Solid State Remote Power Controller E-1071-623/627  
Description  
The E-T-A Solid State Remote Power Controllers E-1071-623/627  
are electronic control modules suitable for inductive loads such as  
electromagnetic valves (solenoids), magnetic brakes etc.  
They are used:  
for safe and quick switching of loads  
for monitoring the electrical condition of the loads  
for compensating different cable lengths  
The load connected to the relay should be operated with a higher voltage  
(DC 28…60 V) than its rated voltage (DC 24 V) because the load current  
is controlled electronically (pulse-controlled characteristics). This is  
to ensure that in industrial plants with different cable lengths (supply  
cables, load cables) an increased inrush current can be applied to  
each load. During hold duty the load current is reduced to a smaller  
value (approx. 60 % of the current rating), thus reducing the operating  
temperature and extending the life of the loads.  
E-1071-623  
The double pole electronic switching output prevents inadvertent  
start-up or dangerous machine movements as may arise upon a  
ground fault in systems with ungrounded power supply (‘IT systems’)  
(see EC Machinery Directive or EN 60204 part 1 “Safety of Machinery  
- Electrical Equipment of Machines”, para 9.4.3.1).  
Technical data (T  
= 25 °C, U = DC 48 V)  
B
ambient  
Rated voltage  
Operating voltage UB  
DC 48 V  
DC 28...60 V  
(see Technical description)  
adjustable between 0.1...3.1 A via switch  
and potentiometer on the front side  
Current rating IN  
Typical applications  
Current consumption I0  
(US = »0«)  
Residual ripple for  
all voltages  
Reverse polarity protection UB (terminals 1 and 2), integral  
Fail Save  
Insulation voltage  
l
Double pole switching of inductive actuators such as electromagnetic  
valves or magnetic clutches in machinery and equipment  
Monitoring the electrical operability of loads  
Protection and monitoring of load circuit cables  
Status indication, failure indication in load circuit visually  
(via LEDs or red tripped button) and via potentialfree status outputs  
Double pole split up of the load circuit manually or electrically in  
the event of overload or short circuit  
typically 16 mA  
l
max. 5 % (3 phase bridge)  
l
fuse  
l
2.5 KV between load circuit, control circuit  
and status signal circuit  
l
Load circuit  
Load output  
NPN transistor, minus switching,  
pulse-controlled (approx. 180 Hz)  
DC 24 V/adjustable between 0.1...3.1 A  
up to 10 % more than pickup current  
typically 60 % of the set rated current IN  
approx. 4.5 A  
Load rating  
Features  
Switch-on current IE  
Holding current IH  
Short circuit  
l
Designed for inductive loads (DC 24 V)  
Individual adjustment to various load currents  
(standard: IN = 0.1...3.1 A)  
Significant reduction of power loss in the load by pulse-controlled  
disconnection current  
Wire break monitoring  
Physical isolation  
l
in the ON and OFF condition (RED LED)  
2-pole in the load circuit,  
by manual circuit breaker release  
or after short circuit disconnection  
2 x ø 2 mm (current proportional voltage:  
1 V = 1 A )  
l
characteristics  
l
Double pole switching output, short-circuit proof (short-circuit  
limitation); physical disconnection from supply  
Current measuring plugs  
l
l
Free-wheeling circuitry  
(see Technical description)  
integral electronic control with quick  
disconnection  
Inrush current and holding current monitoring  
Physical isolation:  
