BB-CANOP [ETC]
CAN OPTICAL REPEATER W/TB;型号: | BB-CANOP |
厂家: | ETC |
描述: | CAN OPTICAL REPEATER W/TB 中继器 |
文件: | 总1页 (文件大小:303K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
CAN (Control Area Network)
Optical Isolator
Model CANOP
www.advantech-bb.com
PRODUCT FEATURES
•
•
Boost signals and increase node capacity of CAN networks
Protocol independent - works with different CAN protocols
and frame lengths
•
•
•
2,000V optical isolation protection from surges and spikes
Terminal block connections (copper)
DIN rail mount enclosure ideal for industrial cabinets
Model CANOP increases the node capacity of CAN (Control Area Network)
systems while protecting CAN networks from component destroying surges and
transients. The CANOP provides 2,000 VDC of optical isolation to separate and
protect critical segments of the system from the rest of the CAN Network. It is
protocol independent, allowing it to work with different CAN protocols and frame
lengths.
ORDERING INFORMATION
MODEL NUMBER
ISOLATION
CAN (COPPER)
CANOP
2,000 VDC
Terminal Blocks
ACCESSORIES
MDR-20-24 - 24 VDC DIN rail mount power supply, 1.0 A output power
According to the CAN specification, the CAN network must be terminated
at both ends. Networks that are not properly terminated may experience data
errors or miss data completely. The CANOP creates two new ends to the CAN
network. Space is provided on the board for a termination resistor on each side,
R6 and R8 (120 Ohm resistor recommended). If the CANOP is not at the end of
the network, it should not be terminated.
SPECIFICATIONS
SERIAL TECHNOLOGY
Baud Rate
CAN Connector
Turnaround
LEDs
250 kbps maximum
Terminal blocks
< 2 µ seconds
TD, RD (may be difficult to see at high baud rates)
The CANOP is bit-wise enable, allowing it to automatically adjust for
different baud rates. Bit-wise enable only enables the driver on every low bit
received. It also disables the driver on the receive side for the low bit plus
a maximum of 2µ seconds. This prevents data from echoing back from the
CANOP, but allows the nodes to respond back.
ISOLATION
2,000 VDC
POWER
Power
Source
150 mA @ 12V, fully loaded
External, 10-30 VDC, required
CAN in Industrial Automation
MECHANICAL
Dimensions
Enclosure
MTBF
MTBF Calc. Method
ENVIRONMENTAL
9.3 x 8.6 x 3.6 cm (4.0 x 3.4 x 1.4 in)
35mm DIN rail mount
269297
The multi-layer structure of Controller Area Network (CAN) allows any station on a
serial bus to communicate with any other station. There are also benefits in central
control and self-diagnosis and correction of transmission errors. A number of CAN-
based, higher level protocols have been developed for use in industrial automation
applications. CAN Application Layer (CAL), CAN Kingdom, CAN-open, DeviceNet
and Smart Distributed System are just a few of these variations.
MIL 217F Parts Count Reliability Prediction Method
Operating Temperature 0 to +70 °C (+32 to +158 °F)
Storage Temperature
-40 to +85 °C (-40 to +185 °F)
All product specifications are subject to change without notice.
CANOP_1717ds
orders@advantech-bb.com
support@advantech-bb.com
Corporate Headquarters: 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA 815-433-5100 Fax 433-5104
European Office: Westlink Commercial Park, Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
相关型号: