E-1072-220 [ETAL]

Voltage rating DC 24 V (19.2...36 V);
E-1072-220
型号: E-1072-220
厂家: ETAL Group    ETAL Group
描述:

Voltage rating DC 24 V (19.2...36 V)

文件: 总4页 (文件大小:206K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Solid State Remote Power Controller E-1072-2...  
Description  
The E-T-A Solid State Remote Power Controller E-1072-2.. complies  
with the EC Machinery Directive 98/37/EG and meets the requirements  
of EN60204 part 1 “Electrical equipment of machinery, safety of  
machinery” in ungrounded DC 24 V supply systems (“IT systems”).  
The E-1072-2.. is a double pole electronic switching amplifier for  
magnetic valves (hydraulic and pneumatic mechanisms), magnetic  
brakes and magnetic couplings with rated voltage DC 24 V and a max.  
current rating of 1 A or 2 A. It combines true circuit breaker characteristics  
with additional diagnostic functions.  
Why use the E-1072-2..  
E-1072-220  
l
for double pole switching of actuators (magnetic valves, magnetic  
brakes) in machinery and equipment  
for monitoring the electronic function of the loads and signal to the PLC  
for preventing a voltage dip of the DC 24 V output voltage in a  
l
Technical Data (T = 25 °C, U = DC 24 V) (T = ambient temperature at U )  
U
S
U
N
l
switch-mode power supply, in the event of a short circuit, as a true  
2 pole, remotely controllable electronic circuit breaker  
for protecting the cables of the load circuit  
for status signalling and for visually indicating load circuit  
faults (LEDs or RED trip button) via potential-free signal contacts  
Voltage rating UN  
Operating voltage US  
Current rating IN  
Current consumption I0  
(UContr = “0”)  
Power loss Pmax (IN= 1 A) typically 1.6 W  
Residual ripple for all voltages max. 5 % (3 phase bridge)  
Reverse polarity protection US integral -> fault release, LEDs not  
lighting  
DC 24 V  
DC 19.2...36 V  
max. 1 A or 2 A  
typically 25 mA  
l
l
l
for double-pole physical isolation of the load circuit – manually  
or electrically in the event of a failure (short circuit/overload)  
Features  
Caution: Ensure free travel of actuator  
button.  
AC 500 V (control circuit, load circuit,  
fault indication “Err1” and “Err2”)  
indication “BM”  
l
Voltage rating DC 24 V (19.2...36 V)  
Current rating IN max. 1 A or 2 A (min. load current 30 mA)  
Activates and monitors DC 24 V magnetic valves  
PLC controllable 2 pole remote power controller with physical  
Insulation voltage  
l
l
l
Load Circuit  
isolation of control input  
- Switching output with integral current limitation to 2 x IN  
- Disconnection of load in the event of short circuit or overload,  
followed by double pole physical isolation of load  
- Permanent wire break monitoring of load circuit  
- Group fault signalisation via relay contact “Err1”  
- Additional signal contact “Err2” when integral circuit breaker  
has tripped due to short circuit or overload in the load circuit  
- LED displays: LED green: OK  
Load output  
(term. 31-term. 32)  
Max. load data  
two pole switching output (minus and  
plus switching), MOS transistors  
DC 24 V/1 A or 2 A (no derating over the  
entire temperature range!)  
DC 24 V / 50 mA (wire break  
threshold 30 mA)  
Min. load data  
Voltage drop at IN (with I =1 A) typically 0.8 V  
Switching times (ton/toff  
Overload disconnection  
Trip time (Iload = 1.5 x IN)  
Short-circuit current IK  
Trip time (upon IK)  
N
)
typically 1 ms (resistive load)  
approx 1.15 x IN  
typically 1 s  
typically 2 x IN current limitaton  
typically 300 ms at IN = 1 A,  
100 ms at IN = 2 A, 2-pole isolation of  
load circuit after approx. 20 ms  
–> RED LED indicates, fault indication F  
“Err1” and “Err2”  
LED red:  
Error  
LED yellow In/Ctrl (control current indication)  
- Integral reverse polarity protection and overload protection for  
control and load circuit  
- No back-up fuse required due to integral fail-safe element  
- Track-mountable, width 22.5 mm  
5
Additional feature E-1072-210  
- additional “status indication” relay output to facilitate confirmation  
to a PLC, for example, of activation and a load current > 30 mA.  
