PMT-24V50W1AG [DELTA]

PMT Panel Mount Power Supply;
PMT-24V50W1AG
型号: PMT-24V50W1AG
厂家: DELTA ELECTRONICS, INC.    DELTA ELECTRONICS, INC.
描述:

PMT Panel Mount Power Supply

文件: 总11页 (文件大小:539K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
PMT  
Highlights & Features  
Universal AC input range  
Allows input voltage from 90Vac to 264Vac without  
power de-rating  
Versatile connector options (Terminal Block, Front Face,  
Harness)  
MTBF > 200,000 hrs.  
Overvoltage / Overcurrent / Over Temperature Protections  
Reliable economical solution with high temperature  
range E-Cap  
Safety Standards  
CB Certified for worldwide use  
Model Number:  
Unit Weight:  
PMT-24V50W1AX  
0.24 kg  
Dimensions (L x W x D): 98 x 98 x 37.5 mm  
General Description  
The new PMT series of panel mount power supplies is the latest offering from one of the world’s largest power supply manufacturers  
and solution providers - Delta. The first range of PMT products will offer a nominal output voltage of 24V with a wide operating  
temperature range from -10°C to +70°C and can withstand shock and vibration requirements (in accordance to IEC60068-2-27 and  
IEC60068-2-6 respectively). In addition to features like overvoltage and overload protections, Delta’s PMT series of panel mount power  
supplies is unlike many other brands in the same price level. The PMT series is designed for cost competitive markets without  
compromising the quality of the components and product specifications. The series of products has an expected life time of 10 years  
and will have no output power de-rating from 90Vac to 264Vac. This versatile series has three different connector options (Terminal  
Block, Front Face and Harness) and can also be converted into L Frame (PML) or Open Frame (PMB) type of power supplies to satisfy  
different application needs.  
Model Information  
PMT Panel Mount Power Supply  
Model Number  
Input Voltage Range  
Output  
Voltage  
Output Current  
PMT-24V50W1AX  
85-264Vac  
24Vdc  
2.09A  
Model Numbering  
PM  
X –  
24V  
50W  
Output Power  
1
A
X
Panel Mount  
Product Type  
T – Enclosed  
L – L Frame*  
Output Voltage  
Single Phase  
No PFC Series  
Connector Type  
A – Terminal Block  
G – Front Face*  
H – Harness*  
B – Open Frame*  
*Options  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
1
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Specifications  
Input Ratings / Characteristics  
Nominal Input Voltage  
Input Voltage Range  
Nominal Input Frequency  
Input Frequency Range  
Input Current  
100-240Vac  
85-264Vac  
50-60Hz  
47-63Hz  
< 1.10A @ 115Vac, < 0.65A @ 230Vac  
> 86.0% @ 115Vac & 230Vac  
< 30A @ 115Vac, < 60A @ 230Vac  
Conform to EN61000-3-2  
< 1mA @ 240Vac  
Efficiency at 100% Load  
Max Inrush Current  
Power Factor  
Leakage Current  
Output Ratings / Characteristics  
Nominal Output Voltage  
Output Voltage Tolerance  
Output Voltage Adjustment Range  
Output Current  
24Vdc  
± 2% (initial set point tolerance from factory)  
22-28Vdc  
2.09A  
Output Power  
50W  
Line Regulation  
< 0.5% typ. (@ 85-264Vac input, 100% input)  
< 1% typ. (@ 85-264Vac input, 0-100% input)  
Load Regulation  
PARD (20MHz)  
< 100mVpp @ 0°C to 50°C,  
< 150mVpp @ -10°C to 0°C  
Rise Time  
< 30ms @ nominal input (100% load)  
< 2500ms @ nominal input (100% load)  
> 16.7ms @ 115Vac  
Start-up Time  
Hold-up Time  
Dynamic Response (Overshoot & Undershoot O/P Voltage)  
Start-up with Capacitive Loads  
± 5% @ 0-100% load (Slew Rate: 0.1A/µS)  
8,000µF Max  
Mechanical  
Case Chassis  
Case Cover  
Dimensions (L x W x D)  
Unit Weight  
Indicator  
Aluminium  
SGCC  
98 x 98 x 37.5 mm  
0.24 kg  
Green LED (DC OK)  
Convection  
Cooling System  
Terminal  
Refer to the Table on Page 7  
Refer to the Table on Page 7  
Wire  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
2
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Environment  
Surrounding Air Temperature  
Operating -10°C to +70°C  
Storage -25°C to +85°C  
> 50°C de-rate power by 2.5% / °C  
Power De-rating  
Operating Humidity  
Operating Altitude  
< 95% RH (Non-Condensing)  
5,000 Meters  
Shock Test (Non-Operating)  
IEC60068-2-27, 50G for a duration of 11ms,  
