EM-1RI [SYSTEMSENSOR]

Relay Module; 继电器模块
EM-1RI
型号: EM-1RI
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Relay Module
继电器模块

继电器
文件: 总2页 (文件大小:228K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
INSTALLATION AND MAINTENANCE INSTRUCTIONS  
3825 Ohio Avenue, St. Charles, Illinois 60174  
1.800.SENSOR2; Fax: 630.377.6495  
www.systemsensor.com  
EM-1RI Relay Module  
SPECIFICATIONS  
Normal Operating Voltage:  
Standby Current:  
Alarm Current:  
15 to 30 VDC  
580 µA max. average (continuous broadcasts)  
2.0 mA (red LED on)  
Short Circuit Current, Dry Control Input:  
Maximum Resistance, Dry Contact Input:  
Temperature Range:  
Humidity:  
30 µA max. average (5VDC)  
100 Ω  
32°F to 120°F (0°C to 49°C)  
10% to 93% RH Non-condensing  
4.17˝ H × 4.26˝ W × 1.22˝ D; (106 mm H × 108 mm W × 31 mm D)  
Dimensions:  
Accessories:  
Wall cover plate (included); SMB500 Surface Mount Electrical Box; CB500 Control Module Barrier  
CURRENT RATING  
MAXIMUM VOLTAGE  
30 VDC  
LOAD DESCRIPTION  
Resistive  
APPLICATION  
Non-Coded  
Coded  
3 A  
2 A  
30 VDC  
Resistive  
.9 A  
.9 A  
.5 A  
1 A  
.3 A  
1.5 A  
.7 A  
2 A  
110 VDC  
125 VDC  
30 VDC  
30 VDC  
125 VAC  
25 VAC  
Resistive  
Resistive  
Non-Coded  
Non-Coded  
Coded  
Inductive (L/R=5ms)  
Inductive (L/R=2ms)  
Inductive (PF=.35)  
Inductive (PF = .35)  
Inductive (PF=.35)  
Inductive (PF=.35)  
Coded  
Non-Coded  
Non-Coded  
Non-Coded  
Non-Coded  
70.7 VAC  
25 VAC  
NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.  
BEFORE INSTALLING  
WIRING  
This information is included as a quick reference installation guide. Refer to the  
appropriate control panel installation manual for detailed system information.  
If the modules will be installed in an existing operational system, inform the  
operator and local authority that the system will be temporarily out of service.  
NOTE: All wiring must conform to applicable local codes, ordinances,  
and regulations.  
1. Install module wiring in accordance with the job drawings and appropri-  
ate wiring diagrams.  
NOTICE: This manual should be left with the owner/user of this equipment.  
NOTE: Separate cable entry openings must be used to maintain required  
spacing between power limited and non-power limited wiring. Optional  
EA-CB may be required to separate power limited and non power limited  
wiring in the electrical box.  
GENERAL DESCRIPTION  
Relay Module, Model EM-1RI, is to be designed for use in activation of the  
types of products that are generally connected to an intelligent fire alarm sys-  
tem. It provides two sets of form C contacts that switch together (one DPDT  
relay). There is also an input that is capable of monitoring a dry set of contacts  
for open or closed conditions. The module also has on-board short circuit iso-  
lators to prevent shorts on the signaling line circuit from disabling more than  
one device on the intelligent loop.  
2. Set the address on the module per job drawings using the IR configura-  
tion tool (model no. EA-CT).  
3. Secure module to electrical box (supplied by installer).  
AUTO ADDRESSING  
Eclipse Series devices are capable of supporting auto addressing, if the fire  
alarm control panel is designed to do so. In auto addressing, the control panel,  
through the use of each device’s on-board isolators, can automatically assign  
device addresses.  
COMPATIBILITY REQUIREMENTS  
To ensure proper operation, this module shall be connected to a listed compat-  
ible control panel.  
MOUNTING  
In order to control which devices are addressed first in wiring configurations  
with branches, a branch marker can be set at a particular device. A branch  
marker is an electronic value from 0 to 255 stored in the device memory. The  
branch markers are set with the IR configuration tool, EA-CT.  
The module mounts directly to 4-inch square electrical boxes. The box must  
have a minimum depth of 21⁄  
inches. Modules must be mounted with the ar-  
row facing upward for proper operation of the IR programming tool. Surface  
mounted electrical boxes (SMB500) are available from System Sensor.  
8
TERMINAL DEFINITIONS  
LED INDICATOR  
T1 (+) SLC in/out  
T7 Normally Closed #1  
T8 Common #1  
T2 (–) SLC in/out  
T3 (+) SLC in/out  
T9 Normally Open #1  
T10 Normally Closed #2  
T11 Common #2  
T4 (–) SLC in/out  
T5 (+) Dry Contact Input  
T6 (–) Dry Contact Input  
T12 Normally Open #2  