Wire break monitoring  
with the load switched on or off; RED LED  
“Error” lighted, group fault signalisation  
“Err1”  
Additional feature E-1072-220  
(see fig. “inrush current curve magnetic valves”)  
(UContr= “0”) wire break threshold R  
(UContr= “1”) minimum current I  
> 30 kΩ  
< 30 mA  
load  
load  
- Analogue output 4-20 mA proportional to load current enables  
permanent monitoring of magnetic valve circuits as well as  
recording of the load current via ET200 sub-assemblies or field  
bus modules (with analogue input). In addition it is possible to  
check the inrush current characteristic curve of a magnetic valve  
to determine whether the armature of the valve has moved or is  
stuck.  
Supervision of load circuit with the load switched on, the load  
current is monitored via the two  
switching outputs GREEN LED indicates  
(OK signal), Iload > 30 mA  
Leakage current (UContr = “0”) typically 1 mA  
Free-wheeling circuitry  
Load current measurement no isolation of load circuit required as a  
integral  
(term. 33: +shunt/  
term. 34: -shunt)  
IN = 1 A: 0.2 Ω/1 %, IN = 2 A: 0.1 Ω/1 %  
measuring shunt is integral with the device.  
Measurement by voltmeter terminal 33 -  
terminal 34 (200 mV = IN)  
Isolation of load circuit  
2-pole by relay contacts  
- by manual release of RED button  
- approx. 20 ms after electronic tripping  
due to overload or short circuit (“OFF”)  
1646  
www.e-t-a.de  
1
Solid State Remote Power Controller E-1072-2...  
Ordering information  
Technical Data (T = 25 °C, U = DC 24 V) (T = ambient temperature at U )  
U
B
U
N
Type  
E-1072  
Control circuit  
Solid State Remote Power Controller  
Version  
Control “In/Ctrl”  
internal low-level signal relay in control  
input (with integral free-wheeling diode)  
“0” : 0...2.4 V  
“1” : 18...32 V  
typically 5...10 mA  
210  
220  
with additional option: status indication  
with additional option: analogue output 4-20 mA  
Voltage rating of load  
DC 24 V  
Control voltage U  
Control current I  
Switching frequency fmax  
Control signal (UContr “1”) “In/Ctrl” YELLOW LED lights with IContr  
flowing  
10 Hz  
Current rating  
1 A or 2 A  
E-1072  
-
210  
-
DC 24 V - 1 A ordering example  
Protection  
reverse polarity protection (diode),  
overvoltage protection (varistor)  
Fault indication  
“Err1”  
Status matrix  
group fault signalisation  
potential-free relay contact N/O, (closed  
circuit principle) DC 30 V/5 mA...1 A  
relay contact “Err1” open  
Operating  
fault-free  
Short circuit Wire break in load  
/ overload in ciruit  
load circuit  
other  
faults  
status  
operation  
Fault indication “Err1”  
- wire breakage in the load circuit  
- load current < 30 mA  
- other faults (ground fault in load circuit  
or internal fault)  
- overload/short circuit (= “Err2”)  
- LED RED “Error” lighted  
- LED GREEN “O.K.” not lighted  
- relay contact “Err1” closed  
typically 600 ms  
Control input  
“0”  
“1”  
“1”  
“0”  
“1”  
“0”  
OFF  
2-pole  
non-  
ON  
2-pole  
conductive  
OFF  
2-pole  
non-  
OFF  
2-pole  
non-  
ON  
2-pole  
conductive  
OFF  
2-pole  
non-  
Load output  
conductive  
conductive conductive  
conductive  
Load circuit  
isolated 2  
pole (via relay  
contacts)  
no  
no  
yes  
no  
no  
no  
Signal delay  
“Err2”  
fault indication  
potenial-free auxiliary contact,  
make contact N/O,  
Indication  
YELLOW LED  
“In/Ctrl”  
0
1
0
1
1
0
1
0
1
0
0
1
1
0
1
0
0
1
DC 30 V/5 mA....1 A  
GREEN LED  
“O.K.”  
