PMT-5V350W1NA [DELTA]
PMT Panel Mount Power Supply;型号: | PMT-5V350W1NA |
厂家: | DELTA ELECTRONICS, INC. |
描述: | PMT Panel Mount Power Supply |
文件: | 总12页 (文件大小:1269K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
PMT
Highlights & Features
–
–
AC input range selectable by switch
Full Aluminium casing for light weight and corrosion resistant
handling
–
–
Built-in automatic fan speed control circuit
Wide operating temperature range from -20°C to +70°C and
cold start at -40°C
–
–
MTBF > 700,000 hrs. as per Telcordia SR-332
Short Circuit / Overvoltage / Overload / Over Temperature
Protections
Safety Standards
CB Certified for worldwide use
Model Number:
PMT-5V350W1A☐☐
Unit Weight:
0.81 kg
Dimensions (L x W x D): 215 x 115 x 50 mm
General Description
The new PMT series of panel mount power supplies is the latest offering from one of the world’s largest power supply manufacturers
and solution providers - Delta. PMT-5V350W1A☐☐ offers a nominal output voltage of 5V with a wide operating temperature range
from -20°C to +70°C and can withstand shock and vibration (in accordance to IEC 60068-2-27 and IEC 60068-2-6 respectively). In
addition to features like overvoltage and overload protections, Delta’s PMT series of panel mount power supplies is unlike many other
brands in the same price level. The PMT series is designed for cost competitive markets without compromising the quality of the
components and product specifications. The series of products has an expected life time of 10 years and will have no output power de-
rating from 100Vac to 132Vac & 180Vac to 264Vac.
Model Information
PMT Panel Mount Power Supply
Model Number
Input Voltage Range
Output
Voltage
Output Current
PMT-5V350W1A☐☐
90-132Vac, 180-264Vac
(Selectable by Switch)
5Vdc
60.0A
Model Numbering
CC Code
PM
T –
5V
350W
1
A
□
□
Panel Mount Product Type Output Voltage Output Power Single Phase No PFC
Connector Type
Blank – Without
T – Enclosed
(350W series
model)
Series
M – Terminal Block connector cover
N – Front Face*
A – With connector
cover
*Options
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
1
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Input Current
100-120Vac, 200-240Vac (Selectable by Switch)
90-132Vac, 180-264Vac (Selectable by Switch)
50-60Hz
47-63Hz
< 7.00A @ 115Vac, < 4.00A @ 230Vac
> 76.0% @ 230Vac
Efficiency at 100% Load
Max Inrush Current
Leakage Current
< 40A @ 115Vac, < 60A @ 230Vac
< 3.5mA @ 240Vac
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
5Vdc
± 3% (initial set point tolerance from factory)
4.50-5.60Vdc
60.0A
Output Power
300W
Line Regulation
± 0.5% typ.
Load Regulation
± 2.5% typ.
PARD (20MHz)
< 150mVpp
Rise Time
< 50ms @ nominal input (100% load)
< 1000ms @ nominal input (100% load)
> 16ms @ 115Vac, > 20ms @ 230Vac
± 1000mVpp @ 10-50% load and 50-100% load
8,000µF Max
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
Mechanical
Case Chassis
Case Cover
Aluminium
Aluminium
Dimensions (L x W x D)
Unit Weight
215 x 115 x 50 mm
0.81 kg
Indicator
Green LED (DC OK)
Forced Cooling
Cooling System
Terminal
M3.5 x 9 Pins (Rated 300V/15A)
M3.5 x 9 Pins (Rated 300V/20A)
AWG 14-12
PMT-5V350W1AM☐
PMT-5V350W1AN☐
Wire
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
2
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Environment
Surrounding Air Temperature
Power De-rating
Operating -20°C to +70°C
Storage -40°C to +85°C
> 50°C de-rate power by 4% / °C,
> 60°C de-rate power by 1% / °C
< 100Vac de-rate power by 3% / V,
< 200Vac de-rate power by 1.5% / V
Operating Humidity
5 to 95% RH (Non-Condensing)
0 to 5,000 Meters
Operating Altitude
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine: 50G for a duration of 11ms,
3 times per direction, 18 times in total
Vibration
Operating IEC 60068-2-6, Sine Wave: 10Hz to 150Hz @ 25m/S²
(2.5G peak); 90 min per axis for all X, Y, Z direction
Non-Operating IEC 60068-2-6, Random: 5Hz to 500Hz @ 2.09Grms
peak; 20 min per axis for all X, Y, Z direction
Pollution Degree
Protections
2
Overvoltage
< 5.75~7.50V, SELV Output, Latch Mode
