DMS-PS-CM Series  
High Efficiency, AC/DC  
Instrumentation Power Supplies  
with Individually Isolated Outputs  
C
US E151252  
®
Features  
DATELs DMS-PS-CM Series of high-efficiency, chassis mount AC/DC power sup-  
plies feature low noise (40mV on main, 8mV on auxiliaries), fully-isolated +24, +12V,  
and +5V outputs, making them perfect for powering today’s complex instrumentation.  
A high-current main output is isolated from the AC line by 3000Vac. In dual- and triple-  
output models, the low-current auxiliary outputs are isolated from the main output by  
1000Vdc, and from each other by 2000Vdc, effectively providing double isolation from  
the AC line! This unprecedented isolation eliminates ground loop problems in complex,  
multiple-instrument applications.  
Full-load efficiencies of up to 80% and output-power ratings of 5, 10 or 16  
Watts, combine to ensure minimal ac power consumption. For intermittent use or low-  
power applications, the 5-Watt model’s no-load quiescent consumption with a nominal  
120Vac input is a mere 0.6 Watts---that’s nearly seven times less than a standard  
4W night light! These low cost, high-efficiency power supplies can significantly reduce  
long-term electricity costs in low (<5Watts) to medium (<16Watts) power applications.  
All DMS-PSX-CM power supplies feature universal inputs of 85-264Vac 50/60Hz,  
built-in line fuses, and on-board ‘Power On’ LED indicators. At full rated load, hold-up  
time is typically 20ms at 120Vac, and 80ms at 230Vac. All outputs provide indefinite  
short-circuit protection and, for added reliability, the main high-current output also  
includes overvoltage protection. A rugged, vibration-proof, chassis mount package  
incorporates large, shock-resistant terminal blocks for all I/O connections.  
Multiple outputs, low noise, low cost, high efficiency, double isolation, and rugged  
construction combine to make DMS-PSX-CM Series AC/DC power supplies the ideal  
choice for powering today’s sensitive instrumentation, and any electronic device that  
requires a reliable dc voltage!  
Up to 80% efficient single, dual, and triple-  
output models  
Individual, fully-isolated outputs:  
3000Vac on main  
4000V double-isolation on auxiliaries  
Available with +5V, +12V, and +24V outputs  
Low noise: 40mVp-pk on main, 8mVp-pk on  
auxiliaries; Ideal for sensitive instrumentation  
Universal input: 85-264Vac @ 47-63Hz  
Choice of 5, 10, or 16W models for minimal  
system power-consumption  
Standby power consumption as low as 0.6W  
Short-circuit protection on all outputs;  
OVP on main output  
Built-in ac mains fuse & 'Power On' indicator  
5W models operate up to 5 LED-display DPM's  
Vibration-resistant, chassis-mount  
modular packages  
EMI compliant; Safety approvals pending  
Low cost!  
LDO  
Regulator  
DC/DC  
Converter  
**  
TB3  
TB2  
+
+
+
IN  
OUT  
GND  
+
+
+
+
V3 (Auxilliary)  
*Not used on single-output models  
**Used only on dual and triple-output models  
LDO  
Regulator  
DC/DC **  
Converter  
+
+
+
IN  
OUT  
GND  
AC/DC Converter  
(Auxilliary)  
V2  
F1  
TB4  
1A/250V  
TB1  
*
+
V1  
AC(L)  
AC(N)  
FG  
+
(Main)  
85-264V  
50/60Hz  
Figure 1. DMS-PS-CM Series Simplified Schematic  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
DATEL, Inc., Mansfield, MA 02048 (USA)  
DMS-PS-CM Series  
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
Performance/Functional Specifications  
Typical at TA = +25°C and VIN = 85-264V @47-63Hz  
AC Input  
DC Outputs (continued)  
Input Voltage Range, All models  
85-264V @47-63Hz  
Efficiency (Typ.@ 120Vac, full load):  
Single Output Models  
Dual Output Models  
75%  
73%  
71%  
Input Current (115V/230V, typ.):  
5-Watt Models  
10-Watt Models  
0.15A/0.07A  
0.3A/0.13A  