Fault indication “Err2”  
signal contact “Err2” closed  
- overload or short circuit in the load circuit  
- LED RED “Error” lighted  
- LED GREEN “O.K.” not lighted  
- relay contact “Err1” open  
- auxiliary contact “Err2” closed  
- RED button “OFF”  
- reset required  
- 2-pole physical isolation in load circuit  
- manual release “OFF”  
RED LED  
“Error”  
relay contacts  
“Err1”  
(group fault)  
closed  
closed  
open  
open  
open  
open  
auxiliary  
contacts “Err2”  
(circuit breaker)  
open  
ON  
open  
ON  
closed  
open  
ON  
open  
ON  
open  
ON  
RED operating/  
reset button  
OFF  
“OFF”  
- reverse polarity of US (LEDs not indicating)  
Option –210  
with status indication “BM”  
potential-free relay contact  
DC 30 V / 5 mA...1 A  
relays contact  
“BM” indication  
option-210  
open  
4 mA  
closed  
open  
open  
4 mA  
open  
4 mA  
open  
4 mA  
Function “BM”  
Option –220  
relay contact closed, if Iload > 30 mA  
relay contact open, with wire breakage  
and after trip of circuit breaker  
analogue output proportional to load current  
“ANA” 4-20 mA, max. load 500 Ω on -US  
(term. 44)  
analgo output  
option-220  
4 mA...  
20 mA  
> 20 mA,  
4 mA  
5
Remark  
ground  
fault in  
load  
circuit or  
internal  
fault  
I
:
Load  
>30 mA  
< 1 A  
RED button to  
be reset  
I
:
Load  
available  
<30 mA  
(or 2 A)  
U
U
Contr = “0” –> 4 mA  
Contr = “0” –> 4 mA with 0 A (load current)  
20 mA with IN  
Accuracy: 5 % of measured value  
1 = LED lights  
0 = LED does not light  
General data  
Operating modes at:  
Ambient Temperature  
Storage temperature  
Terminals  
0...+50 °C (without condensation)  
-20...+70 °C  
-
-
reverse polarity: indication of fault “Err2”; LEDs not illuminated!  
manual release “OFF” (RED button out): indication of fault “Err1”  
and “Err2”, additionally lighted LED RED “Error”.  
with US = 0 V: group fault signalisation »Err1« (closed circuit  
principle)  
COMBICON MSTBO 2.5/4 1x2.5 mm2 max.  
16-pole  
-
Some are double terminals -> loop-through  
possibility (continuous load max. 6 A)  
not required because of integral fail-safe  
element with VDE approval  
PA 66-FR  
symmetric rail to EN 50022-35  
3 g, to IEC 60068-2-6 test Fc  
IP20 housing  
Back-up protection  
for SSRPC  
Housing material  
Mounting  
Vibration  
Degree of protection  
(IEC 529/DIN 40050)  
EMC  
IP20 terminals  
emitted interference EN 50081-1  
interference suppression EN 61000-6-2  
22.5 x 99 x 122 mm (w x h x d)  
approx. 130 g  
Mounting dimensions  
Mass  
2
www.e-t-a.de  
1646  
Solid State Remote Power Controller E-1072-2...  