Overload / Overcurrent
> 105~135% of rated load current, Hicc-up Mode,
Non-Latching (Auto-Recovery)
Over Temperature
Short Circuit
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
Protection Against Shock
Class I with PE* connection
*PE: Primary Earth
Reliability Data
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
Expected Cap Life Time
Expected Cap Life Time
Safety Standards / Directives
Electrical Safety
UL/cUL recognized to UL 60950-1 and CSA C22.2
No. 60950-1, CB scheme to IEC 60950-1
Material and Parts
Galvanic Isolation
RoHS Directive 2011/65/EU Compliant
Input to Output 3.0KVac
Input to Ground 1.5KVac
Output to Ground 0.5KVac
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
3
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
EMC
EMC / Emissions*
CISPR22, EN55022, FCC Title 47: Class A
(With Delta EMI filter P/N: 10DKAW5)
Immunity to*
EN 55024
Electrostatic Discharge
IEC61000-4-2 Level 4 Criteria A1)
Air Discharge: 15kV
Contact Discharge: 8kV
Radiated Field
IEC61000-4-3 Level 3 Criteria A1)
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation
Electrical Fast Transient / Burst
Surge
IEC61000-4-4 Level 3 Criteria A1)
2kV
IEC61000-4-5 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Conducted
IEC61000-4-6 Level 3 Criteria A1)
150kHz-80MHz, 10Vrms
Power Frequency Magnetic Fields
Voltage Dips
IEC61000-4-8 Criteria A1)
10A/Meter
IEC61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable
Low Energy Pulse Test (Ring Wave)
IEC61000-4-12 Level 3 Criteria A1)
Common Mode2): 2kV
Differential Mode3): 1kV
Harmonic Current Emission
NA
Voltage Fluctuation and Flicker*
IEC/EN 61000-3-3
*Fulfills tested conditions
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
4
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Block Diagram
Device Description
PMT-5V350W1AM☐: Terminal Block
PMT-5V350W1AN☐: Front Face
1) Input & Output terminal block connector
2) DC voltage adjustment potentiometer
3) DC OK control LED (Green)
4) AC selectable switch
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
5
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Dimensions
L x W x D: 215 x 115 x 50 mm (PMT-5V350W1AM☐: Terminal Block)
L x W x D: 215 x 115 x 50 mm (PMT-5V350W1AN☐: Front Face)
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
6
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Engineering Data
De-rating
Note
1. Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2. If the output capacity is not reduced when the
surrounding air temperature >70°C, the
device will run into Over Temperature
Protection. When activated, the output
voltage will go into bouncing mode and will
recover
when
the
surrounding
air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3. To ensure sufficient convection cooling,
always maintain a distance of ≥ 20mm from
fan ventilated surfaces while the device is in
operation.
4. Depending
on
the
surrounding
air
temperature and output load delivered by the
power supply, the device housing can be
very hot!
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 4% / °C
5. If the device has to be mounted in any other
orientation, please do not hesitate to contact
info@deltapsu.com for more details.
> 60°C de-rate power by 1% / °C
Output De-rating VS. Input Voltage
No output power de-rating for the input
voltage from 100Vac to 132Vac & 200Vac to
264Vac
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
7
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Assembly & Installation
Ⓐ
Side Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 5mm length (Refer to Fig. 4 on the
next page). This is to maintain a safety distance between the screw and internal components.
Base Mounting: Fig. 2 and Fig. 3 show the mounting hole locations for power supply assembly onto a metal mounting surface. The
power supply shall be mounted on minimum of 4 mounting holes using M4 screw maximum 4mm length (Refer to Fig. 4 on the
next page).
Ⓑ
Ⓒ
Ⓓ
Connector
This surface belongs to customer’s end system or panel where the power supply is mounted.
