ADG0042D [MTU]

DIESEL GENERATOR SET;
ADG0042D
型号: ADG0042D
厂家: MTU ONSITE ENERGY CORPORATION    MTU ONSITE ENERGY CORPORATION
描述:

DIESEL GENERATOR SET

文件: 总4页 (文件大小:428K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
A TOGNUM GROUP BRAND  
DIESEL GENERATOR SET  
TYPE ADG42D  
42 kVA/Prime/50Hz  
(46 kVA/LTP/50Hz)  
Optional equipment shown. Standard equipment may vary.  
BENEFITS  
//  
//  
//  
//  
Most compact design  
Air cooled engine — trouble-free cooling system  
Lowest maintenance cost  
High user-friendlyness  
SYSTEM RATINGS  
Prime (LTP)  
ADG42D  
ADG42D  
ADG42D  
Voltage (L-L)  
380V  
400V  
415V  
Phase  
3
3
3
PF  
0.8  
0.8  
0.8  
Hz  
50  
50  
50  
kWe  
kVA  
33.6 (36.8)  
42 (46)  
33.6 (36.8)  
42 (46)  
33.6 (36.8)  
42 (46)  
AMPS  
64  
61  
58  
Generator model  
Temp rise  
Load acceptance  
ACG-0042-4-400  
125°C (150°C)  
100%  
ACG-0042-4-400  
125°C (150°C)  
100%  
ACG-0042-4-400  
125°C (150°C)  
100%  
Power available up to 25°C/100 m  
Technical data for prime power  
/ // /  
2
50 Hz 42 kVA  
CERTIFICATIONS AND STANDARDS  
//  
//  
Engine-generator set is designed and manufactured in  
Power rating  
facilities certified to standards ISO 9001:2008  
Performance Assurance Certification (PAC)  
- Engine-generator set tested to ISO 8528-5 for  
transient response  
- Verified product design, quality and performance integrity  
- All generator sets are type and factory tested  
- Permissible average power output during 24 hours of  
operation is approved up to 75% for prime power rating  
- Permissible average power output during 24 hours of  
operation is approved up to 100% for limited time power  
rating. Operating hours are limited to 500 hours per year.  
//  
STANDARD EQUIPMENT  
//  
//  
Engine  
Generator  
Air cleaners  
Oil pump  
NEMA MG1, IEEE and ANSI standards compliance for temperature rise  
and motor starting  
Oil drain extension & S/O valve  
Full pre-filter with water seperator  
Full flow oil filters  
VDE 0530, IEC 34.1, BS5000, CSA C22.2-100, AS1359  
Self-ventilated  
Superior voltage waveform  
Exhaust manifold – dry  
Blower fan & fan drive  
Electric starting motor – 12V  
Governor – mechanical  
SAE flywheel  
No load to full load regulation  
125°C prime temperature rise (insulation class H)  
1 bearing, sealed  
Full amortisseur windings  
125% rotor balancing  
Flexible fuel connectors  
3-phase voltage sensing  
Automatic voltage regulator 0,5%  
Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.  
/ // /  
3
50 Hz 42 kVA  
STANDARD FEATURES  
//  
//  
The generator set complies to G2  
Engine-generator set tested to ISO 8528-5 for transient  
response  
MTU Onsite Energy is a single source supplier  
Global product support  
2 year standard warranty  
Self-exited generator  
//  
- Brushless, rotating field generator  
- 300% short circuit capability  
- 2/3 pitch windings  
Cooling system 50°C  
- Integral set-mounted  
//  
//  
//  
//  
//  
//  
F4L 914 diesel engine 4-cycle  
- Engine driven fan  
Engine-generator resilient mounted  
APPLICATION DATA  
//  
//  
Engine  
Fuel Consumption and Fuel Tank Capacity  
PRIME  
Manufacturer  
Model  
Type  
Arrangement  
Displacement  
Bore: cm  
Deutz  
F4L 914  
4-cycle  
4/in-line  
4.31 l  
At 100% load  
At 75% load  
At 50% load  
At 25% load  
Capacity of base frame fuel tank (open set)  
Capacity of base frame fuel tank (sound proof)  
9.3 l/h (205 g/kWh)  
7.1 l/h (208 g/kWh)  
5.2 l/h (230 g/kWh)  
3.7 l/h (325 g/kWh)  
155 l  
10.2  
155 l  
Stroke: cm  