3 times per direction, 18 times in total  
Vibration (Non-Operating)  
Pollution Degree  
IEC60068-2-6, 10Hz to 55Hz @ 50m/S² (5G peak);  
90 min per axis for all X, Y, Z direction  
2
Protections  
Overvoltage  
< 32V, ±10%, SELV Output, Hicc-up Mode,  
Non-Latching (Auto-Recovery)  
Overload / Overcurrent  
Over Temperature  
Short Circuit  
> 120% of rated load current, Hicc-up Mode,  
Non-Latching (Auto-Recovery)  
Non-Latching (Auto-Recovery)  
Hicc-up Mode, Non-Latching  
(Auto-Recovery when the fault is removed)  
Class I with PE* connection  
Protection Against Shock  
*PE: Primary Earth  
Reliability Data  
MTBF  
> 200,000 hrs.  
Expected Cap Life Time  
10 years (115Vac & 230Vac, 50% load @ 40°C)  
Safety Standards / Directives  
Electrical Safety  
TUV Bauart to EN60950-1, UL/cUL recognized to  
UL60950-1 and CSA C22.2 No. 60950-1, CB scheme to  
IEC60950-1, CCC to GB4943  
ITE  
CE  
IEC/EN/UL 60950-1  
In conformance with EMC Directive 2004/108/EC and  
Low Voltage Directive 2006/95/EC  
Material and Parts  
Galvanic Isolation  
RoHS Directive 2011/65/EU Compliant  
Input to Output 3.0KVac  
Input to Ground 1.5KVac  
Output to Ground 0.5KVac  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
3
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
EMC  
EMC / Emissions  
Immunity to  
CISPR22, EN55022, FCC Title 47: Class B  
Electrostatic Discharge  
IEC61000-4-2 Level 4 Criteria A1)  
Air Discharge: 15kV  
Contact Discharge: 8kV  
Radiated Field  
IEC61000-4-3 Level 3 Criteria A1)  
80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation  
Electrical Fast Transient / Burst  
Surge  
IEC61000-4-4 Level 3 Criteria A1)  
2kV  
IEC61000-4-5 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
Conducted  
IEC61000-4-6 Level 3 Criteria A1)  
150kHz-80MHz, 10Vrms  
Power Frequency Magnetic Fields  
Voltage Dips  
IEC61000-4-8 Criteria A1)  
10A/Meter  
IEC61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable  
Low Energy Pulse Test (Ring Wave)  
IEC61000-4-12 Level 3 Criteria A1)  
Common Mode2): 2kV  
Differential Mode3): 1kV  
1) Criteria A: Normal performance within the specification limits  
2) Asymmetrical: Common mode (Line to earth)  
3) Symmetrical: Differential mode (Line to line)  
Block Diagram  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
4
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Dimensions  
L x W x D: 98 x 98 x 37.5 mm  
Engineering Data  
De-rating  
Note  
1. Power supply components may degrade, or  
be damaged, when the power supply is  
continuously used outside the shaded region,  
refer to the graph shown in Fig. 1.  
2. If the output capacity is not reduced when the  
surrounding air temperature >50°C, the  
device will run into Over Temperature  
Protection. When activated, the output  
voltage will go into bouncing mode and will  
recover  
when  
the  
surrounding  
air  
temperature is lowered or the load is reduced  
as far as necessary to keep the device in  
working condition.  
3. In order for the device to function in the  
manner intended, it is also necessary to keep  
a safety distance of 20mm with adjacent units  
while the device is in operation.  
4. Depending  
on  
the  
surrounding  
air  
temperature and output load delivered by the  
power supply, the device can be very hot!  
5. If the device has to be mounted in any other  
orientation, please do not hesitate to contact  
info@deltapsu.com for more details.  
Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation  
> 50°C de-rate power by 2.5% / °C  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
5
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Output De-rating VS. Input Voltage  
No output power de-rating for the input  
voltage from 90Vac to 264Vac  
Assembly & Installation  
Mounting holes for power supply assembly onto the mounting surface.  
The power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5 mm length.  
This surface belongs to customer’s end system or panel where the power supply is mounted.  
Connector  
Fig. 2.3 Side Mounting (Horizontal)  
Fig. 2.1 Side Mounting (Vertical)  
Fig. 2.2 Base Mounting (Vertical)  