0.33A/0.16A  
Triple Output Models  
16-Watt Models  
DC-Output Terminal Blocks (TB1, TB2, TB3):  
Wire Size &Type  
16-20AWG (1.5 to 0.5mm2),  
solid or stranded  
Inrush Current (All models, typical peak):  
@115Vac  
@230Vac  
14.1A  
32.5A  
Insulation Strip Length  
Screw Tightening Torque  
0.25 inches (6.4mm)  
3.6 pound-inches (0.4Nm)  
Isolation (Min.):  
Short Circuit Protection (All outputs)  
Overvoltage Protection V1 (max.)  
Foldback, self-recovering  
134% x Vout  
Output V1 to AC Input  
3000Vac  
Outputs V2 & V3 to AC Input  
AC Input to Frame Ground  
Output V1 to Frame Ground  
Outputs V2 & V3 to Frame Ground  
Outputs V2 & V3 to Output V1  
Output V2 to Output V3  
3000Vac + 1000Vdc  
1500Vac  
Environmental  
500Vac  
Operating Temperature  
0 to +50°C @ full rated power;  
–25 to +70°C @ 50% rated power  
(see Figure 3)  
500Vac + 1000Vdc  
1000Vdc  
2000Vdc  
Storage Temperature  
Cooling  
–40 to +85°C  
Frame Ground Leakage Current (Max.):  
@115Vac  
@230Vac  
0.5mA  
3.5mA  
Free air convection with derating  
(see Figure 3 and Technical  
Notes)  
Switching Frequency (Typical):  
V1 (5W and 10W models)  
V1 (16W models)  
75kHz  
83kHz  
100kHz  
Humidity (Non-condensing)  
0 to 85%  
Physical  
V2 & V3 (All models)  
Dimensions  
See Mechanical Specifications  
Line Fuse (Built-in)  
1A/250Vac, 5 x 20mm, meeting  
IEC60127-2, sheet 3 specification  
for time lag fuses (slow-blow)  
Weight:  
5 Watt Models  
10 Watt Models  
16 Watt Models  
5.8 ounces (165 grams)  
6.9 ounces (195 grams)  
7.9 ounces (223 grams)  
AC Mains Terminal Block (TB4):  
Wire Size & Type  
14-20AWG (2.5 to 0.5mm2),  
solid or stranded  
Case Materials:  
Outer Case  
Insulation Strip Length  
Screw Tightening Torque  
Rated Voltage  
0.25 inches (6.4mm)  
ABS, UL94 5VA  
Phenolic, UL94 V-0  
Plastic, UL94 V-1  
4.4 pound-inches (0.5Nm)  
630V (VDE 0110-V. Group 2);  
250V (VDE 0110-V. Group 3)  
DC/DC Modules  
AC/DC Modules  
EMI (All models)  
Meets CISPR Pub. 22 & FCC  
Class B  
All models will also operate from a regulated and filtered 110 to 340Vdc input.  
Safety Approvals  
Pending  
Unless otherwise specified, load regulation is measured with the output under  
test undergoing a load change of 100% to 50% at nominal line input and, when  
applicable, with all other outputs operating at 50% of rated load.  
DC Outputs  
Line Regulation (All outputs)  
0.1% (max)  
Transient response is defined as the output returning to within its specified  
tolerance in 10ms or less, following a 90% load change.  
Load Regulation: ➀  
V1 (All models)  
V2 & V3 (All models)  
2%  
0.2% (max)  
Output Accuracy (Max.):  
V1 (All models)  
V2 & V3 (All models)  
2.0%  
2.5%  
Hold-Up Time (47-63Hz):  
@115Vac  
@230Vac  
20mSec. typ.  
80mSec. typ.  
Noise & Ripple  
(All models, 20MHz bandwidth):  
See Noise & Ripple graphs  
40mVp-pk (typ.)  
V1  
V2 & V3  
8mVp-pk (typ.)  
Transient Response ➀  
See Transient Response graphs  
DATEL, Inc., Mansfield, MA 02048 (USA)  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
2
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
DMS-PS-CM Series  
Ordering Information and Selection Guide  
DATEL Part No.  
DMS-PS1-CM  
DMS-PS2-CM  
DMS-PS3-CM  
DMS-PS4-CM  
DMS-PS5-CM  
DMS-PS6-CM  
DMS-PS7-CM  
DMS-PS8-CM  
DMS-PS9-CM  
DMS-PS10-CM  
DMS-PS11-CM  
DMS-PS12-CM  
Rated Power  
5 Watts  
V1 Output  
5Vdc/1A  
V2 Output  
V3 Output  
5 Watts  
5Vdc/0.65A  
5Vdc/0.35A  
24Vdc/0.45A  
24Vdc/0.35A  
24Vdc/0.30A  
24Vdc/0.70A  
24Vdc/0.60A  
24Vdc/0.55A  
12Vdc/1.35A  
12Vdc/1.2A  
12Vdc/1.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
5 Watts  
4.85Vdc/0.2A  
10 Watts  
10 Watts  
10 Watts  
16 Watts  
16 Watts  
16 Watts  
16 Watts  
16 Watts  
