FCPS-24S8 [ETC]
6-Amp and 8-Amp 24-Volt Remote Power Supplies; 6安培和8安培24伏特远程电源型号: | FCPS-24S8 |
厂家: | ETC |
描述: | 6-Amp and 8-Amp 24-Volt Remote Power Supplies |
文件: | 总3页 (文件大小:395K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
July 20, 2004
DN-6927 • E-30
FCPS-24S6 and FCPS-24S8
6-Amp and 8-Amp
24-Volt Remote Power Supplies
Section: Power Supplies
GENERAL
California
State Fire
Marshal
The FCPS-24S6 (6-amp) and FCPS-24S8 (8-amp) are com-
pact, cost-effective remote power supplies with battery charger.
The FCPS-24S6/-24S8 may be connected to any 12- or 24-
volt Fire Alarm Control Panel (FACP) or may be used as a
stand-alone supply. Primary applications include Notification
Appliance (bell) Circuit (NAC) expansion (to support ADA re-
quirements and NAC synchronization) or auxiliary power to
support 24-volt system accessories. The FCPS-24S6/-24S8
provides regulated and filtered 24 VDC power to four notifi-
cation appliance circuits configured as either four Class B (Style
Y) or Class A (Style Z, with ZNAC-4 option module). Alter-
nately, the four outputs may be configured as all non-resettable,
all resettable, or two non-resettable and two resettable. The
FCPS-24S6/-24S8 also contains a battery charger capable of
charging up to 18 AH batteries.
7315-0028:225
MEA
299-02-E
S635
FEATURES
• UL-Listed NAC synchronization using System Sensor,
Wheelock, or Gentex “Commander²” appliances.
• Cascadable for up to ten power supplies (four for Gentex)
with strobe timing maintained.
• Operates as a “sync follower” or as a “sync generator” (de-
fault). See note on page 2.
• Contains two fully-isolated input/control circuits — triggered
from FACP NAC (NAC expander mode) or jumpered per-
manently “ON” (stand-alone mode).
• Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4
module) NACs.
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output,
with 3 amps maximum/circuit, in NAC expander mode (UL 864).
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous out-
put in stand-alone mode (UL 1481).
• Compatible with coded inputs; signals passed through.
• Battery charger may be disabled via DIP switch for applica-
tions requiring larger batteries.
• Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1 mm²) wire.
• Optional power-supervision relay (A77-716B).
• In stand-alone mode, output power circuits may be config-
ured as: resettable (reset line from FACP required), non-
resettable, or a mix of two and two.
STANDARDS and CODES
• Fully regulated and filtered power output — optimal for pow-
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
• Power-limiting technology meets UL power-limiting require-
ments.
The FCPS-24S6/-24S8 complies with the following standards:
• NFPA 72 National Fire Alarm Code.
• UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
• Form-C normally-closed trouble relay.
• UL 1481 Power Supplies for Fire Alarm Systems (stand-
alone mode).
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
SPECIFICATIONS
• AC trouble report selectable for immediate or 8-hour delay.
Primary (AC) power:
• Works with virtually any UL 864 fire alarm control which uti-
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
• FCPS-24S6/-24S8: 120 VAC, 60 Hz, 3.2 A maximum.
• Wire size: minimum #14 AWG (2.0 mm²) with 600 V insulation.
Control input circuit:
• Requires input trigger voltage of 9.0 – 32 VDC.
• Trigger input voltage: 9 to 32 VDC.
• Trigger current: 2.0 mA (16 – 32 V). Per input: 1.0 mA (9 –
16 V).
• Self-contained in compact, locking cabinet — 15" (38.1 cm)
high x 14.5" (36.83 cm) wide x 2.75" (6.985 cm) deep.
• Includes integral battery charger capable of charging up to 18
AH batteries. Cabinet capable of housing 7.0 AH batteries.
Trouble contact rating: 5 amps at 24 VDC.
NOTIFIER® is a Honeywell company.
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applications
or anticipate all requirements. All specifications are subject to change without notice.
For more information, contact NOTIFIER. Phone: (203) 484-7161 FAX: (203) 484-7118
12 Clintonville Road, Northford, Connecticut 06472
DN-6927 • 07/20/04 — Page 1 of 3
Auxiliary power output: specific application power 500 mA SYNC FOLLOWER/GENERATOR NOTE
maximum.