Base Mounting (Horizontal)
Base Mounting (Vertical)
Side Mounting (Horizontal)
Fig. 2 Mounting Orientation
–
–
Use flexible cable (stranded or solid) of AWG No. 14-12. The input/output connectors’ allowable current is 23A max per pin. User
should calculate and select the suitable wire specification (type/quantity/diameter) according to actual output current. The torque at
the connector shall not exceed 13Kgf.cm. The insulation stripping length should not exceed 0.275” or 7mm.
Recommended mounting torque of the product and its mounting accessories is 9~12Kgf.cm.
Safety Distance
D1 = 4mm Min.
D2 = 20mm Min.
Fig. 3 Mounting Hole Locations and the Safety Distance
For safety reasons, please ensure the mounted device is kept at ≥ 4mm safety distance at all sides from other components and
equipments. In addition, to ensure sufficient convection cooling, always maintain a distance of ≥ 20mm from fan ventilated surfaces
while the device is in operation. Please insert an insulation sheet between the system and product, if the safety distance is < 4mm.
Only use M4 screw ≤ 5 mm through the base mounting holes at Ⓐ.
This is to keep a safe distance between the screw and internal
components.
Only use M4 screw ≤ 4 mm through the base mounting holes at Ⓑ.
Fig. 4 Assembly Reference
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
8
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Improper Installations
Safety Instructions
–
–
–
Must select correct AC input voltage before turning on (Refer to the “Device Description” on Page 5).
The device is not recommended to be placed on low thermal conductive surface. For example, plastics.
Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power supply.
Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!
Do not touch the terminals while power is being supplied. Risk of electric shock.
–
–
Prevent any foreign metal, particles or conductors from entering the device through the openings during installation.
It may cause: - Electric shock; Safety Hazard; Fire; Product failure.
–
Warning: When connecting the device, secure Earth connection before connecting L and N. When disconnecting the device,
remove L and N connections before removing the Earth connection. The power supply must be mounted by metal screws onto a
grounded metal surface. It is highly recommended that the Earth terminal on the connector be connected to the grounded metal
surface.
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
9
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Functions
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 95% of its set value, after the input voltage is removed.
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Inrush Current
Dynamic Response
Inrush current is the peak, instantaneous, input current
measured and, occurs when the input voltage is first applied.
For AC input voltages, the maximum peak value of inrush
current will occur during the first half cycle of the applied AC
voltage. This peak value decreases exponentially during
subsequent cycles of AC voltage.
The power supply output voltage will remain within
±1000mVpp of its steady state value, when subjected to a
dynamic load from 10 to 50% and 50 to 100% of its rated
current.
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
10
TECHNICAL DATASHEET
PMT Panel Mount Power Supply
5V 300W 1 Phase / PMT-5V350W1A□□
Overload & Overcurrent Protections
Overvoltage Protection
The power supply’s Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current exceeds
105~135% of rated load current. In such occurrence, the VO
will start to droop and once the power supply has reached its
maximum power limit, the protection is activated and the power
supply will go into “Hiccup mode” (Auto-Recovery). The power
supply will recover once the fault condition of the OLP and
OCP is removed and IO is back within the specifications.
The power supply’s overvoltage circuit will be activated when
its internal feedback circuit fails. The output voltage shall not
exceed its specifications defined on Page
“Protections”.
3
under
Over Temperature Protection
As mentioned above, the power supply also has Over
Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load, the power supply will run
into OTP when the operating temperature is beyond what is
recommended in the de-rating graph. When activated, the
output voltage will go into bouncing mode until the temperature
drops to its normal operating temperature as recommended in
the de-rating graph.
It is not recommended to prolong the duration of IO when it is
<105~135% but >100%, since it may cause damage to the
PSU.
Short Circuit Protection
The power supply’s output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied,
the output current will operate in “Hiccup mode”, as shown in
the illustration in the OLP/OCP section on this page. The
power supply will return to normal operation after the short
circuit is removed.
Others
Delta RoHS Compliant
Restriction of the usage of hazardous substances
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in
electrical and electronic equipment”.
This product conforms to this standard.
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (May 2014, Rev. 01)
11
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Delta:
PMT-5V350W1AMB
相关型号:
PMT103J2G
METALIZED POLYPROPYLENE FILM CAPACITORS PMT & PMF Series: Axial Leaded, Flat & Tubular
RFE
©2020 ICPDF网 联系我们和版权申明