Improper Installations  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
6
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Only use M3 screw ≤ X mm through the base mounting holes (Refer to  
the Screw Protrusion Length in the table below). This is to keep a safe  
distance between the screw and internal components.  
Connection & Screw Protrusion Data  
Product Group  
PMT  
Item  
Connector Options  
A – Terminal Block  
G – Front Face*  
H – Harness*  
22-18  
AWG  
22-12  
22-12  
Torque  
13Kgf.cm  
13Kgf.cm  
Input Connector  
Output Connector  
Input Mating Connector  
Output Mating  
Input & Output Terminal  
B3P5-VH(LF)(SN)  
B2P3-VH(LF)(SN)  
VHR-5N  
VHR-3N  
SVH-21T-P1.1  
5mm (6mm Max)  
22-18  
Screw Protrusion Length 5mm (6mm Max)  
5mm (6mm Max)  
PML*  
AWG  
22-12  
22-12  
Torque  
13Kgf.cm  
13Kgf.cm  
Input Connector  
Output Connector  
Input Mating Connector  
Output Mating  
Input & Output Terminal  
B3P5-VH(LF)(SN)  
B2P3-VH(LF)(SN)  
VHR-5N  
VHR-3N  
SVH-21T-P1.1  
5mm (6mm Max)  
22-18  
Screw Protrusion Length 5mm (6mm Max)  
5mm (6mm Max)  
PMB*  
AWG  
22-12  
22-12  
Torque  
13Kgf.cm  
13Kgf.cm  
Input Connector  
Output Connector  
Input Mating Connector  
Output Mating  
Input & Output Terminal  
B3P5-VH(LF)(SN)  
B2P3-VH(LF)(SN)  
VHR-5N  
VHR-3N  
SVH-21T-P1.1  
5mm  
Screw Protrusion Length 5mm  
5mm  
*Options  
To ensure sufficient convection cooling, always maintain a safety distance of 20mm from all ventilated surfaces while the device is  
in operation.  
The device is not recommended to be placed on low thermal conductive surfaces, for example, plastics.  
Prevent any foreign metal, particles or conductors to enter the device through the openings during installation. It can cause: -  
Electric shock; Safety Hazard; Fire; Product failure.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
7
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Functions  
Start-up Time  
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.  
Rise Time  
The time required for the output voltage to change from 10% to 90% of its set value.  
Hold-up Time  
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time  
required for the output to reach 95% of its set value, after the input voltage is removed.  
Graph illustrating the Start-up Time, Rise Time, and Hold-up Time  
Inrush Current  
Dynamic Response  
Inrush current is the peak, instantaneous, input current measured  
and, occurs when the input voltage is first applied. For AC input  
voltages, the maximum peak value of inrush current will occur  
during the first half cycle of the applied AC voltage. This peak  
value decreases exponentially during subsequent cycles of AC  
voltage.  
The power supply output voltage will remains within ±5% of its  
steady state value, when subjected to a dynamic load from 0 to  
100% of its rated current.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
8
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Overload & Overcurrent Protections  
Overvoltage Protection  
The power supply’s Overload (OLP) and Overcurrent (OCP)  
Protections will be activated when output current exceeds 120%  
of IO (Max load). In such occurrence, the VO will start to droop and  
once the power supply has reached its maximum power limit, the  
protection is activated and the power supply will go into “Hiccup  
mode” (Auto-Recovery). The power supply will recover once the  
fault condition of the OLP and OCP is removed and IO is back  
within the specifications.  
The power supply’s overvoltage circuit will be activated when its  
internal feedback circuit fails. The output voltage shall not exceed  
its specifications defined on Page 3 under “Protections”.  
Over Temperature Protection  
As mentioned above, the power supply also has Over  
Temperature Protection (OTP). This is activated when the  
overload condition persists for an extended duration and the  
output current is below the overload trigger point but >100% load.  
In the event of a higher operating condition at 100% load, the  
power supply will run into OTP when the surrounding air  
temperature is >50°C. When activated, the output voltage will go  
into bouncing mode until the operating surrounding air  