Dimensions  
Connection diagram  
ꢒꢒꢕꢐ  
ꢕꢁꢁ6  
ꢂ1 ꢂꢂ ꢂꢆ ꢂ4  
11 1ꢂ 1ꢆ 14  
ꢇꢈꢄꢁꢉꢊꢋ  
ꢏꢊꢊꢐꢊ  
ꢌꢍꢎꢍ  
ꢌꢑꢑ  
1072 -220-  
ꢀꢁ ꢂ4ꢃ1ꢅ  
ꢆ1 ꢆꢂ ꢆꢆ ꢆ4  
41 4ꢂ 4ꢆ 44  
ꢂꢃꢄꢄꢅꢆꢇꢈꢉꢊꢋ ꢇꢊꢈꢋ  
ꢆꢌ ꢍꢎꢏ ꢐꢑꢑꢒꢒꢓꢔꢐ  
114  
ꢕꢔ1ꢐ  
4ꢕ4ꢀ  
mm  
)
This is a metric design and millimeter dimensions take precedence (  
inch  
Basic circuit diagram -210  
Basic circuit diagram -220  
ꢙ  
ꢀꢁꢙ  
ꢆꢈꢉ  
ꢊꢆꢈꢈꢄ ꢀꢁꢂꢃꢄꢅꢆ  
ꢇꢁꢂꢃꢄꢅꢆ  
11ꢎ 14  
ꢩꢦꢒ  
ꢱꢦꢒ  
red  
ꢱꢦꢓꢁꢌꢈꢄ  
11  
ꢩꢦꢓꢁꢌꢈꢄ  
ꢠꢄꢃꢃꢌ  
44  
4ꢘ  
11  
44  
4ꢯ  
1ꢯ  
14  
ꢔꢕꢖꢓ ꢗꢕꢔꢈ  
ꢇꢞꢍꢊ ꢆꢞꢇꢃ  
ꢄꢋꢄꢏꢉꢅꢂꢐꢑꢏ ꢏꢂꢐꢉꢅꢂꢋ ꢒꢐꢑꢉ  
ꢃꢊꢃꢋꢈꢄꢁꢌꢍꢋ ꢋꢁꢌꢈꢄꢁꢊ ꢎꢌꢍꢈ  
ꢏꢐꢑꢒꢓ ꢡꢄꢄꢁꢄ ꢔꢌꢑꢓꢈꢄꢊ  
ꢁꢂꢃꢄꢅ  
ꢆꢂꢇꢈꢄꢉ  
ꢀꢁꢂꢃꢄ  
ꢅꢁꢆꢇꢃꢈ  
ꢊꢄꢋꢋꢂꢃ  
ꢉꢃꢊꢊꢁꢂ  
ꢖꢗ ꢋꢆꢆꢃꢆ ꢑꢄꢒꢂꢅꢆꢓ  
ꢆꢈꢞꢈꢎꢆ  
ꢚ 1 ꢛꢜ  
ꢖ 1 ꢗꢘ  
ꢝꢞꢀΩ/1ꢟ  
ꢙꢚꢛΩ/1ꢜ  
ꢀ1  
ꢛ1  
ꢚ ꢀ ꢛꢜ  
ꢝꢞ1Ω/1ꢟ  
ꢌꢪꢫꢪꢎ  
ꢖ ꢛ ꢗꢘ  
ꢙꢚ1Ω/1ꢜ  
4 ꢬ ꢍꢟ ꢭꢪ  
ꢢꢭꢮꢤ  
ꢛꢛ  
ꢭꢕꢰꢣ  
ꢱꢟꢟ Ω  
ꢇꢁꢮ  
ꢀꢀ  
ꢎ4  
ꢎꢎ ꢎꢀ  
ꢋꢂꢡꢢ  
ꢘ1  
ꢤ  
41  
ꢌꢋꢆꢆꢍꢎ  
4ꢀ  
ꢀꢎ  
ꢌꢋꢆꢆ1ꢎ  
44  
ꢯ4  
ꢯꢯ ꢯꢛ  
ꢰ ꢊꢁꢞꢟ  
ꢯ1  
41  
