2966757 [PHOENIX]
Power/Signal Relay, Momentary, 0.004A (Coil), 220VDC (Coil), 0.1A (Contact), 48VDC (Contact), AC/DC Input, DC Output, DIN-Rail Mount, ROHS COMPLIANT;型号: | 2966757 |
厂家: | PHOENIX CONTACT |
描述: | Power/Signal Relay, Momentary, 0.004A (Coil), 220VDC (Coil), 0.1A (Contact), 48VDC (Contact), AC/DC Input, DC Output, DIN-Rail Mount, ROHS COMPLIANT 继电器 |
文件: | 总4页 (文件大小:243K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
PLC-OS…
PLC INTERFACE With Solid-State Relay,
Universal Version
INTERFACE
Data Sheet
103148_en_02
© PHOENIX CONTACT - 03/2008
1.2
Plug-In Bridges Save Wiring
1
Description
The PLC INTERFACE module achieves maximum
efficiency with the user-friendly FBST plug-in bridge system.
The PLC-OS… makes effective use of the bridging options
for the A1/A2 connection on the control side and for the
power supply at connection 13 on the load side. Especially
effective here are the 500 mm long color-insulated
continuous plug-in bridges that can easily be cut to the
required length and quickly inserted in the bridge shafts.
They eliminate the need for complicated and time-
consuming loop bridges.
PLC-OS… relay modules, which can be used universally,
comprise 6.2 mm basic terminal blocks and plug-in
miniature solid-state relays with screw or spring-cage
connection.
1.1
Input Voltages From 24 V to 230 V
The PLC-OS… is available on the control side in all common
industrial voltages from 24 V to 230 V. A further advantage
is the ready-integrated input circuit. It consists of a status
indicator and polarity reversal protection function, and
ensures that the operating state is displayed clearly, also
preventing destruction of the optical electronics should the
polarity be accidentally reversed.
1.3
Additional Advantages
–
Switching power of up to 24 V DC/3 A, depending on
the type
–
–
IP67-protected fully encapsulated optical electronics
Available with input or power solid-state relays as an
option
–
–
Integrated input circuit
Solid-state relay can be replaced using an engagement
lever
–
–
–
Wear-resistant switching
Resistant to vibrations and shocks
Inflammability class V0 according to UL94
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
PLC-OS…
2
Ordering Data
PLC INTERFACE With Screw Connection
Description
Type
Order No.
Pcs./Pck.
PLC INTERFACE With Input Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC... basic
terminal block and plug-in miniature solid-state
relay (see INTERFACE catalog), for mounting on
3. Other input voltages on request.
24 V DC PLCOSC- 24DC/48DC/100
2966728
2966744
2966757
10
10
10
120 V AC/110 V DC PLCOSC-120UC/48DC/100
1
230 V AC/220 V DC PLCOSC-230UC/48DC/100
PLC INTERFACE With Power Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC.../21
basic terminal block and plug-in miniature solid-
state relay (see INTERFACE catalog), for
mounting on 3. Other input voltages on
request.
24 V DC PLCOSC- 24DC/24DC/2
2966634
2966650
2966663
10
10
10
120 V AC/110 V DC PLCOSC-120UC/24DC/2
1
230 V AC/220 V DC PLCOSC-230UC/24DC/2
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
PLC INTERFACE With Spring-Cage Connection
Description
Type
Order No.
Pcs./Pck.
PLC INTERFACE With Input Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC... basic
terminal block and plug-in miniature solid-state
relay (see INTERFACE catalog), for mounting on
3. Other input voltages on request.
24 V DC PLCOSP- 24DC/48DC/100
2967549
2967552
2967565
10
10
10
120 V AC/110 V DC PLCOSP-120UC/48DC/100
1
230 V AC/220 V DC PLCOSP-230UC/48DC/100
PLC INTERFACE With Power Solid-State Relay, Universal Version
PLC INTERFACE, comprising PLC-BSC.../21
basic terminal block and plug-in miniature solid-
state relay (see INTERFACE catalog), for
mounting on 3. Other input voltages on
request.