temperature drops to 50°C or output capacity is reduced as  
recommended in the de-rating graph.  
Additionally, if the IO is <120% but >100% for a prolong period of  
time (depending on the load), the Over Temperature Protection  
(OTP) will be activated due to high temperature on critical  
components. The power supply will then go into “Hiccup mode”  
until the fault is removed.  
Short Circuit Protection  
The power supply’s output OLP/OCP function also provides protection against short circuits. When a short circuit is applied, the output  
current will operate in “Hiccup mode”, as shown in the illustration in the OLP/OCP section on this page. The power supply will return to  
normal operation after the short circuit is removed.  
Operating Mode  
Redundancy Operation  
In order to ensure proper redundancy operation  
for the power supply unit (PSU), ensure that the  
output voltage difference between the two units  
is kept at 0.45~0.50V for 24V supplies. Follow  
simple steps given below to verify:  
Step 1.  
Measure output voltage of PSU 1 and PSU 2. If  
PSU 1 is the master unit, then VO of PSU 1  
must be higher than PSU 2.  
In order to set the output voltage, connect the  
power supply to 50% load and set the PSU 1  
and PSU 2 output voltage.  
Step 2.  
Connect the right DRR module, 20A as per the  
system requirement to the power supply units  
PSU 1 and PSU 2 at Vin 1 & Vin 2 respectively.  
Fig. 3  
Redundancy / Parallel Operation Connection Diagram  
Step 3.  
Connect the system load from Vout. Please note  
that output voltage Vout from DRR module will be  
= VO (output voltage of power supply) – Vdrop* (in  
DRR module).  
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and  
surrounding air temperature.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
9
TECHNICAL DATASHEET  
PMT Panel Mount Power Supply  
24V 50W 1 Phase / PMT-24V50W1AX  
Parallel Operation  
These DRR modules can also be used for Parallel function in order to increase the output power by N+1 (e.g. 2.5A + 2.5A = 5A or 2.5A  
+ 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the DRP024V060W1AZ  
is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as  
below (Refer to Fig. 3 for the Connection Diagram).  
Step 3.  
Step 1.  
Connect PSU 1 and PSU 2 with the DRR-20A module and  
Set output load condition for both supplies at 50% and measure  
measure at Vin 1 & Vin 2 to verify the voltage difference. Ensure  
the voltages are within ±25mV.  
the output voltages.  
Step 2.  
Step 4.  
Adjust output voltages to the same level or within ±25mV  
difference.  
Output voltage from DRR module Vout will be = VO (output  
voltage of power supply) – Vdrop* (in DRR module).  
*Vdrop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.  
Others  
Delta RoHS Compliant  
Restriction of the usage of hazardous substances  
The European directive 2011/65/EU limits the maximum impurity level of homogeneous materials such as lead,  
mercury, cadmium, chrome, polybrominated flame retardants PBB and PBDE for the use in electrical and  
electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substances in  
electrical and electronic equipment”.  
This product conforms to this standard.  
All parameters are specified at 25°C ambient unless otherwise noted.  
www.DeltaPSU.com (February 2013, Rev. 01)  
10  
Mouser Electronics  
Authorized Distributor  
Click to View Pricing, Inventory, Delivery & Lifecycle Information:  
Delta:  
PMT-24V50W1AA  

相关型号:

PMT-24V50W1AH

PMT Panel Mount Power Supply
DELTA

PMT-24V50W1AX

PMT Panel Mount Power Supply
DELTA

PMT-5V350W1AM

PMT Panel Mount Power Supply
DELTA

PMT-5V350W1AMA

PMT Panel Mount Power Supply
DELTA

PMT-5V350W1NA

PMT Panel Mount Power Supply
DELTA

PMT-D1V100W1AAA

PMT Panel Mount Power Supply
DELTA

PMT-D1V100W1AGA

PMT Panel Mount Power Supply
DELTA

PMT-D1V100W1AHA

PMT Panel Mount Power Supply
DELTA

PMT103J2G

METALIZED POLYPROPYLENE FILM CAPACITORS PMT & PMF Series: Axial Leaded, Flat & Tubular
RFE

PMT200EN

100 V N-channel Trench MOSFET
NXP

PMT200EPE

70 V, P-channel Trench MOSFETProduction
NEXPERIA

PMT21EN

7400mA, 30V, N-CHANNEL, Si, SMALL SIGNAL, MOSFET, PLASTIC, SC-73, 4 PIN
NXP