, SW7 or SW8 to  
ON (DP1, DP2 or DP3 respectively).  
NOTE: The "000" to "1999" display readings referred to in the  
instructions above are for illustrative purposes only. If other display  
readings such as "000" to "1200" are desired, refer to the DIP-  
Switch Settings Tables for SW1-SW4 settings. (SW5 is reserved for  
future use, it has no affect on display operation.) The initial setting  
of R3 and R7 fully clockwise is recommended in the adjustment  
procedure for all the following examples.  
DMS-PS1-CM-C  
DMS-PS4-CM-C  
DMS-PS7-CM-C  
+5V/1.0A AC/DC power supply module  
+24V/0.45A AC/DC power supply module  
+24V/0.7A AC/DC power supply module  
DMS-20-CP  
Panel cutout punch  
Note: A DMS-BZL4 bezel assembly with a sealing gasket is supplied with each meter.  
www.murata-ps.com  
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000  
MPM_DMS20pc_5V.B04 Page 2 of 4  
DMS-20PC-0/5 Series  
0-5V and 0-10V Input 3½ Digit, LED  
Display Process Control Monitors  
4. Desired display readings are:  
ON  
Examples (0-5V Inputs)  
1.0V input = "000"  
6.0V input = "090"  
1. Desired display readings are:  
ON  
1
4
2
3
5
6
7
8
0.0V input = "0.00"  
5.0V input = "6.00"  
Even though this input is positioned between +1.0V and +6.0V,  
it still meets the 5V full scale input range listed in the Functional  
1
3
4
6
7
8
2
5
Use DIP-switch setting #3 in Table 1 and enable decimal point DP2  
via SW7. Apply 0.0V and adjust R3 so the display reads "0.00".  
Apply 5.0V and adjust R7 so the display reads "6.00".  
Specifications section. Use DIP-switch setting #8 in Table 1. Apply  
1.0V and adjust R3 so the display reads "000". Apply 6.0V and adjust  
R7 so the display reads "090". With this type of input, it is advisable  
to recheck both input levels to be sure the potentiometer settings do  
not affect one another.  
2. Desired display readings are:  
ON  
0.0V input = "000"  
5.0V input = "800"  
1
2
3
4
5
6
7
8
0-10V Inputs  
Use DIP-switch setting #2 in Table 1. Apply 0.0V and adjust R3 so  
the display reads "000". Apply 5.0V and adjust R7 so the display  
reads "800". For these display readings, no decimal points are  
used. Set SW6, SW7 and SW8 to OFF.  
While the DMS-20PC-0/5 is optimized for operation with 0-5V inputs,  
its versatile input stage can also accommodate most 0-10V applica-  
tions. The meter's zero/offset potentiometer (R3) has enough adjust-  
ment range to produce a "000" display reading with input signal levels  
between –0.1V and +1.0V. Table 2. summarizes the available ranges  
when the DMS-20PC-0/5 is used with 0-10V inputs.  
3. Desired display readings are:  
ON  
0.0V input = ".000"  
5.0V input = ".250"  
1
4
6
7
8
2
3
5
Example (0-10V Inputs)  
Use DIP-switch setting #5 in Table 1 and enable decimal point DP1  
via SW6. Apply 0.0V and adjust R3 so the display reads "000". Apply  
5.0V and adjust R7 so the display reads ".250".  
ON  
1. Desired display readings are:  
0.0V input = "000"  
1
4
2
3
5
6
7
8
10.0V input = "500"  
Table 1. 0-5V DIP-Switch Settings €  
Use DIP switch setting #4 in Table 2. Apply 0.0V and adjust R3 so  
the display reads "000". Apply 10.0V and adjust R7 so the display  
reads "500".  
Display Reading  
SW1  
SW2  
SW3  
SW4  
0.0V Input  
1. 000  
5.0V Input  
1200-1999  
700-1200  
400-700  
300-400  
190-300  
120-190  
100-150  
90-140  
Off  
On  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
On  
Off  
On  
Off  
On  
On  
Off  
Off  
Off  
On  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
On  
On  
On  
Table 2. 0-10V DIP-Switch Settings  
2. 000  
3. 000  
4. 000  
5. 000  
6. 000  
7. 000  
8. 000  
Display Reading  
SW1  
SW2  
SW3  
SW4  
0.0V Input  
1. 000  
2. 000  
3. 000  
4. 000  
5. 000  
6. 000  
7. 000  
10.0V Input  
1400-1999  
800-1400  
600-800  
380-600  
240-380  
200-300  
180-280  
On  
Off  
Off  
Off  
Off  
Off  
On  
Off  
On  
Off  
On  
Off  
On  
On  
Off  
Off  
On  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
