EM-1SRI [SYSTEMSENSOR]

Supervised Control Module; 监督控制模块
EM-1SRI
型号: EM-1SRI
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Supervised Control Module
监督控制模块

文件: 总4页 (文件大小:291K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
INSTALLATION AND MAINTENANCE INSTRUCTIONS  
3825ꢀOhioꢀAvenue,ꢀSt.ꢀCharles,ꢀIllinoisꢀ60174  
1-800-SENSOR2,ꢀFAX:ꢀ630-377-6495  
www.systemsensor.com  
EM-1SRI Supervised Control Module  
SPECIFICATIONS  
NormalꢀOperatingꢀVoltage:ꢀ  
15ꢀtoꢀ30ꢀVDC  
StandbyꢀCurrent:ꢀ  
630ꢀµAꢀmax.ꢀaverageꢀ(continuousꢀbroadcasts)  
AlarmꢀCurrent:ꢀ  
MaximumꢀNACꢀCircuitꢀLineꢀLoss:ꢀ  
2ꢀmAꢀ(redꢀLEDꢀon)  
4ꢀVDC  
Power Supply Monitor  
Maximumꢀ(Speakers):ꢀ  
Maximumꢀ(NAC):ꢀ  
TroubleꢀRange:ꢀ  
70.7ꢀVꢀRMS.ꢀ50ꢀW  
Regulatedꢀ24VDCꢀ  
0ꢀtoꢀ2ꢀVDC  
MaxꢀNACꢀCurrentꢀRating:ꢀ  
TemperatureꢀRange:ꢀ  
Humidity:ꢀ  
Dimensions:ꢀ  
Accessories:ꢀ  
ForꢀClassꢀBꢀwiringꢀsystem,ꢀ3A  
ForꢀClassꢀAꢀwiringꢀsystem,ꢀ2A  
32°Fꢀtoꢀ120°Fꢀ(0°Cꢀtoꢀ49°C)  
10ꢀtoꢀ93%ꢀRHꢀNoncondensing  
4.17˝ꢀHꢀxꢀ4.26˝ꢀWꢀxꢀ1.22˝ꢀD;ꢀ(106ꢀmmꢀHꢀxꢀ108ꢀmmꢀWꢀxꢀ31ꢀmmꢀD)  
39ꢀkΩꢀEndꢀofꢀLineꢀResistorꢀPartꢀ#ꢀA2263-00ꢀ(included)  
Wallꢀcoverꢀplateꢀ(included)  
SMB500ꢀSurfaceꢀMountꢀElectricalꢀBox  
A2143-60ꢀBypassꢀcapacitorꢀ  
EA-CBꢀControlꢀModuleꢀBarrier  
BEFORE INSTALLING  
noꢀshortꢀexists,ꢀtheꢀdeviceꢀwillꢀreapplyꢀtheꢀexternalꢀpower.ꢀ  
ThisalgorithmcanbeenabledwhenusingaDCexternalꢀ  
supplyꢀthatꢀisꢀguaranteedꢀtoꢀbeꢀaboveꢀ9ꢀvolts.  
Thisꢀinformationꢀisꢀincludedꢀasꢀaꢀquickꢀreferenceꢀinstalla-  
tionꢀguide.ꢀReferꢀtoꢀtheꢀappropriateꢀcontrolꢀpanelꢀinstalla-  
tionꢀmanualꢀforꢀdetailedꢀsystemꢀinformation.ꢀIfꢀtheꢀmodulesꢀ  
willꢀbeꢀinstalledꢀinꢀanꢀexistingꢀoperationalꢀsystem,ꢀinformꢀ  
theꢀ operatorꢀ andꢀ localꢀ authorityꢀ thatꢀ theꢀ systemꢀ willꢀ beꢀ  
temporarilyꢀoutꢀofꢀservice.  
COMPATIBILITY REQUIREMENTS  
Toꢀensureꢀproperꢀoperation,ꢀthisꢀmoduleꢀshallꢀbeꢀconnectedꢀ  
toꢀaꢀlistedꢀcompatibleꢀcontrolꢀpanel.  
MOUNTING  
NOTICE:ꢀThisꢀmanualꢀshouldꢀbeꢀleftꢀwithꢀtheꢀowner/userꢀ  
Theꢀmoduleꢀmountsꢀdirectlyꢀtoꢀ4˝ꢀsquareꢀelectricalꢀboxes.ꢀ  
Theꢀ boxꢀ mustꢀ haveꢀ aꢀ minimumꢀ depthꢀ ofꢀ 21/8˝.ꢀ Modulesꢀ  
mustꢀbeꢀmountedꢀwithꢀtheꢀarrowꢀfacingꢀupwardꢀforꢀproperꢀ  
operationofꢀtheꢀIRꢀconfigurationꢀtoolꢀ(modelꢀno.ꢀEA-CT).ꢀ  
Surfaceꢀ mountedꢀ electricalꢀ boxesꢀ (SMB500)ꢀ areꢀ availableꢀ  
fromꢀSystemꢀSensor.  
ofꢀthisꢀequipment.  
GENERAL DESCRIPTION  
ControlꢀModule,ꢀModelꢀEM-1SRI,ꢀisꢀusedꢀtoꢀswitchꢀanꢀex-  
ternalpowersupplyoraudioamplifiertonotificationap-  
pliances.Inadditiontoswitchingtheexternalpower,theꢀ  
deviceꢀ willꢀ monitorꢀ theꢀ wiringꢀ (whileꢀ externalꢀ powerꢀ isꢀ  
notꢀswitchedꢀtoꢀtheꢀauxiliaryꢀdevices)ꢀtoꢀtheꢀauxiliaryꢀde-  
viceꢀforꢀopenꢀandꢀshortꢀcircuitsꢀviaꢀanꢀendꢀofꢀlineꢀresistor.ꢀ  
Thisꢀ moduleꢀ isꢀ capableꢀ ofꢀ Classꢀ Aꢀ orꢀ Classꢀ Bꢀ operation.ꢀ  
Theꢀmoduleꢀalsoꢀhasꢀon-boardꢀshortꢀcircuitꢀisolatorsꢀtoꢀpre-  
ventꢀshortsꢀonꢀtheꢀsignalingꢀlineꢀcircuitꢀfromꢀdisablingꢀmoreꢀ  
thanꢀoneꢀdeviceꢀonꢀtheꢀintelligentꢀloop.  
WIRING  
NOTE:ꢀAllꢀwiringꢀmustꢀconformꢀtoꢀapplicableꢀlocalꢀcodes,ꢀ  
ordinances,ꢀandꢀregulations.  
1.ꢀ Installꢀmoduleꢀwiringꢀinꢀaccordanceꢀwithꢀtheꢀjobꢀdraw-  
ingsꢀ andꢀ appropriateꢀ wiringꢀ diagrams.ꢀ Optionalꢀ EA-CBꢀ  
mayꢀ beꢀ requiredꢀ toꢀ separateꢀ powerꢀ limitedꢀ andꢀ nonꢀ  
powerꢀ limitedꢀ wiringꢀ inꢀ theꢀ electricalꢀ boxꢀ (seeꢀ Figureꢀ  
Theꢀcontrolꢀmoduleꢀwillꢀalsoꢀhaveꢀtheꢀcapabilityꢀtoꢀmoni-  
torꢀ theꢀ externalꢀ powerꢀ inputꢀ forꢀ lossꢀ ofꢀ powerꢀ (DCꢀ volt-  
ageꢀ suppliesꢀ only).ꢀ Thisꢀ featureꢀ canꢀ beꢀ disabledꢀ throughꢀ  
deviceꢀ configurationꢀ programming.ꢀ Ifꢀ theꢀ externalꢀ powerꢀ  
isswitchedtotheauxiliarydevicesandthereisalossofꢀ  
theꢀ DCꢀ supply,ꢀ theꢀ controlꢀ moduleꢀ hasꢀ theꢀ capabilityꢀ ofꢀ  
runningꢀanꢀalgorithmꢀinꢀwhichꢀtheꢀdeviceꢀwillꢀswitchꢀbackꢀ  
tomonitormodeandcheckthelineforshortcircuits.Ifꢀ  
1B).ꢀ2.ꢀ  
Fornewinstallationsusetheenclosed39ꢀ  
kΩꢀEOLꢀresistor.ꢀForꢀretrofitꢀapplicationsꢀwhereꢀtheꢀex-  
istingꢀ47ꢀkΩꢀcannotꢀbeꢀeasilyꢀreplaced,ꢀitꢀmayꢀbeꢀleftꢀinꢀ  
placeꢀwithoutꢀlossꢀofꢀperformance.  
3.ꢀ Settheaddressonthemoduleperjobdrawingsusingꢀ  
theꢀIRꢀconfigurationꢀtoolꢀ(modelꢀno.ꢀEA-CT).  
4.ꢀ Secureꢀmoduleꢀtoꢀelectricalꢀboxꢀ(suppliedꢀbyꢀinstaller).  
D500-54-00ꢀ  
1ꢀ  
I56-2016-004  
Auto Addressing  
TESTING  
EclipseSeriesdevicesarecapableofsupportingautoad- Theꢀ followingꢀ resistanceꢀ valuesꢀ canꢀ beꢀ usedꢀ toꢀ testꢀ theꢀ  
dressing,iftherealarmcontrolpanelisdesignedtodoꢀ moduleꢀafterꢀinstallation:  