WARNING  
All relay switch contacts are shipped in the standby state (open) state, but may  
have transferred to the activated (closed) state during shipping. To ensure that  
the switch contacts are in their correct state, modules must be made to com-  
municate with the panel before connecting circuits controlled by the module.  
IR RECEIVER  
C0166-00  
D500-61-00  
1
I56-2023-005  
FIGURE 2: WIRING DIAGRAM:  
SIGNAL LINE CIRCUIT (SLC)  
30 VDC MAX.  
TWISTED PAIR RECOMMENDED AND IS POWER  
LIMITED AND SUPERVISED  
CONNECT MODULES  
TO LISTED COMPATIBLE  
CONTROL PANELS ONLY  
( + )  
( – )  
( + )  
( – )  
( + )  
12  
11  
10  
9
1
2
3
4
FROM PANEL OR  
( – )  
PREVIOUS PANEL  
( + )  
RELAY  
CONTACTS  
TO NEXT DEVICE  
( – )  
8
7
5
6
{
MODULE DOES NOT SUPER-  
VISE CONTROLLED CIRCUITS.  
TERMINALS 1-6 ARE POWER  
LIMITED. TERMINALS 7-12 ARE  
NON-POWER LIMITED.  
NORMALLY OPEN (T12)  
COMMON (T11)  
RELAY  
CONTACT #2  
NORMALLY CLOSED (T10)  
NOTE: NORMALLY OPEN OR  
NORMALLY CLOSED CONTACT  
DEVICE (NOT SUPERVISED).  
NOTE: NORMALLY CLOSED  
OPTION MAY NOT BE USED  
FOR FIRE APPLICATIONS.  
NORMALLY OPEN (T9)  
COMMON (T8)  
RELAY  
CONTACT #1  
NORMALLY CLOSED (T7)  
C0110-02  
ThREE-YEAR LIMITED WARRANTY  
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing  
the malfunction and suspected cause of failure. The Company shall not be obligated to  
repair or replace units which are found to be defective because of damage, unreasonable  
use, modifications, or alterations occurring after the date of manufacture. In no case shall  
the Company be liable for any consequential or incidental damages for breach of this  
or any other Warranty, expressed or implied whatsoever, even if the loss or damage is  
caused by the Company’s negligence or fault. Some states do not allow the exclusion or  
limitation of incidental or consequential damages, so the above limitation or exclusion  
may not apply to you. This Warranty gives you specific legal rights, and you may also  
have other rights which vary from state to state.  
System Sensor warrants its enclosed module to be free from defects in materials and  
workmanship under normal use and service for a period of three years from date of  
manufacture. System Sensor makes no other express warranty for this module. No agent,  
representative, dealer, or employee of the Company has the authority to increase or  
alter the obligations or limitations of this Warranty. The Company’s obligation of this  
Warranty shall be limited to the repair or replacement of any part of the module which  
is found to be defective in materials or workmanship under normal use and service  
during the three year period commencing with the date of manufacture. After phoning  
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization  
number, send defective units postage prepaid to: System Sensor, Returns Department, RA  
FCC STATEMENT  
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must  
accept any interference received, including interference that may cause undesired operation.  
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide  
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used  
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-  
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try  
to correct the interference by one or more of the following measures:  
– Reorient or relocate the receiving antenna.  
– Increase the separation between the equipment and receiver.  
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.  
– Consult the dealer or an experienced radio/TV technician for help.  
D500-61-00  
2
I56-2023-005  
©2007 System Sensor  

相关型号:

EM-1SRI

Supervised Control Module
SYSTEMSENSOR

EM-23046-C36

MICROPHONE
KNOWLES

EM-23046-P16

MICROPHONE
KNOWLES

EM-23069-000

MICROPHONE
KNOWLES

EM-24047-000

MICROPHONE
KNOWLES

EM-4530

EM4530 & EM4530P-C Omnidirectional Electret Condenser Microphone
SOBERTON

EM-4530-C

EM4530 & EM4530P-C Omnidirectional Electret Condenser Microphone
SOBERTON

EM-5

Euro Base Modular 5m Coax
ETC

EM-6027

Omnidirectional Electret Condenser Microphone
SOBERTON

EM-6027P

EM6027, EM6027S-BC, & EM6027P Omnidirectional Electret Condenser Microphone
SOBERTON

EM-6027P_18

EM ELECTRET CONDENSER MICROPHONE
SOBERTON

EM-6781

EM-6781 is ultra-small Hall effect ICs of a single silicon chip composed of Hall element and a signal processing IC
AKM