16 Watts  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
4.85Vdc/0.2A  
Tehnical Notes  
3. Fuse Replacement: If any dc-output drops to zero volts, and no fault  
conditions exist within the external load circuitry or the ac mains, F1  
may have failed. F1 is located on the circuit (etch) side of the pc-board.  
Fuse replacement is performed by first de-energizing and then discon-  
necting the ac mains from TB4. Next, disconnect all load wiring from  
TB1, TB2, and TB3. Lastly, remove the four screws that secure the  
pc-board to the plastic case. After making sure that the new fuse is  
securely attached to its mounting clips, re-assemble the unit using all  
four screws. Reconnect all input and output wiring and re-apply ac  
power.  
IMPORTANT! To ensure safe and reliable operation, DMS-PS-CM  
power supplies must be installed and serviced by qualified per-  
sonnel. Contact DATEL if there is any doubt regarding their instal-  
lation and/or operation. Please read all of the following technical  
and application notes BEFORE installing or making connections  
to DMS-PS-CM power supplies.  
Warnings (Marking)  
Caution, unit may become hot in normal operation, thereby creat-  
ing a potential burn hazard. Disconnect ac mains and then allow  
unit to cool before servicing.  
If the unit still does not operate properly, and the ac supply at TB4 is  
measured to be within its specified operating range, the power supply  
is defective and must be replaced. Except for F1, DMS-PS-CM supplies  
contain no other user-serviceable components.  
Reference document: IEC 417, No. 5041.  
Dangerous, potentially lethal voltages are present during  
normal operation. Disconnect ac mains before servicing.  
Reference document: IEC 417, No. 5036.  
4. Wire Gauges and Fusing: All wiring connected to the DMS-PS-CM’s  
terminal blocks must meet the requirements specified in the Functional  
Specifications section. All ac supply and load wiring must be rated  
for the voltages and currents they will conduct and must comply with  
any code or application-mandated requirements pertaining to the user’s  
specific installation. Applications subject to vibration should include  
adequate strain reliefs on both input and output wiring. Install the strain  
reliefs within 2-3 inches (5-7.5cm) of the terminal blocks.  
Caution, refer to accompanying documents for more information.  
Reference document: ISO 3864, No. B.3.1.  
It is recommended that all wiring be rated for 600V and 105°C opera-  
tion (UL1015 type, for example). Also, wire insulation must be stripped  
to within 10% of the dimensions shown in Figure 2. All wires must  
be inserted into their respective terminal blocks such that the screw  
terminal does not pinch their insulation. No more than two wires  
should be connected to any single terminal on TB1 through TB4.  
If two wires are attached to a single terminal, be sure to use only two  
20AWG (0.5mm2) wires on TB1, TB2, and TB3, and only two 18 or  
20AWG (0.75 or 0.5mm2) wires on TB4.  
1. Shock Hazard: DMS-PS-CM Series power supplies feature touch-  
proof terminals blocks and fully-isolated plastic construction, thereby  
greatly reducing the risk of electrical shock. However, these are mains-  
powered devices whose operation is derived from hazardous and  
potentially lethal voltages.  
All service and installation must be performed by qualified personnel,  
with the ac supply voltage de-energized. Before making connections to  
any of the unit’s terminal blocks, use a digital voltmeter to verify that the  
ac supply is de-energized (off).  
2. AC Supply Fuse (F1): All DMS-PS-CM Series power supplies are  
equipped with a built-in 1A/250V time-lag fuse. Replacement fuses  
must be of the same type and rating; please refer to the Functional  