so.ꢀInꢀautoꢀaddressing,ꢀtheꢀcontrolꢀpanel,ꢀthroughꢀtheꢀuseꢀ  
ofeachdevice’son-boardisolators,canautomaticallyas-  
signꢀ deviceꢀ addresses.ꢀ Inꢀ orderꢀ toꢀ controlꢀ whichꢀ devicesꢀ  
areꢀaddressedꢀfirstꢀinꢀwiringꢀconfigurationsꢀwithꢀbranches,ꢀ  
aꢀbranchꢀmarkerꢀcanꢀbeꢀsetꢀatꢀaꢀparticularꢀdevice.ꢀAꢀbranchꢀ  
markerisanelectronicvaluefrom0to255storedintheꢀ  
deviceꢀ memory.ꢀ Theꢀ branchꢀ markersꢀ areꢀ setꢀ withꢀ theꢀ IRꢀ  
configurationꢀtool,ꢀEA-CT.ꢀ  
ꢀꢀShortꢀCircuit:ꢀ <50Ω  
ꢀꢀOpenꢀCircuit:ꢀ >1MΩ  
ꢀꢀGroundꢀFault:ꢀ <50Ω  
WARNING  
Allrelayswitchcontactsareshippedinthestandbystateꢀ  
(open)ꢀ state,ꢀ butꢀ mayꢀ haveꢀ transferredꢀ toꢀ theꢀ activatedꢀ  
(closed)stateduringshipping.Toensurethattheswitchꢀ  
contactsꢀareꢀinꢀtheirꢀcorrectꢀstate,ꢀmodulesꢀmustꢀbeꢀmadeꢀ  
toꢀcommunicateꢀwithꢀtheꢀpanelꢀbeforeꢀconnectingꢀcircuitsꢀ  
controlledꢀbyꢀtheꢀmodule.  
Terminal Definitions  
T1ꢀꢀ  
T2ꢀꢀ  
T3ꢀꢀ  
T4ꢀꢀ  
T7ꢀꢀ  
T8ꢀꢀ  
(+)ꢀSLCꢀin/out  
(–)ꢀSLCꢀin/out  
(+)ꢀSLCꢀin/out  
(–)ꢀSLCꢀin/out  
(–)ꢀexternalꢀpowerꢀlineꢀin/out  
(+)ꢀexternalꢀpowerꢀlineꢀin/out  
T9ꢀꢀ  
T10ꢀ  
T11ꢀ  
T12ꢀ  
T13ꢀ  
T14ꢀ  
(–)ꢀexternalꢀpowerꢀlineꢀin/out  
(+)ꢀexternalꢀpowerꢀlineꢀin/out  
NACꢀ(+)ꢀA/B  
NACꢀ(–)ꢀA/B  
NACꢀ(–)ꢀClassꢀA  
NACꢀ(+)ꢀClassꢀA  
Figure 1A: Supervised Control Module  
LED  
INDICATOR  
IR  
RECEIVER  
Figure 1B: Module mounting with barrier (model no. EA-CB)  
C0164-00  
C0183-00  
D500-54-00ꢀ  
2ꢀ  
I56-2016-004  
Figure 2: Typical Class B, Style Y NAC configuration.  
SIGNAL LINE CIRCUIT (SLC)  
30 VDC MAX.  
TWISTED PAIR RECOMMENDED  
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED  
FROM PANEL OR  
PREVIOUS DEVICE  
(+)  
+
14  
13  
12  
11  
10  
9
1
2
3
4
MODULE POLARITIES ARE  
SHOWN IN ALARM  
+
(–)  
(+)  
(–)  
(–)  
(–)  
(+)  
(–)  
TO NEXT  
DEVICE  
EOL  
RESISTOR  
24 VDC  
POWER  
SUPPLY  
(+)  
(–)  
8
(+)  
(+)  
7
24 VDC POWER SUPPLY  
UL LISTED  
ISOLATED, REGULATED,  
POWER LIMITED PER NFPA 70  
LISTED FOR FIRE PROTECTION  
WITH BATTERY BACK-UP  
EOL RELAY  
SHOWN  
ENERGIZED  
24 VDC COIL  
A77-716B  
TO NEXT CONTROL MODULE  
TERMINALS 10 (+) AND 9 (–)  
OR END OF LINE RELAY  
(IF REQUIRED)  
OR EQUIVALENT  