13.2  
Compression ratio  
Rated RPM (speed)  
Engine governor  
Gross power: kWm  
Aspiration  
20.6 :1  
1,500  
Mechanical  
43.5 kW  
Natural aspiration  
//  
Cooling System  
PRIME  
Max. ambient temperature: °C  
Fan power consumption: kW  
Cooling air flow: m3/h  
50  
0.5  
1810  
10  
//  
Lubrication System  
Air pressure loss: mbar  
//  
Oil capacity (sump) min./max.  
Lube oil consumption (in % of fuel cons.)  
Oil pressure min. (warning): bar  
Oil pressure min. (shut-down): bar  
Max. oil temperature: °C  
11 l  
0.5  
1.5  
1.5  
130  
Combustion Air  
PRIME  
Combustion air volume: m3/h  
Max. air intake restriction: mbar  
Air cleaner type  
174  
20  
Dry, replaceable element  
with safety catridge  
//  
Fuel System  
//  
Exhaust System  
Recommended fuel  
see MTU fluids & lubrication spec.  
PRIME  
Max. exhaust gas temperature: °C  
Max. exhaust back pressure: mbar  
Exhaust gas flow: m3/h  
580  
30  
476  
//  
Heat Rejection  
PRIME  
Engine radiation and convection: kW  
Heat rejection of generator: kW  
approx. 32.8  
approx. 4.8  
Represents standard product only. Consult Factory/MTU Onsite Energy distributor for additional configurations.  
Technical data for prime power  
/ // /  
4
50 Hz 42 kVA  
WEIGHTS AND DIMENSIONS  
1988  
1110  
Drawing above for illustration purposes only, based on standard sound proof 400 volt engine-generator set. Do not use for installation design.  
See website for unit specific template drawings.  
System  
Dimensions (LxWxH)  
Weight (dry/less tank)  
Sound Proof Unit (SPU)  
1988 x 1110 x 1736 mm  
approx. 1175 kg  
NOISE EMISSION (SOUND PROOF)  
Sound power LWA: dB(A)  
93  
Sound power LPA@1m: dB(A)  
Sound power LPA@7m: dB(A)  
76  
64  
RATING DEFINITIONS AND CONDITIONS  
//  
Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of  
generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in  
accordance with ISO 8528-1, ISO 3046-1, BS 5514, AS 2789, and DIN 6271.  
//  
//  
Limited time power ratings apply to installations served by a reliable utility source. The standby rating is applicable to constant  
or varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with  
ISO 8528-1, ISO 3046-1, BS 5514, AS 2789 and DIN 6271.  
Deration factor:  
Altitude: Consult your local MTU Onsite Energy distributor for altitude derations.  
Temperature: Consult your local MTU Onsite Energy distributor for temperature derations.  
Materials and specifications subject to change without notice.  
// A Tognum Group Company: MTU Onsite Energy Systems GmbH / 94099 Ruhstorf / Germany / Phone + 49 8531 97 82-0 / Fax + 49 8531 97 82-1510 /  
sales_oer@mtu-online.com /www.mtuonsiteenergy.com  

相关型号:

ADG0062D

DIESEL GENERATOR SET
MTU

ADG0102D

DIESEL GENERATOR SET
MTU

ADG1201

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1201BRJZ-R2

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1201BRJZ-REEL7

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1202

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1202BRJZ-R2

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1202BRJZ-REEL7

Low Capacitance, Low Charge Injection, 【15 V/+12 V iCMOS SPST in SOT-23
ADI

ADG1204

2 pF Off Capacitance, 1 pC Charge Injection, +-15 V/12 V 4:1 iCMOS Multiplexer
ADI

ADG1204YCP

2 pF Off Capacitance, 1 pC Charge Injection, +-15 V/12 V 4:1 iCMOS Multiplexer
ADI

ADG1204YCPZ-500RL7

Low Capacitance, Low Charge Injection, ±15 V/12 V, 4:1 iCMOS Multiplexer
ADI

ADG1204YCPZ-REEL7

Low Capacitance, Low Charge Injection, ±15 V/12 V, 4:1 iCMOS Multiplexer
ADI