ꢢꢡꢄꢄꢛꢤ  
4ꢛ  
ꢛꢯ  
ꢢꢡꢄꢄ1ꢤ  
ꢛ4  
ꢇꢠꢒꢐꢉ  
ꢌꢏꢐꢐꢎ  
ꢆꢝꢎꢌꢈ  
ꢢꢏꢣꢣꢤ  
ꢙꢚꢃꢛꢄ ꢖꢄ ꢌꢏꢐꢐꢎ ꢜꢃꢄꢉꢖꢅꢖꢃꢄ ꢛꢖꢅꢚ ꢄꢃ ꢓꢃꢕꢉ ꢝꢁꢞ ꢟ ꢠꢡ  
ꢕꢄꢉ red ꢀꢁtton ꢅꢆꢖꢢꢢꢈꢉꢣ  
ꢒꢝꢁꢂꢌ ꢍꢌ ꢢꢏꢣꢣꢤ ꢋꢁꢌꢟꢍꢈꢍꢁꢌ ꢂꢍꢈꢝ ꢌꢁ ꢊꢁꢞꢟ ꢥꢦ ꢖ ꢙ ꢧꢨ  
ꢌꢑꢄꢒꢂꢅꢆꢓꢎ  
ꢌꢏꢣꢧꢣꢎ  
ꢌꢋꢆꢆꢃꢆꢎ  
ꢌꢏꢐꢐꢎ  
ꢌꢋꢆꢆ1ꢎ  
ꢌꢋꢆꢆꢍꢎ  
ꢌꢪꢫꢪꢎ  
ꢇ ꢤꢋꢥ ꢦꢈꢓꢓꢃꢛ  
ꢇ ꢤꢋꢥ ꢊꢆꢈꢈꢄ  
ꢇ ꢤꢋꢥ ꢆꢈꢉ  
ꢢꢔꢌꢑꢓꢈꢄꢊꢤ  
ꢢꢏꢚꢫꢚꢤ  
ꢢꢡꢄꢄꢁꢄꢤ  
ꢢꢏꢣꢣꢤ  
ꢢꢡꢄꢄ1ꢤ  
ꢢꢡꢄꢄꢛꢤ  
ꢢꢭꢮꢤ  
ꢩ ꢐꢡꢪ ꢉꢃꢊꢊꢁꢂ  
ꢩ ꢐꢡꢪ ꢠꢄꢃꢃꢌ  
ꢩ ꢐꢡꢪ ꢄꢃꢟ  
ꢞꢌꢟ red ꢀꢁtton ꢈꢄꢍꢀꢀꢃꢟꢚ  
ꢇ ꢆꢈꢉ ꢨꢩꢅꢅꢃꢄ  
ꢩ ꢄꢃꢟ ꢬꢎꢈꢈꢁꢌ  
ꢇ ꢆꢈꢓꢕꢦ ꢜꢃꢄꢅꢕꢜꢅ  
ꢇ ꢗꢖꢊꢄꢕꢓ ꢜꢃꢄꢅꢕꢜꢅ  
ꢇ ꢕꢄꢕꢓꢃꢊꢩꢈ ꢃꢩꢅꢢꢩꢅ  
4ꢬꢍꢟ ꢭꢪ  
ꢩ ꢄꢃꢊꢞꢉ ꢋꢁꢌꢈꢞꢋꢈ  
ꢩ ꢆꢍꢠꢌꢞꢊ ꢋꢁꢌꢈꢞꢋꢈ  
ꢩ ꢄꢃꢊꢞꢉ ꢋꢁꢌꢈꢞꢋꢈ  
5
Inrush current curve magnetic valve  
ꢖꢃꢀꢗ  
ꢓꢑꢂꢂꢋꢐꢉ  
1
ꢀꢁꢁꢂꢃꢄꢅ 4ꢆ ꢇꢈ  
ꢆ ꢎ  
ꢙꢛ  
ꢓꢃꢐꢉꢂꢃꢖ  
ꢊꢐꢁꢑꢉ  
ꢙꢚꢚ  
ꢉꢊꢇꢋ ꢌꢉꢍ  
1
ꢏꢐꢂꢑꢈꢒ ꢓꢑꢂꢂꢋꢐꢉ ꢓꢑꢂꢔꢋ ꢊꢕ ꢀꢂꢇꢀꢉꢑꢂꢋ ꢃꢕ ꢔꢀꢖꢔꢋ ꢒꢀꢈ ꢇꢃꢔꢋꢗ ꢀꢐꢗ ꢂꢋꢀꢓꢒꢋꢗ ꢊꢉꢈ ꢕꢊꢐꢀꢖ ꢁꢃꢈꢊꢉꢊꢃꢐꢅ  
ꢏꢐꢂꢑꢈꢒ ꢓꢑꢂꢂꢋꢐꢉ ꢓꢑꢂꢔꢋ ꢊꢕ ꢀꢂꢇꢀꢉꢑꢂꢋ ꢃꢕ ꢔꢀꢖꢔꢋ ꢒꢀꢈ ꢐꢃꢉ ꢇꢃꢔꢋꢗꢅ  
1646  
www.e-t-a.de  
3
Solid State Remote Power Controller E-1072-2...  