FROM TERMINALS  
7 AND 8 OF LAST  
CONTROL MODULE  
ON BRANCH  
C0106-04  
REQUIRED FOR PANELS  
WITHOUT POWER SUPPLY  
MONITORING  
Figure 3: Typical Class A, Style Z NAC configuration.  
SIGNAL LINE CIRCUIT (SLC)  
30 VDC MAX.  
TWISTED PAIR RECOMMENDED  
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED  
FROM PANEL OR  
PREVIOUS DEVICE  
MODULE POLARITIES ARE  
SHOWN IN ALARM  
+
(+)  
14  
13  
12  
11  
10  
9
1
2
3
4
+
(–)  
(+)  
(–)  
(+)  
(–)  
(+)  
EOL RESISTOR  
IS INTERNAL AT  
TERMINALS 13 & 14  
(–)  
(+)  
(–)  
(+)  
(–)  
TO NEXT  
DEVICE  
24 VDC  
POWER  
SUPPLY  
8
7
24 VDC POWER SUPPLY  
UL LISTED  
EOL RELAY  
SHOWN  
ENERGIZED  
24 VDC COIL  
A77-716B  
ISOLATED, REGULATED,  
POWER LIMITED PER NFPA 70  
LISTED FOR FIRE PROTECTION  
WITH BATTERY BACK-UP  
TO NEXT CONTROL MODULE  
TERMINALS 10 (+) AND 9 (–)  
OR END OF LINE RELAY  
(IF REQUIRED)  
OR EQUIVALENT  
FROM TERMINALS  
7 AND 8 OF LAST  
CONTROL MODULE  
ON BRANCH  
C0107-04  
REQUIRED FOR PANELS  
WITHOUT POWER SUPPLY  
MONITORING  
Figure 4: Typical Class B, Style Y Audio NAC configuration.  
SIGNAL LINE CIRCUIT (SLC)  
30 VDC MAX.  
TWISTED PAIR RECOMMENDED  
ALL WIRING SHOWN IS SUPERVISED  
FROM PANEL OR  
PREVIOUS DEVICE  
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION  
+
(+)  
14  
13  
12  
11  
10  
9
1
2
3
4
+
(–)  
(+)  
EOL  
RESISTOR  
(–)  
(+)  
TO NEXT  
DEVICE  
(–)  
(+)  
(–)  
AUDIO  
AMPLIFIER  
70.7 Vrms Max.  
8
7
AUDIO CIRCUIT MUST BE  
TWISTED PAIR AS A MINIMUM  
WHEN A 70.7 V AUDIO AMPLIFIER IS USED,  
TERMINALS 1-4 ARE POWER LIMITED,  
WHILE TERMINALS 7-14 ARE  
TO NEXT CONTROL MODULE  
LAST MODULE MUST  
RETURN WIRES  
AUDIO AMP.  
C0108-01  
NON-POWER LIMITED  
D500-54-00ꢀ  
3ꢀ  
I56-2016-004  
Figure 5: Typical Class A, Style Z Audio NAC configuration.  
ALL WIRING SHOWN IS SUPERVISED  
SIGNAL LINE CIRCUIT (SLC)  
30 VDC MAX.  
TWISTED PAIR RECOMMENDED  
FROM PANEL OR  
PREVIOUS DEVICE  
SPEAKERS MUST BE LISTED FOR FIRE PROTECTION  
+
(+)  
14  
13  
12  
11  
10  
9
1
2
3
4
+
(–)  
(+)  
(–)  
(+)  
TO NEXT  
DEVICE  
(–)  
AUDIO  
AMPLIFIER  
70.7 Vrms Max.  
(–)  
(+)  
8
7
REQUIRED  
BYPASS CAPACITORS:  