On  
On  
On  
€ The DMS-20PC-0/5 is optimized for handling 5V signal ranges that are  
positioned between 0.1V and +6.0V. As such, input ranges can be anywhere  
between –0.1V to +4.9V and +1.0V to +6.0V as long as their full range is  
5 Volts. The meter's zero/offset potentiometer (R3) has enough adjustment  
range to produce a "000" display reading for input signal levels between  
0.1V and +1.0V.  
Please note the DMS-20PC digital panel meter from which the DMS-20PC-0/5  
is derived has an accuracy specification of 2 counts (max.). Thus, it may not  
always be possible to obtain the exact desired display readings.  
www.murata-ps.com  
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000  
MPM_DMS20pc_5V.B04 Page 3 of 4  
DMS-20PC-0/5 Series  
0-5V and 0-10V Input 3½ Digit, LED  
Display Process Control Monitors  
MECHANICAL SPECIFICATIONS  
TOLERANCES:  
2 PL DEC 0.02 ( 0.51)  
3 PL DEC 0.010 ( 0.254)  
18 to 26 AWG (Solid or stranded)  
0.20" (5.08mm)  
WIRE SIZE:  
STRIPPING LENGTH:  
0.95  
(24.1)  
A
U N S I D E M A  
0.040  
(1.02)  
5 / 0 - C  
S - M 2 D 0 P  
®
®
0.44  
(11.2)  
TYP.  
0.040  
(1.02)  
1.30  
(33.0)  
0.040  
(1.02)  
0.80  
(20.3)  
Back View  
0.88  
(22.4)  
1
1.38  
(35.1)  
12  
ON  
DIP  
Switches  
1.25  
1
2
3
4
5
6
7
8
(31.8)  
Front View  
Zero/Offset  
Adjust  
+
+
R3  
R7  
+
+
Gain/Span  
Adjust  
TB1  
TB2  
Signal Power  
Input Input  
DP1  
DP2  
DP3  
(SW6) (SW7) (SW8)  
BEZEL INSTALLATION AND RECOMMENDED DRILL AND PANEL CUTOUT  
0.187  
(4.75)  
#2-56 INSERT  
0.156 (3.96) DEEP  
BEZEL INSTALLATION  
1.280  
(32.51)  
FRONT VIEW  
PANEL  
®
®
1.826 (46.38)  
0.116 (2.95)  
INTERNAL CORNER RADII:  
0.032 (0.81) MAX.  
GASKET  
1.07  
(27.18)  
0.838  
(21.29)  
BEZEL  
PANEL CUTOUT  
0.145 (3.68)  
1.336 (33.93)  
1.626 (41.30)  
0.093 (2.362) DIA  
(4 REQUIRED)  
USA:  
Mansfield (MA), Tel: (508) 339-3000, email: sales@murata-ps.com  
Toronto, Tel: (866) 740-1232, email: toronto@murata-ps.com  
Milton Keynes, Tel: +44 (0)1908 615232, email: mk@murata-ps.com  
Canada:  
UK:  
Murata Power Solutions, Inc.  
11 Cabot Boulevard, Mansfield, MA 02048-1151 U.S.A.  
Tel: (508) 339-3000 (800) 233-2765 Fax: (508) 339-6356  
www.murata-ps.com email: sales@murata-ps.com ISO 9001 and 14001 REGISTERED  
11/25/08  
Murata Power Solutions, Inc. makes no representation that the use of its products in the circuits described herein, or the use of other  
technical information contained herein, will not infringe upon existing or future patent rights. The descriptions contained herein do not imply  
the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without  
France:  
Germany:  
Japan:  
Montigny Le Bretonneux, Tel: +33 (0)1 34 60 01 01, email: france@murata-ps.com  
München, Tel: +49 (0)89-544334-0, email: munich@murata-ps.com  
Tokyo, Tel: 3-3779-1031, email: sales_tokyo@murata-ps.com  
Osaka, Tel: 6-6354-2025, email: sales_osaka@murata-ps.com  
China:  
Shanghai, Tel: +86 215 027 3678, email: shanghai@murata-ps.com  
Guangzhou, Tel: +86 208 221 8066, email: guangzhou@murata-ps.com  
notice.  
© 2008 Murata Power Solutions, Inc.  
Singapore: Parkway Centre, Tel: +65 6348 9096, email: singapore@murata-ps.com  
www.murata-ps.com  
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000  
MPM_DMS20pc_5V.B04 Page 4 of 4  

相关型号:

DMS-PS10-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS11-CM

Converter
ETC

DMS-PS12-CM

Converter
ETC

DMS-PS2-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS3-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS4-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS4-CM-C

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors
MURATA

DMS-PS5-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS6-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS7-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS7-CM-C

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors
MURATA

DMS-PS8-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA