BB-DR-UPS40 [ETC]
PS, UPS CHARGER, METAL, 40A, 24V;型号: | BB-DR-UPS40 |
厂家: | ETC |
描述: | PS, UPS CHARGER, METAL, 40A, 24V |
文件: | 总3页 (文件大小:531K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
40A DC UPS Module
DR-UPS40
■
‧
‧
‧
‧
‧
‧
‧
‧
‧
SPECIFICATION
MODEL
DR-UPS40
DC VOLTAGE (Typ.)
RATED CURRENT
Note.5 24 ~ 29V
40A
DC INPUT /
DC BUS
VOLTAGE RANGE (Typ.)
CURRENT RANGE
CHARGE CURRENT (Typ.) Note.4 2A
EXTERNAL BATTERY (Typ.) 4 / 7 / 12AH / 24V
RELAY CONTACT RATING (max.) 30VDC, 1A
21 ~ 29V
0 ~ 40A
BATTERY
INPUT /
OUTPUT
Relay contact : Short when DC voltage between 21~29V(±3%), relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
DC BUS OK
Short when battery voltage falls below 21.9V(±3%) or battery failure is observed through the battery test function, relay contacts
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery OK : dark
Relay contact : Short when battery in discharge condition, relay contacts
LED(Yellow):light : Battery discharging ; dark : Battery is not discharging or discharging current<2.0A
-20 ~ +70℃
FUNCTION
BATTERY FAIL
Note.2
BATTERY DISCHARGE
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY -20 ~ +85℃, 10 ~ 95% RH
20 ~ 90% RH
ENVIRONMENT
VIBRATION
Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y, Z axes ; Mounting : Compliance to IEC600068-2-6
Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal :0.5KVAC
Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
SAFETY &
EMC
(Note 3)
Compliance to EN61000-4-2,3,4,5,6,8,11, heavy industry level, criteria A
161.9K hrs min. MIL-HDBK-217F (25℃)
55.5*125.2*100mm (W*H*D)
EMC IMMUNITY
MTBF
DIMENSION
OTHERS
NOTE
0.55Kg; 20pcs/12Kg/1.29CUFT
PACKING
℃
File Name:DR-UPS40-SPEC 2017-07-07
40A DC UPS Module
DR-UPS40
Mechanical Specification
Case No.923D
Unit:mm
125.2
LED TB2
1
2
3
4
1
2
3
4
5
6
TB1
Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1
2
3
4
BATTERY INPUT +
BATTERY INPUT -
DC INPUT -
DC INPUT +
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1
2
3
4
5
6
BAT DISC 1
BAT DISC 2
BAT FAIL 1
BAT FAIL 2
DC OK 1
DC OK 2
Block Diagram
Derating Curve
25Ax2
LOAD
100
80
+
+
24V
BATTERY
BAT.
TEST
CHARGE
CIRCUIT
LIMIT
INPUT
60
40
POWER
SUPPLY
DETECTION
CIRCUIT
20
-20
0
10
20
30
45
50
60
70 (VERTICAL)
DC
OK
BAT
BAT
FAIL DISCHARGE
AMBIENT TEMPERATURE (℃)
File Name:DR-UPS40-SPEC 2017-07-07
40A DC UPS Module
DR-UPS40
Suggested Application
1.Back up connection for AC interruption
DR-UPS40
24V
PSU
Battery
24V/40A max.
Load
BAT
- -DC
+
+
-
-
-
+
+
+
2.Combine redundancy module (DR-RDN20) to back up AC interruption or failure of PSU
DR-UPS40
DR-RDN20
24V
Battery
PSUA
PSUB
Load
BAT
DC
- -
+
+
-- -
+
-
-
-
-
+
+
+
+
File Name:DR-UPS40-SPEC 2017-07-07
相关型号:
©2020 ICPDF网 联系我们和版权申明