100µF 16V NONPOLARIZED  
<10µA LEAKAGE  
EOL RESISTOR  
IS INTERNAL  
AT TERMINALS  
13 AND 14  
AUDIO CIRCUIT MUST BE  
TWISTED PAIR AS A MINIMUM  
WHEN A 70.7 V AUDIO AMPLIFIER  
IS USED, TERMINALS 1-4 ARE  
POWER LIMITED, WHILE TERMINALS  
7-14 ARE NON-POWER LIMITED  
TO NEXT CONTROL MODULE  
LAST MODULE MUST  
RETURN WIRES  
A2143-60  
C0109-01  
Three-Year Limited Warranty  
SystemꢀSensorꢀwarrantsꢀitsꢀenclosedꢀproductꢀtoꢀbeꢀfreeꢀfromꢀdefectsꢀinꢀmateri-  
alsꢀandꢀworkmanshipꢀunderꢀnormalꢀuseꢀandꢀserviceꢀforꢀaꢀperiodꢀofꢀthreeꢀyearsꢀ  
fromꢀdateꢀofꢀmanufacture.ꢀSystemꢀSensorꢀmakesꢀnoꢀotherꢀexpressꢀwarrantyꢀforꢀ  
thisꢀairꢀductꢀsmokeꢀdetector.ꢀNoꢀagent,ꢀrepresentative,ꢀdealer,ꢀorꢀemployeeꢀofꢀ  
theCompanyhastheauthoritytoincreaseoraltertheobligationsorlimitationsꢀ  
ofꢀthisꢀWarranty.ꢀTheꢀCompany’sꢀobligationꢀofꢀthisꢀWarrantyꢀshallꢀbeꢀlimitedꢀ  
toꢀtheꢀreplacementꢀofꢀanyꢀpartꢀofꢀtheꢀproductꢀwhichꢀisꢀfoundꢀtoꢀbeꢀdefectiveꢀ  
inꢀmaterialsꢀorꢀworkmanshipꢀunderꢀnormalꢀuseꢀandꢀserviceꢀduringꢀtheꢀthreeꢀ  
yearꢀperiodꢀcommencingꢀwithꢀtheꢀdateꢀofꢀmanufacture.ꢀAfterꢀphoningꢀSystemꢀ  
Sensor’sꢀtollꢀfreeꢀnumberꢀ800-SENSOR2ꢀ(736-7672)ꢀforꢀaꢀReturnꢀAuthorizationꢀ  
number,ꢀ sendꢀ defectiveꢀ unitsꢀ postageꢀ prepaidꢀ to:ꢀ Systemꢀ Sensor,ꢀ Returnsꢀ  
Department,ꢀRAꢀ#__________,ꢀ3825ꢀOhioꢀAvenue,ꢀSt.ꢀCharles,ꢀILꢀ60174.ꢀPleaseꢀ  
includeꢀ aꢀ noteꢀ describingꢀ theꢀ malfunctionꢀ andꢀ suspectedꢀ causeꢀ ofꢀ failure.ꢀ  
TheꢀCompanyꢀshallꢀnotꢀbeꢀobligatedꢀtoꢀꢀreplaceꢀunitsꢀwhichꢀareꢀfoundꢀtoꢀbeꢀ  
defectiveꢀbecauseꢀofꢀdamage,ꢀunreasonableꢀuse,ꢀmodifications,ꢀorꢀalterationsꢀ  
occurringꢀ afterꢀ theꢀ dateꢀ ofꢀ manufacture.ꢀ Inꢀ noꢀ caseꢀ shallꢀ theꢀ Companyꢀ beꢀ  
liableꢀforꢀanyꢀconsequentialꢀorꢀincidentalꢀdamagesꢀforꢀbreachꢀofꢀthisꢀorꢀanyꢀ  
otherꢀWarranty,ꢀexpressedꢀorꢀimpliedꢀwhatsoever,ꢀevenꢀifꢀtheꢀlossꢀorꢀdamageꢀ  
isꢀcausedꢀbyꢀtheꢀCompany’sꢀnegligenceꢀorꢀfault.ꢀSomeꢀstatesꢀdoꢀnotꢀallowꢀtheꢀ  
exclusionꢀorꢀlimitationꢀofꢀincidentalꢀorꢀconsequentialꢀdamages,ꢀsoꢀtheꢀaboveꢀ  
limitationꢀorꢀexclusionꢀmayꢀnotꢀapplyꢀtoꢀyou.ꢀThisꢀWarrantyꢀgivesꢀyouꢀspecificꢀ  
legalꢀrights,ꢀandꢀyouꢀmayꢀalsoꢀhaveꢀotherꢀrightsꢀwhichꢀvaryꢀfromꢀstateꢀtoꢀstate.  
FCC Statement  
Thisꢀdeviceꢀcompliesꢀwithꢀpartꢀ15ꢀofꢀtheꢀFCCꢀRules.ꢀOperationꢀisꢀsubjectꢀtoꢀtheꢀfollowingꢀtwoꢀconditions:ꢀ(1)ꢀThisꢀdeviceꢀmayꢀnotꢀcauseꢀharmfulꢀinterference,ꢀandꢀ(2)ꢀthisꢀdeviceꢀ  
mustꢀacceptꢀanyꢀinterferenceꢀreceived,ꢀincludingꢀinterferenceꢀthatꢀmayꢀcauseꢀundesiredꢀoperation.  
NOTE:ꢀThisꢀequipmentꢀhasꢀbeenꢀtestedꢀandꢀfoundꢀtoꢀcomplyꢀwithꢀtheꢀlimitsꢀforꢀaꢀClassꢀBꢀdigitalꢀdevice,ꢀpursuantꢀtoꢀPartꢀ15ꢀofꢀtheꢀFCCꢀRules.ꢀTheseꢀlimitsꢀareꢀdesignedꢀtoꢀpro-  
videꢀreasonableꢀprotectionꢀagainstꢀharmfulꢀinterferenceꢀinꢀaꢀresidentialꢀinstallation.ꢀThisꢀequipmentꢀgenerates,ꢀusesꢀandꢀcanꢀradiateꢀradioꢀfrequencyꢀenergyꢀand,ꢀifꢀnotꢀinstalledꢀ  
andꢀusedꢀinꢀaccordanceꢀwithꢀtheꢀinstructions,ꢀmayꢀcauseꢀharmfulꢀinterferenceꢀtoꢀradioꢀcommunications.ꢀHowever,ꢀthereꢀisꢀnoꢀguaranteeꢀthatꢀinterferenceꢀwillꢀnotꢀoccurꢀinꢀaꢀ  
particularꢀinstallation.ꢀIfꢀthisꢀequipmentꢀdoesꢀcauseꢀharmfulꢀinterferenceꢀtoꢀradioꢀorꢀtelevisionꢀreception,ꢀwhichꢀcanꢀbeꢀdeterminedꢀbyꢀturningꢀtheꢀequipmentꢀoffꢀandꢀon,ꢀtheꢀuserꢀ  
isꢀencouragedꢀtoꢀtryꢀtoꢀcorrectꢀtheꢀinterferenceꢀbyꢀoneꢀorꢀmoreꢀofꢀtheꢀfollowingꢀmeasures:  
–ꢀReorientꢀorꢀrelocateꢀtheꢀreceivingꢀantenna.  
–ꢀIncreaseꢀtheꢀseparationꢀbetweenꢀtheꢀequipmentꢀandꢀreceiver.  
–ꢀConnectꢀtheꢀequipmentꢀintoꢀanꢀoutletꢀonꢀaꢀcircuitꢀdifferentꢀfromꢀthatꢀtoꢀwhichꢀtheꢀreceiverꢀisꢀconnected.  
–ꢀConsultꢀtheꢀdealerꢀorꢀanꢀexperiencedꢀradio/TVꢀtechnicianꢀforꢀhelp.  
D500-54-00ꢀ  
4ꢀ  
I56-2016-004ꢀ  
©2006ꢀSystemꢀSensor  

相关型号:

EM-23046-C36

MICROPHONE
KNOWLES

EM-23046-P16

MICROPHONE
KNOWLES

EM-23069-000

MICROPHONE
KNOWLES

EM-24047-000

MICROPHONE
KNOWLES

EM-4530

EM4530 & EM4530P-C Omnidirectional Electret Condenser Microphone
SOBERTON

EM-4530-C

EM4530 & EM4530P-C Omnidirectional Electret Condenser Microphone
SOBERTON

EM-5

Euro Base Modular 5m Coax
ETC

EM-6027

Omnidirectional Electret Condenser Microphone
SOBERTON

EM-6027P

EM6027, EM6027S-BC, & EM6027P Omnidirectional Electret Condenser Microphone
SOBERTON

EM-6027P_18

EM ELECTRET CONDENSER MICROPHONE
SOBERTON

EM-6781

EM-6781 is ultra-small Hall effect ICs of a single silicon chip composed of Hall element and a signal processing IC
AKM

EM-7117-10

15 A, BARRIER STRIP TERMINAL BLOCK, 2 ROWS, 2 DECKS
COOPER