Specifications section of this datasheet for more information. F1 is  
conservatively rated in order to reduce nuisance tripping which might  
occur during power-up or output overload conditions. However, F1 is  
primarily intended to provide protection in the event of catastrophic  
failure in the DMS-PS-CM’s ac/dc converter.  
0.25"  
(6.4mm)  
Figure 2. Insulation Strip Length  
DATEL, Inc., Mansfield, MA 02048 (USA)  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
3
DMS-PS-CM Series  
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
The ac-mains circuit supplying power to DMS-PS-CM supplies must  
be fused according to the current rating of the wire gauge used, in  
accordance with applicable regulatory codes. The built-in 1ampere line  
fuse (F1) only protects the module itself from destructive over currents.  
full rated current) will adversely affect the operation and stability  
of auxiliary outputs V2 and V3. On these models, V1 must be  
adjusted to within 2 % of its nominal value (+5.0V, +12.0V, or  
+24.0V, depending on model).  
5. AC Mains Connections (TB4): To ensure EMI-compliant operation,  
all three ac-supply inputs must be properly connected to TB4. Never  
operate any DMS-PS-CM power supply without a ground connection  
to TB4’s ‘FG’ terminal.  
9. Temperature Derating (See Figure 3): All DMS-PS-CM supplies are  
specified to operate at their full rated power over the temp range of 0°C  
to +50°C in still air (convection cooling) without any thermal derating.  
For operation over +50°C in still air, derate the output power linearly by  
2.5% per °C down to 50% rated power at +70°C. To operate the units at  
full rated power between +50°C and +70°C, a minimum forced-airflow  
of 100 LFM is required. For operation below 0°C, derate the output  
power linearly by 2.0% per °C down to 50% rated power at –25°C.  
On 120Vac 50/60Hz mains, connect the black or "hot" lead to ‘AC(L)’,  
the white or “neutral” lead to ‘AC(N)’, and the supply ground (earth)  
to ‘FG’ (Frame Ground). On 220V 50/60Hz ac mains with line and  
neutral conductor-designations, connect the line to AC(L), the neutral  
to AC(N), and the ground to ‘FG’.  
Unless forced air with the velocity noted above is employed, DMS-  
PS-CM supplies should never be mounted upside down (terminal  
blocks facing down). Also, always provide sufficient clearances in order  
to ensure adequate airflow around the supply.  
6. Connector Torque Ratings: It is extremely important to tighten all  
input and output terminal blocks securely. TB4’s screw terminals must  
be torqued to 4.4 pound-inches (0.5Nm). TB1, TB2, and TB3 must be  
torqued to 3.6 pound-inches (0.4Nm). Proper tightening will minimize  
losses and ensure safe, reliable operation.  
10.V1 Peak Capabilities: DMS-PS-CM power supplies have a maximum  
continuous output-current rating that’s specified in the Ordering and  
Selection Guide. In addition, each model’s V1 output can intermittently  
supply 120% of its continuous rated current for short periods of time if  
the duty cycle is less than 10%. Peak current ratings do not apply to  
the auxiliary outputs V2 or V3.  
7. ‘Power On’ LED: The Power On LED indicates that the unit has  
ac-power applied and its V1 dc-output is operational. However, the  
power-on LED’s illumination does not imply nor guarantee that the  
unit’s dc-outputs are within their specified accuracy.  
11.Isolated Outputs: Unlike the majority of competitive ac/dc power sup-  
plies, all dual- and triple-output DMS-PS-CM power supplies feature  
fully-isolated outputs. This is an important feature when, for reasons  
of high common mode voltages, an instrument’s input circuit must be  
isolated from the system ground. All V1 outputs are isolated from the ac  
mains by a minimum of 3000Vac, while auxiliary outputs V2 and V3 are  
isolated from one another by 2000Vdc, and fromV1 by 1000Vdc. The  
low noise, double-isolated auxiliaries are ideal for powering sensitive  
instrumentation that requires low ac leakage-currents.  
8. Output Adjustment: The main output, V1, on all 5, 10, and 16W  
models is adjustable by approximately –10% to +15%. V1’s adjustment  
potentiometer is accessed via a small hole located next to the  
Power-On LED. While not recommended, field adjustment of single-  
output models can be performed within the tolerance window noted  
above. However, keep in mind that the unit’s maximum output power  
capability must not be exceeded. For example, increasing V1’s output  
voltage by 10% produces a corresponding 10% reduction in V1’s  
maximum output current.  
All ac/dc and dc/dc power components utilized in the construction  
of DMS-PS-CM power supplies are 100% hi-pot tested during their  
manufacturing processes. In addition, after final assembly by DATEL,  
all models are subjected to an additional hi-pot testing consisting of  
On dual-and triple-output units, V1 is factory calibrated with all  
outputs simultaneously loaded to 100% of their rated current. On  
all dual- and triple output models, adjusting V1 under any condi-  
tion other than those just noted (i.e., all outputs loaded to their  
2.0% / ºC  
1 0 0  
2.5% / ºC  
7 5  
5 0  
2 5  
0
70ºC  
–25 –10  
0
10  
15  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
70  
75  
Figure 3.Temperature Derating  
DATEL, Inc., Mansfield, MA 02048 (USA)  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
4
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
DMS-PS-CM Series  
1000Vac sequentially applied between the ac mains input and each  
output, and between each output and all other outputs.  
3. Model Selection & Energy Conservation: In order to achieve the  
lowest possible energy consumption, be sure to determine your appli-  
cation’s total current requirements. This is especially true when using  
DMS-PS-CM supplies to power DATELs energy-efficient LED and/or  
LCD display digital panel meters (DPMs) and process monitors. In  
general, choose a power supply that will accommodate your maximum  
current consumption plus a 20% margin. Choosing the lowest-wattage  
model suitable for a given application will provide lower procurement  
costs and lower long-term operating costs.  
Application Information  
1. Chassis Mounting Considerations: In order to minimize self-heating,  
DMS-PS-CM power supplies should always be mounted in either a  
vertical or horizontal position. Avoid mounting units upside-down or in  
close proximity to other heat-generating devices. Also, be sure to use  
the mounting hardware described in Figure 4 below in order to ensure  
a secure, vibration-resistant installation.  
When calculating total current requirements in installations employing  
three or more DMS-Series meters, it is acceptable practice to use each  
meter’s typical current consumption rating. However, be sure to consult  
the relevant product datasheets for all instrumentation comprising your  
application.  
For applications where DMS-PS-CM power supplies will be powering  
only DATEL DPM’s, a 5-Watt DMS-PS3-CM can power up to four, stan-  
dard intensity (‘-RS’ suffix) red-LED DMS-30PC meters: two meters on  
V1, and one meter each on V2 and V3. The same DMS-PS3-CM could  
also be used to power over 40 low-power red DMS-30PC meters (‘-RL’  
suffix), or over 800 DMS-30LCD non-backlit meters! Of course, these  
statements are made without regard to ground-loop problems that may  
be encountered when powering 800 DPM’s from a single power supply.  
Screw,  
Split Lock Washer,  
