Description
Power Supplies with Battery Chargers
The HPF24S6 and HPF24S8 are compact, cost-effective, 6
amp. or 8 amp. remote power supplies with integral battery
chargers. These adaptable power supplies may be con-
nected to any 12 or 24 volt Fire Alarm Control Panel
(FACP) or the power supplies may stand alone. Primary
applications include the following:
•
Notification Appliance Circuits (NAC) expansion to sup-
port ADA requirements and NAC synchronization
Auxiliary power to support 24 volt system accessories
•
HFP24S6/8
dh1061.jpg
These power supplies provide regulated and filtered 24
VDC power to four (4), notification appliance circuits, con-
figured as either four Class B (Style Y) or Class A (Style A,
with ZNAC-4 Option Module). Alternately, the four outputs
may be configured as follows:
Features
•
UL Listed NAC synchronization using System Sensor,
Cooper-Wheelock or Gentex (Commander Series)
appliances.
•
•
•
•
all non-resettable
all resettable
•
•
•
Cascade up to ten (10) power supplies (four (4) power
supplies with Gentex) with strobe timing maintained.
Operates as a sync follower or a sync generator
(default).
two non-resettable
two resettable
The power supplies also contain a battery charger with a
charging capacity of up to 18 Amp Hour batteries.
Contains two (2), fully -isolated input/control circuits
energized from FACP notification appliance circuit
(NAC expander mode) or jumpered permanently on
(stand-alone mode).
The HPF24S6 and HPF24S8 power supplies comply with
the following Agency standards:
•
•
NFPA 72 National Fire Alarm Code,
•
•
•
Configured to internally house addressable SLC control
module for alarm activation.
UL Standard 864, 9th Edition for control units for Fire
Alarm Systems (NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems
(stand-alone mode).
Four (4) Class B (Style Y) or four (4), Class A (Style Z)
(with ZNAC-4 Module) notification appliance circuits.
6.0A or 8.0A (depending on model) full load output
(3.0A maximum per circuit) in NAC expander mode
(UL Standard 864).
•
•
4.0A or 6.0A continuous output in stand-alone mode
(UL Standard 1481).
An ISO 9000-2000 Company
SIGNALING
UOXX.S6677 7315-1637:102
UTRZ.S6677
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installation pwurpwoswes,.ganadmareeswubejecllt-tofcchia.cngoemwithout notice. No responsibility is assumed by Gamewell-FCI for their use.
CS-60062 Rev. A1 page 1 of 2
Features (Continued)
Specifications (Continued)
•
In stand-alone mode, output power circuits configured
as resettable, (using the FACP reset switch),
non-resettable, or a combination of both.
Fully regulated and filtered power output (optimal for
powering four-wire smoke detectors, annunciators and
other system peripherals requiring regulated/filtered
power).
Output Circuits
•
•
•
+24 VDC filtered, regulated
3.0A maximum for any one circuit
4.0A maximum total continuous current for all outputs
(Stand-alone mode) for the HPF24S6 and 6A for the
HPF24S8
•
•
6A or 8A, depending on the model, maximum total
short-term current for all outputs (NAC Expander mode).
Secondary Power (Battery) Charging Circuit
•
Power-limiting technology meets UL power-limiting
requirements.
•
•
•
•
Supports lead-acid batteries only
Float Charge Voltage: 27.6 VDC
Maximum Charge Current: 1.5A
Maximum Battery Capacity: 18 AH
•
•
Normally-closed trouble relay.
Fully supervised power supply, battery and notification
appliance circuits.
Ordering Information
•
•
Selectable earth fault detection.
AC trouble report selectable for immediate or up to 8
hour delay.
Model
Description
HPF24S6
Remote charger 6A power supply
(120 VAC). Includes the main printed
circuit board, transformers, red
enclosure, and installation instructions.
Remote charger 8A power supply
(120 VAC). Includes the main printed
circuit board, transformers, red
•
Compatible with any UL 864 fire alarm control which
uses an industry standard reverse polarity notification
circuit (including unfiltered and unregulated bell power).
Requires input trigger voltage of 9.0 -32 VDC.
Self-contained in compact, lockable cabinet
15” H x 14.5” W x 2.75” D (38.1 H x 36.8 W x 7.0 D cm).
Includes an integral battery charger capable of charging
up to 18 AH batteries. The cabinet has the capacity of
housing 7.0 AH batteries.
HPF24S8
•
•
enclosure, and installation instructions.
•
•
•
FCPS-24S6RB Replacement mother board.
ZNAC-4 -
BAT-1270 -
Class A (Style Z) NAC option module
Battery, 12 volt, 7.0 AH (two required).
Battery charger may be disabled via DIP (Dual In-Line
Package) switch for applications requiring larger
batteries.
Fixed, clamp-type terminal blocks accommodate
up to 12 AWG (3.1 mm2) wire.
Specifications
Primary (AC) Power
•
•
•
HPF24S6: 120 VAC 60 Hz, 3.2A maximum
HPF24S8: 120 VAC 60 Hz, 3.2A maximum
Wire size: minimum 14 AWG (2.0 mm²) with 600V
insulation
Control Input Circuit
•
•
Input Voltage: 9.0 to 32 VDC
Input Current: 2.0 mA (16 - 32 V)
per input 1.0 mA (9 - 16 V)
Trouble Contact Rating
5.0A at 24 VDC
Auxiliary Power Output
Specific Application Power - 500 mA maximum
•
•
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-60062 Rev. A1 page 2 of 2