- optocoupler in the control circuit  
- physical disconnection of load circuit, manually or in the event  
of a short circuit  
- optocoupler for status outputs  
Reverse polarity and overvoltage protection in the control, load  
and status circuits  
Control current indication by YELLOW LED  
O.K. indication by GREEN LED  
Wire break indication by RED LED (load circuit)  
Fault indication by RED LED  
(short circuit, over/undervoltage, setting error)  
Two status outputs for PLCs for evaluation  
(status indication, ON indication)  
^
5
Control circuit  
Control  
Control voltage US  
optocoupler in control input  
»0« = DC 0…5 V  
»1« = DC 8.5…35 V  
Control current IS  
typically 5...10 mA  
l
Switching frequency fmax  
Control signal (US = »1«)  
Protection  
1 Hz  
YELLOW LED lights (Icontrol flowing)  
reverse polarity protection (diode)  
l
l
l
l
Status outputs  
2 signal outputs  
ON indication/function indication  
- physically isolated by optocoupler  
- transistor outputs, plus switching  
- auxiliary voltage UA: DC 12...60 V  
- max. 50 mA per output  
l
l
- integral free-wheeling diode  
- reverse polarity and overvoltage  
protection  
Quick disconnection (do not connect a free-wheeling diode to the  
load as the free-wheeling current is controlled electronically)  
Break time < make time  
ON indication  
(terminal 8)  
US = »0« : output non-conductive  
< 70 ms switch-off signal delay  
US = »1« : output connecting plus potential  
(term. 10) to term. 8 only as long  
as load current flows, not with  
wire break or short circuit  
< 15 ms switch-off signal delay  
fault: output non-conductive  
no fault: output connecting plus potential  
(terminal 10) to terminal 9  
Function indication  
(terminal 9)  
1646  
www.e-t-a.de  
1
Solid State Remote Power Controller E-1071-623/627  
Technical data (T  
= 25 °C, U = DC 48 V)  
Technical description  
ambient  
B
Rated current IN, hold current IH  
General data  
The current rating of the applicable load at its rated voltage should  
be set between 0.1...3.1 A. The holding current of the load is internally  
adjusted to 60 % of the set current rating. This holding current can  
be measured by means of a voltmeter connected to the 2 mm current  
Ambient temperature  
Terminals  
0…+60 °C (without condensation)  
1071-623: screw terminals  
1071-627: screw-less spring-loaded  
terminals  
^
measuring plugs (current-proportional voltage: 1 V = 1 A).  
Connection: max. 2 x 2.5 mm2 solid  
max. 2 x 1.5 mm2 flex with  
sleeve  
Setting the current rating  
Housing  
clamping plate: polycarbonate GV, blue  
cover: polycarbonate, black  
track-mountable to EN 50022-35  
The current rating is set by means of a rotary switch (switch  
setting 0 A - 1 A - 2 A) and a 270° potentiometer (setting range  
between 0.1...1.1 A). The sum of the two settings should equal the  
current rating of the load.  
Mounting  
Self-extinguishing properties to UL 94: V = 0; VDE 0304: grade 1  
Degree of protection  
Mounting dimensions  
Mass  
housing, terminals IP20 DIN 40050  
45 x 74 x 128 mm  
approx. 170 g  
Example: 24 V load with IN = 1.5 A  
Setting: switch 1 A + potentiometer 0.5 A  
Technical description  
1
2
3
4
5
Operating voltage UB  
Steuerstrom  
O.K.  
The max. operating voltage of the SSRPC is approx. DC 60 V. The  
min. operating voltage required for 24 V solenoids depends on the  
overall ohmic resistance in the load circuit. The switch-on current is  
reduced by:  
Fehler  
Drahtbruch  
1
2
0
GERMANY  
IN/A  
0,8  
+
E-1071-623  