In some installations, it is necessary to synchronize the flash
Output circuits:
• +24 VDC filtered, regulated.
timing of all strobes in the system for ADA compliance. Strobes
accomplish this by monitoring very short timing pulses on the
NAC power which are created by the FACP. When installed at
the end of a NAC wire run, the FCPS-24S6/-24S8 can track
(i.e., “follow”) the strobe synchronization timing pulses on the
existing NAC wire run. This maintains the overall system flash
timing of the additional strobes attached to the FCPS.
• 3.0 amps maximum for any one circuit.
• Total continuous current for all outputs (stand-alone mode):
for FCPS-24S6: 4.0 amps maximum; for FCPS-24S8: 6.0
amps maximum.
• Total short-term current for all outputs (NAC expander mode):
for FCPS-24S6: 6.0 amps maximum; for FCPS-24S8: 8.0
amps maximum.
Secondary power (battery) charging circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 VDC.
• Maximum charge current: 1.5 amps
• Maximum battery capacity: 18 AH.
When the FCPS-24S6/-24S8 is configured (via DIP switch set-
tings) as a “sync follower,” the FCPS’s NAC outputs track the
strobe synchronization pulses present at the FCPS’s sync in-
put terminal. The pulses originate from an upstream FACP or
other power supply.
When the FCPS-24S6/-24S8 is configured (via DIP switch set-
tings) as a “sync generator,” the FCPS’s sync input terminals
are not used. Rather, the FCPS is the originator of the strobe
synchronization pulses on the FCPS’s NAC outputs. In “sync
generator” mode, the sync type (System Sensor, Wheelock,
or Gentex) is selectable via DIP switch settings.
APPLICATIONS
Example 1: Expand notification appliance power an addi-
tional 6.0 amps (FCPS-24S6) or 8.0 amps (FCPS-24S8). Use
up to four Class B (Style Y) outputs or four Class A (Style Z)
outputs (using ZNAC-4). For example, the FACP notification
appliance circuits will activate the FCPS when reverse-polar-
ity activation occurs. Trouble conditions on the FCPS are
sensed by the FACP through the notification appliance circuit.
PRODUCT LINE INFORMATION
FCPS-24S6: 6.0 amp, 120 VAC remote charger power sup-
ply. Includes main printed circuit board, transformers, enclo-
sure (15" [38.1 cm] high x 14.5" [36.83 cm] wide x 2.75" [6.985
cm] deep), and installation instructions.
Example 2: Use the FCPS to expand auxiliary regulated
24-volt system power up to 4.0 amps (FCPS-24S6) or up to
6.0 amps (FCPS-24S8). Both resettable and non-resettable
power options are available. Resettable outputs are created
by connecting the resettable output from the FACP to one or
both of the FCPS inputs.
FCPS-24S8: 8.0 amp, 120 VAC remote charger power sup-
ply. Includes main printed circuit board, transformers, enclo-
sure (15" [38.1 cm] high x 14.5" [36.83 cm] wide x 2.75" [6.985
cm] deep), and installation instructions.
ZNAC-4: Class A (Style Z) NAC option module.
A77-716B: 12/24 VDC end-of-line relay for monitoring four-
wire smoke detector power.
Example 3: Use addressable control modules to activate
the FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
BAT-1270: Battery, 12 volt, 7.0 AH (two required, see BAT
Series data sheet DN-6933).
PS-1270: Battery, 12 volt, 7.0 AH (two required, see PS
Series data sheet DN-1109).
For example, an addressable control module is used to acti-
vate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output from
the FCPS provides power to the
addressable control module.
*Addressable FACPs are capable
of locating control and monitor
modules at distances of up to
10,000 feet (3048 meters).
AGENCY LISTINGS
AND APPROVALS
See the first page of this data
sheet for listing agencies and file
numbers. These listings and ap-
provals apply to the FCPS-24S6
and the FCPS-24S8. In some
cases, certain modules or appli-
cations may not be listed by cer-
tain approval agencies, or listing
may be in process. Consult fac-
tory for latest listing status.
6827blok.wmf
SIMPLIFIED
BLOCK DIAGRAM
Page 2 of 3 — DN-6927 • 07/20/04
6827bord.wmf
DN-6927 • 07/20/04 — Page 3 of 3