24 V DC PLCOSP- 24DC/24DC/2
2967471
2967484
2967497
10
10
10
120 V AC/110 V DC PLCOSP-120UC/24DC/2
1
230 V AC/220 V DC PLCOSP-230UC/24DC/2
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
With the 120 V and 230 V modules, an OPT-60DC/... 60 V solid-state relay is normally used due to the input circuit integrated in the basic terminal
block.
For the protection of input and output, inductive loads must be dampened with an effective protective circuit.
Accessories
Description
Insulating plate
Type
PLC-ATP BK
Order No.
2966841
Pcs./Pck.
25
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for
potential bridging) and for safe isolation between adjacent modules.
For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com.
103148_en_02
PHOENIX CONTACT
2
PLC-OS…
3
Technical Data
Input Data
Nominal input voltage
PLCOS...48DC/100
PLCOS...24DC/2
1
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
24 V DC
120 V AC/110 V DC
230 V AC/220 V DC
Permissible range (with reference to U
Switching level
)
0.8 ... 1.2 x U
0.8 ... 1.1 x U
0.8 ... 1.2 x U
0.8 ... 1.1 x U
N
N
N
N
N
1 signal ("H")
0.8 x U
0.4 x U
8 mA
0.8 x U
0.3 x U
4 mA
0.8 x U
0.4 x U
9 mA
0.8 x U
N
N
N
N
N
N
N
0 signal ("L")
0.25 x U
4 mA
N
Typical input current at U
N
Typical response time at U
20 μs
6 ms
20 μs
6 ms
N
Typical release time at U
Transmission frequency f
Input circuit
300 μs
300 Hz
10 ms
10 Hz
Yellow LED, bridge
rectifier
300 μs
300 Hz
10 ms
10 Hz
Yellow LED, bridge
rectifier
N
limit
Yellow LED,
protection
Yellow LED,
protection
against polarity
reversal, free-
wheeling diode
against polarity
reversal, free-
wheeling diode
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
Output Data
PLCOS...48DC/100
PLCOS...24DC/2
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
Output configuration
48 V DC
33 V DC
3 V DC
100 mA
–
3 A (see "Derating Curve")
15 A (10 ms)
2-wire floating
Output circuit
Protection against polarity reversal, surge protection
Voltage drop at maximum limiting continuous current
≤ 1 V
≤ 200 mV
General Data
Impulse voltage withstand level
Ambient temperature range
Operation
2.5 kV, 50 Hz, 1 min.
-25°C ... 60°C
-40°C ... 85°C
100% operating factor
V0
Storage/transport
Nominal operating mode
Inflammability class according to UL 94 (housing)
Standards/specifications
1
IEC 60664, IEC 60664 A, DIN VDE 0110 (basic insulation)
Pollution degree
2
Surge voltage category
Mounting position
III
Any
Mounting
Can be aligned without spacing
Conductor cross-section
Solid, with screw connection
Stranded, with screw connection
Solid, with spring-cage connection
Stranded, with spring-cage connection
Stripping length
2
2
0.14 mm ... 2.5 mm (26 - 14 AWG)
2
2
0.14 mm ... 1.5 mm (26 - 14 AWG)
2
2
0.2 mm ... 2.5 mm (24 - 14 AWG)
0.2 mm ... 1.5 mm (24 - 14 AWG)
2
2
Screw connection
10 mm
Spring-cage connection
Dimensions (W x H x D)
Housing material
8 mm
6.2 mm x 94 mm x 80 mm
Polyamide PA, green
1
The PLC-ATP BK insulating plate must be installed for safe isolation between adjacent modules (see "Accessories"). FBST 8-PLC... or FBST 500... is
then used for potential bridging.
103148_en_02
PHOENIX CONTACT
3
PLC-OS…
Tests/Approvals
CE
c
UL
GL
U u
F
4
Block Diagram
5
Derating Curve
3
2
1
0
13+
14
A2
A1
1)
1)
The input circuit
0
10
20
30
40
50
60
depends on the type
Ambient temperature [°C]
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
103148_en_02
4
相关型号:
2966906
Power/Signal Relay, SPDT, Momentary, 0.015A (Coil), 12VDC (Coil), 6A (Contact), 250VDC (Contact), DC Input, AC/DC Output, DIN-Rail Mount, ROHS COMPLIANT
PHOENIX