DC 24 V-Last  
0,1-3,1 A  
0,6  
0,4  
- the voltage drop on the load cable  
0,2  
1,0  
1,1  
- the load resistance increasing with the operating temperature of  
the load.  
0,1  
+
I
Last  
= 0,6 x IN  
^
1V =1A  
Minimum operating voltage UB min  
6
7
8
9
10  
IN  
Cable length  
Cable size UB min  
2
1.5 mm  
2.5 mm  
33/35/37/40 V  
32/33/35/37 V  
1 A  
2x50 m/2x100 m/2x200 m/2x300 m  
2
2
1.5 mm  
2.5 mm  
35/38/44/49 V  
34/35/39/42 V  
2 A  
3 A  
2x50 m/2x100 m/2x200 m/2x300 m  
2x50 m/2x100 m/2x200 m/2x300 m  
2
Faulty setting of current rating  
The red LED (failure indication) blinks in the event of a faulty setting.  
The load is disconnected only after approx. 15 sec if the current rating  
value is not corrected and the red LED will be permanently lighted.  
Reset is only possible by switching on again.  
The tolerance range, in which faulty setting will not be indicated, is  
approx. 30 % of the holding current.  
2
1.5 mm  
2.5 mm  
37/41/50/58 V  
35/38/42/48 V  
2
The load capacity is no longer ensured when the minimum operating  
voltage falls below UB min = 28 V. The RED LED (fault) will indicate  
and the output will be switched off. Only when an operating voltage  
of 29.4 V is exceeded will the load be switched on again and normal  
operation status is restored.  
Ordering information  
Resistance increase in the load circuit:  
1.5 mm2 cable  
2.5 mm2 cable  
approx. 2.8 Ω/100 m distance  
approx. 1.6 Ω/100 m distance  
5
Type No.  
E-1071  
SSRPC  
Terminals  
Maximum operating voltage UB max  
623  
627  
screw terminals  
The load capacity is no longer ensured when the max. operating  
voltage UB max = 60 V is exceeded. The RED LED (fault) will indicate  
and the output will be switched off. Only when the operating voltage  
falls below 57 V will the load be switched on again and normal opera-  
tion status is restored.  
screw-less connectors  
Voltage rating of load  
DC 24 V  
Current rating  
0.1 A...3.1 A  
E-1071  
-
623 - DC 24 V - 0.1 A...3.1 A ordering example  
Switch-on current IE = pickup current  
The output transistor connects the operating voltage to the inductive  
load until actual switch-on of the solenoid (pickup current). After this  
period the load current is set back to holding current IH.  
I
I
N = Current rating  
E = Switch-on current/  
pickup current  
Current  
IH = Holding current  
IN  
IE  
IH  
quick disconnection  
ca. 10...100 ms  
ON  
time t  
OFF  
2
www.e-t-a.de  
1646  
Solid State Remote Power Controller E-1071-623/627  
Operating modes  
Schematic diagram  
mode  
fault-free  
wire break  
load short  
circuit (1)  
U too low/  
B
high (2)  
faulty  
setting  
ꢃꢄꢅꢅꢆꢇꢈ ꢅꢉꢈꢊꢇꢋ  
ꢌꢅꢆꢍꢆꢈꢈꢊꢇꢋ  
ꢌꢎꢏꢍꢊꢃꢉꢐ  
ꢊꢍꢑꢐꢉꢈꢊꢑꢇ  
control input  
(terminals 6 and 7)  
ꢑꢒꢒ  
»0«  
»1«  
»0«  
»1«  
»0«  
»1«  
»0«  
»1«  
LED YELLOW – control c.  
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
0
0
1
1
0
0
1
0
0
0
1
1
0
0
1
1
1
ꢄꢆꢇ  
ꢈꢉꢊꢋꢋꢋ6ꢌ ꢍ ꢎꢏꢐ  
ꢚꢂꢥꢋ 6ꢋ1ꢬ  
ꢄꢆꢂ  
1ꢌ  
LED GREEN - O.K.  
LED RED - wire break  
LED RED - fault  
ꢜꢖꢂꢖꢢꢜ  
ꢡ  
4
ꢣꢢꢔꢕꢖꢓꢁꢔ  
ꢕꢁꢔꢖꢙꢁꢀ ꢂꢔꢃ  
ꢚꢁꢔꢓꢖꢁꢙꢓꢔꢗ  
ꢛꢀꢛꢕꢖꢙꢁꢔꢓꢕꢜ  
ꢍꢑꢐꢆꢇꢑꢊꢗ  
ꢀꢁꢂꢃ  
ꢜꢖꢂꢖꢢꢜ  
ꢇ  
ꢁꢤꢛꢙꢂꢖꢓꢁꢔ  
status function  
(terminal 9)  
status operation  
(terminal 8)  
1
0
1
1
0
0
0
0
0
0
0
0
0
0
0
0
ꢅꢆꢂ  
ꢚꢂꢥꢋ ꢦꢏ  
ꢄꢆꢠ  
6
ꢕꢁꢔꢖꢙꢁꢀ  
ꢓꢔꢤꢢꢖ  
physical isolation  
0
0
0
0
0
1
0
0
ꢔꢕꢖ  
ꢅꢆꢠ  
ꢗꢘ ꢗꢔ ꢙꢖ ꢙꢖ  
Notes:  
ꢑꢒꢎꢅꢓꢔꢃꢓꢕꢂꢖꢓꢁꢔ ꢕꢢꢙꢙꢛꢔꢖꢅꢤꢙꢁꢤꢁꢙꢖꢓꢁꢔꢂꢀ  
ꢭꢁꢀꢖꢂꢗꢛ ꢁꢢꢖꢤꢢꢖ ꢆꢈꢮꢐ  
1 Short circuit: load (+) to load (-)  
2 Underoltage: device disconnects at 28 V and reconnects at 29.4 V  