Flat Washer  
Panel/Chassis  
Threaded  
Hole  
Screw,  
Flat Washer  
Panel/Chassis  
Scope Probe  
Flat Washer,  
Split Lock Washer,  
Hole  
Oscilloscope  
Nut  
Figure 4. Chassis Mounting  
V1  
+
2. Bipolar Operation (See Figure 5): DMS-PS-CM power supplies’ fully  
isolated outputs allow for the generation of bipolar (positive and nega-  
tive) supply voltages. Bipolar outputs can be used to power dual-supply  
operational amplifiers, as well as any other type of instrumentation that  
requires bipolar supply voltages. However, please keep in mind that  
when connecting and operating any two outputs in this fashion, each  
output retains its maximum current rating.  
BW = 20MHz  
DMS-PS-CM  
Figure 6. Measuring Ripple and Noise  
DMS-PS6-CM  
V1  
V2  
V3  
+
+
+
+24V –5V  
COM  
+5V  
Figure 5. Bipolar Connections  
DATEL, Inc., Mansfield, MA 02048 (USA)  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
5
DMS-PS-CM Series  
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
Typical Performance Curves TA = +25°C, VIN = 120V @60Hz  
Noise and Ripple - 100% Load, 20MHz Bandwidth  
DMS-PS3-CM  
V1 (+5V)  
DMS-PS6-CM  
V1 (+24V)  
DMS-PS9-CM  
V1 (+24V)  
DMS-PS3-CM  
V2 (+4.85V)  
DMS-PS6-CM  
V2 (+4.85V)  
DMS-PS9-CM  
V2 (+4.85V)  
Transient Response - 10% to 100% Load Step  
DMS-PS3-CM  
V1 (+5V)  
DMS-PS6-CM  
V1 (+24V)  
DMS-PS9-CM  
V1 (+24V)  
DMS-PS3-CM  
V2 (+4.85V)  
DMS-PS6-CM  
V2 (+4.85V)  
DMS-PS9-CM  
V2 (+4.85V)  
DATEL, Inc., Mansfield, MA 02048 (USA)  
Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 E–mail:sales@datel.com Internet:www.datel.com  
6
H I G H E F F I C I E N C Y , A C / D C I N S T R U M E N T A T I O N P O W E R S U P P L I E S  
DMS-PS-CM Series  
Mechanical Specifications  
MECHANICAL DIMENSIONS: Inches (mm)  
TOLERANCES: 2 PL DEC 0.02 ( 0.51)  
3 PL DEC 0.010 ( 0.254)  
5 Watt &  
10 Watt Models  
16 Watt Models  
Power On  
V1  
Power  
V1 Adjust  
Adjust On  
Detail  
See detail  
+
V3  
®
®
0.188  
(4.8)  
TB3  
DMS-PSX-CM  
AC(L)  
AC(N)  
FG  
AC/DC POWER SUPPLY  
+
V2  
2.835  
(72.0)  
TB2  
TB1  
TB4  
+
V1  
1.42  
(36.1)  
4.625 (117.5)  
5.125 (130.2)  
1.000 (25.4)  
4.165 (105.8)  
5W models: 0.77 (19.6)  
10W models: 0.87 (22.1)  
16W models: 0.93 (23.6)  
0.125  
(3.2)  
®
®
DS-0505A  
01/02  
ISO 9001 Registered  
DATEL (UK) LTD. Tadley, England Tel: (01256)-880444  
DATEL S.A.R.L. Montigny Le Bretonneux, France Tel: 01-34-60-01-01  
DATEL GmbH München, Germany Tel: 89-544334-0  
DATEL, Inc. 11 Cabot Boulevard, Mansfield, MA 02048-1151  
Tel: (508) 339-3000 (800) 233-2765 Fax: (508) 339-6356  
Internet: www.datel.com  
Email: sales@datel.com  
DATEL KK Tokyo, Japan Tel: 3-3779-1031, Osaka Tel: 6-6354-2025  
DATEL makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights.The descriptions contained herein do  
not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifications are subject to change without notice. The DATEL logo is a registered DATEL, Inc. trademark.  

相关型号:

DMS-PS2-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS3-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS4-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS4-CM-C

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors
MURATA

DMS-PS5-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS6-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS7-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS7-CM-C

0-5V and 0-10V Input 3½ Digit, LED Display Process Control Monitors
MURATA

DMS-PS8-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-PS9-CM

High Efficiency, AC/DC Instrumentation Power Supplies with Individually Isolated Outputs
MURATA

DMS-SA16-00A1E

15.6"/18.5" Open Frame PC
ADVANTECH

DMS-SA16-00A2E

15.6"/18.5" Open Frame PC
ADVANTECH