Terminal selection  
ꢀꢁꢂ ꢃꢄꢅꢆ  
ꢀ1 ꢀꢀ  
11 1ꢀ  
Level Terminal Remark  
11  
12  
+UContr (Control voltage plus)  
not used  
ꢀꢁ  
1ꢁ  
ꢀ4  
14  
ꢂꢃꢄꢃꢂ ꢀ  
ꢂꢃꢄꢃꢂ 1  
DC 18...32 V  
1
2
}
13 / 14 -UContr (Vontrol voltage minus)  
21  
option-210:  
status indication “BM” analog output  
(relay contact) 4-20 mA  
23 / 24 “Err1” group fault signalisation  
option-220:  
Kl. 21 (+)  
22  
Kl. 22 (-)  
(relay contact )  
31  
32  
load (+)  
load (-)  
DC 24 V / 1 A (or 2 A)  
33 / 34 load current measurement by voltmeter  
N = 1 A: shunt 0.2 Ω/1 %  
3
4
I
IN = 2 A: shunt 0.1 Ω/1 %  
shunt integral with device  
Kl. 33: shunt+ / Kl. 34: shunt-  
ꢁ1 ꢁꢀ  
41 4ꢀ  
ꢁꢁ  
4ꢁ  
ꢁ4  
44  
ꢂꢃꢄꢃꢂ ꢁ  
ꢂꢃꢄꢃꢂ 4  
41 / 42 “Err2” indication of fault circuit breaker  
(auxiliary contact)  
ꢇꢈꢉꢊꢆ ꢃꢄꢅꢆ ꢋꢉꢁꢌꢌꢁꢍꢎ  
43  
44  
+US (operating voltage plus)  
-US (operating voltage minus)  
DC 19.2...36 V  
Typical time/current characteristics (T = 25 °C)  
A
ꢃꢑꢐꢐꢆꢅꢇ ꢕꢁꢔꢁꢇꢖꢇꢁꢄꢅ  
ꢇꢈꢉꢊ ꢗ ꢌ ꢍꢎ  
ꢀꢁꢂꢃꢄꢅꢅꢆꢃꢇꢁꢄꢅ  
ꢇꢈꢉꢊ 1ꢊ1ꢋ ꢌ ꢍꢎ  
1ꢓꢓ  
1ꢓ  
1
ꢓꢊ1  
ꢂꢏꢄꢐꢇ ꢃꢁꢐꢃꢑꢁꢇ  
ꢀꢁꢂꢃꢄꢅꢅꢆꢃꢇꢁꢄꢅ  
ꢇꢈꢉꢊ ꢒꢓꢓ ꢔꢂ  
ꢓꢊꢓ1  
1ꢊꢋ ꢌ ꢍꢎ  
ꢍꢘ  
1
ꢔꢁꢅꢊ 1ꢊꢓꢋ ꢌ ꢍꢎ  
ꢔꢖꢌꢊ 1ꢊꢗꢋ ꢌ ꢍꢎ  
5
ꢙ ꢇꢁꢔꢆꢂ ꢐꢖꢇꢆꢀ ꢃꢑꢐꢐꢆꢅꢇ  
All dimensions without tolerances are for reference only. In the interest of improved design,  
performance and cost effectiveness the right to make changes in these specifications without  
notice is reserved. Product markings may not be exactly as the ordering codes. Errors and  
omissions excepted.  
4
www.e-t-a.de  
1646  

相关型号:

E-1072-220-DC24V-1A

Voltage rating DC 24 V (19.2...36 V)
ETAL

E-1073

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0100-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0100-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0102-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0102-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0233-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-0233-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-1100-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-1100-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-1102-437-B3-K12-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL

E-1073-1102-437-B3-K60-5

Battery and cable protection for all types of vehicle (including electric), battery powered systems.
ETAL