Overvoltage: device disconnects at 60 V and reconnects at 57 V  
1 - LED status output carries to plus potential  
0 - LED status output is non-conductive  
Dimensions  
129 OFF condition  
5.08  
124 ON condition  
4.88  
121  
45  
1.77  
4.76  
119.5  
4.70  
5
rail EN 50022-35x7.5  
(not included in delivery)  
mm  
inch  
This is a metric design and millimeter dimensions take precedence (  
)
1646  
www.e-t-a.de  
3
Solid State Remote Power Controller E-1071-623/627  
Terminal selection  
E-1071-623 (0.1 - 3.1 A)  
E-1071-627 (0.1 - 3.1 A)  
Terminal  
1
2
3
4
5
Operating voltage +UB: max. DC 60 V  
6
Control voltage +US: max. 35 V  
Operating voltage (-)  
7
Control voltage -US  
Load (+)  
8
Status output “operation” (max. 50 mA)  
Status output “function” (max. 50 mA)  
Auxiliary voltage +UA for status outputs: max. DC 60 V/100 mA)  
Load (-)  
9
Auxiliary voltage -UA for status outputs  
10  
5
4
www.e-t-a.de  
1646  
Solid State Remote Power Controller E-1071-623/627  
Application note:  
Controlling and monitoring of solenoid valves in combination with LED valve plugs  
Possible configuration of E-1071-62x  
Please note:  
lꢀ  
In the event of using a plug or suppressor element not  
with screw terminals:  
with screwless terminals:  
E-1071-623-DC 24 V-0.1...3.1 A  
E-1071-627-DC 24 V-0.1...3.1 A  
recommended, the wire break monitoring function might be  
limited in the not activated condition.  
Often DC 24 V solenoids with a low power rating are used which are  
to be controlled and monitored by the above mentioned devices.  
Sometimes these solenoids are fitted with solenoid valve plugs, e.g.  
made by Hirschmann, and hold a small electronic pcb  
- with LED,  
- a series resistor  
- a protective diode connected in anti-parallel to the LED  
The following components can be recommended:  
l
Recommended valve plugs with LED, Hirschmann  
- type GDML 2011 LED 24 YE, contains the pcb  
type GDME-LED 24 YE  
- type GDML 2011 LED 24 RD, contains the pcb  
type GDME-LED 24 RD  
status indication (LED) with a protective diode connected in  
anti-parallel  
ꢀꢁꢂ  
ꢀꢁꢂ 1  
ꢀꢃꢂ  
ꢀꢃꢂ ꢄ  
l
Recommended adapter with LED, Murr Elektronik  
- suppressor element model B – 10 mm LED,  
24 V DC/50 VA/W, part no.: 3124875  
5
- suppressor element model BI – 11 mm LED,  
24 V AC/DC/50 VA/W, part no.: 3124215  
- suppressor element model C – 8 mm LED,  
24 V AC/DC/50 VA/W, part no.: 312811  
All dimensions without tolerances are for reference only. In the interest of improved design,  
performance and cost effectiveness the right to make changes in these specifications wit-  
hout notice is reserved.Product markings may not be exactly as the ordering codes. Errors  
and omissions excepted.  
1646  
www.e-t-a.de  
5
5
6
www.e-t-a.de  
1646  

相关型号:

E-1071-627-DC24V-2.0A

Designed for inductive loads (DC 24 V)
ETAL

E-1071-627-DC24V-3.1A

Designed for inductive loads (DC 24 V)
ETAL

E-1072-128

Nennspannung DC 24 V (19,2...36 V)
ETAL

E-1072-128-DC24V-3A

Nennspannung DC 24 V (19,2...36 V)
ETAL

E-1072-210-DC24V-1A

Voltage rating DC 24 V (19.2...36 V)
ETAL

E-1072-210-DC24V-2A

Voltage rating DC 24 V (19.2...36 V)
ETAL

E-1072-220

Voltage rating DC 24 V (19.2...36 V)
ETAL

E-1072-220-DC24V-1A

Voltage rating DC 24 V (19.2...36 V)
ETAL

E-1073

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0100-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0100-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0102-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL