MODEL: R7FN-TS4  
EX-FACTORY SETTING  
Remote I/O R7 Series  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-7808-TS4)  
FLEX NETWORK I/O MODULE  
(Thermocouple input, 4 points, isolated)  
Functions & Features  
RELATED PRODUCTS  
• PC configurator software (model: R7CON)  
The configurator software is downloadable at M-System’s  
web site.  
• 4 points thermocouple input module for FLEX NETWORK  
• Input sensor can be selected with the front DIP switches  
for all channels.  
A dedicated cable is required to connect the module to the  
PC. Please refer to the internet software download site or  
the users manual for the PC configurator for applicable  
cable types.  
• Easy parameter setting of individual channels with M-  
System's configurator software  
FLEX NETWORK is registered trademark of Digital  
Electronics Corporation in Japan.  
• Screen editor software (model: GP-Pro EX)  
Screen editor software GP-Pro EX (Ver.2.70 or higher) is  
available.  
115 (4.53)  
For versions between 2.60 and 2.70, the driver must be  
installed. The driver is downloadable at Digital Electronics  
Corporation's web site. http://www.proface.co.jp/  
53 (2.09)  
GENERAL SPECIFICATIONS  
Connection: M3 separable screw terminal (torque 0.5 N·m)  
Solderless terminal: Refer to the drawing at the end of the  
section.  
54 (2.13)  
mm (inch)  
Communication cable  
MODEL: R7FN–TS4-R[1]  
Recommended manufacture: Japan Solderless Terminal  
MFG.Co.Ltd  
ORDERING INFORMATION  
• Code number: R7FN-TS4-R[1]  
Specify a code from below for [1].  
(e.g. R7FN-TS4-R/Q)  
Applicable wire size: 0.2 to 0.5 mm  
2
(AWG 26 to 22)  
Others  
Recommended manufacture: Japan solderless terminal  
MFG.Co.Ltd, Nichifu Co.,ltd  
• Specify the specification for option code /Q  
(e.g. /C01/SET)  
Applicable wire size: 0.25 to 1.65 mm  
2
(AWG 22 to 16)  
Screw terminal: Nickel-plated steel  
Housing material: Flame-resistant resin (gray)  
Isolation: Input 0 to input 1 to input 2 to input 3 to FLEX  
NETWORK to power to FG  
I/O TYPE  
TS4: Thermocouple input, 4 points  
Zero adjustments: Configurable via R7CON  
Span adjustments: Configurable via R7CON  
Conversion rate: Configurable via R7CON  
Thermocouple setting: Configurable via the front DIP switch  
or R7CON  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
Burnout setting: Selectable between upscale (*) and  
downscale with the front DIP switch  
(*) Factory default setting  
[1] OPTIONS  
Linearization: Standard  
blank: none  
Cold junction compensation: CJC sensor attached to the  
input terminals  
/Q: Options other than the above (specify the specification)  
Status indicator LED: PWR, RUN  
SPECIFICATIONS OF OPTION: Q (multiple selections)  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
(Refer to the instruction manual)  
/C02: Polyurethane coating  
/C03: Rubber coating  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 1/6  
http://www.m-system.co.jp/  
MODEL: R7FN-TS4  
■Recommended solderless terminal  
INPUT SPECIFICATIONS  
Input resistance: 30 kΩ min.  
3.3 (.13) max  
Burnout sensing: 0.1 μA  
BURNOUT  
INDICATION (°C)  
T/C  
CONFORMANCE  
RANGE (°C)  
mm (inch)  
Upscale  
+1472  
+1120  
+1300  
+ 500  
1920  
Downscale  
-272  
-272  
-260  
-272  
24  
K (CA)  
-150 to +1370  
-170 to +1000  
-180 to +1200  
-170 to + 400  
400 to 1760  
200 to 1760  
0 to 1760  
E (CRC)  
J (IC)  
FLEX NETWORK COMMUNICATION  
Communication configuration: 1: N  
Connection method: Multi-drop Connection  
Communication method: Cyclic Time Division, half-duplex  
Communication I/F: Differential, pulse transfer isolation  
Error Check: Format, bit, CRC-12 verification  
Max. Number of Nodes: 63 (1008 I/O points)  
Required node: 4  
T (CC)  
B (RH)  
R
-100  
-100  
-52  
+1860  
+1860  
+2416  
+1400  
+ 700  
+1000  
+1496  
+1860  
S
C (WRe 5-26)  
0 to 2315  
N
-272  
-252  
-252  
-52  
-130 to +1300  
-200 to +600  
-200 to +900  
0 to 1395  
U
L
P (Platinel II)  
(PR)  
Network cable: Pro-face’s following cable  
FN-CABLE2010-31-MS (10 m)  
-52  
0 to 1760  
BURNOUT  
INDICATION (°F)  
CONFORMANCE  
RANGE (°F)  
FN-CABLE2050-31-MS (50 m)  
T/C  
FN-CABLE2200-31-MS (200 m)  
Upscale  
+2682  
+2048  
+2372  
+932  
Downscale  
-458  
-458  
-436  
-458  
75  
Transmission distance: 12 Mbps: 100 meters (328 ft)(*)  
6 Mbps: 200 meters (656 ft)  
K (CA)  
-238 to +2498  
-274 to +1832  
-292 to +2192  
-274 to +752  
752 to 3200  
392 to 3200  
32 to 3200  
E (CRC)  
J (IC)  
(*) Factory default setting  
T (CC)  
Station address: Rotary switch  
B (RH)  
3488  
(Refer to the instruction manual)  
R
-148  
-148  
-62  
+3380  
+3380  
+4381  
+2552  
+1292  
+1832  
+2725  
+3380  
Terminating resistor: Built-in  
S
C (WRe 5-26)  
32 to 4199  
N
-458  
-422  
-422  
-62  
-202 to +2372  
-328 to +1112  
-328 to +1652  
32 to 2543  
U
L
P (Platinel II)  
(PR)  
-62  
32 to 3200  
INSTALLATION  
Current consumption  
DC: Approx. 90 mA  
Operating temperature: -10 to +55°C (14 to 131°F)  
Storage temperature: -20 to +65°C (-4 to +149°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Atmosphere: No corrosive gas or heavy dust  
Mounting: DIN rail (35 mm rail)  
Weight: 200 g (0.44 lb)  
PERFORMANCE  
Conversion accuracy: ±1°C (±1.8°F) except ±2°C (±3.6°F)  
for B, R, S, C, PR  
Conversion rate: 250 msec. (*) or 500 msec. selectable  
(*) Factory default setting  
Converted data range:  
• Engineering unit value (°C, K) × 10 (integer)  
• Engineering unit value (°F)  
Cold junction compensation error:  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 2/6  
http://www.m-system.co.jp/  
MODEL: R7FN-TS4  
±1°C max. (at 25°C ±10°C)  
±1.8°F max. (at 77°F ±18°F)  
(±1.5°C or ±2.7°F for R, S, PR)  
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span  
Response time: Conversion rate × 2 + 50 msec. (0 – 90 %)  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute (input 0 to input  
1 to inpu 2 to input 3 to FLEX NETWORK to power to FG)  
STANDARDS & APPROVALS  
EU conformity:  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
EN 50581  
EXTERNAL VIEW  
Operating Mode Setting DIP SW (SW1)  
PC Configurator Jack  
Station Address Setting Rotary SW  
Status Indicator LED  
ON  
2 3 4 5 6 7 8  
1
X10  
8
X1  
8
PWR RUN  
CNFG.  
STATION ADD.  
4
5
6
7
10 11 12 13 14 15 16 17 18  
1
2
3
1
2
3
4
5
6
7
8
9
FLEX NETWORK,  
Power Supply Terminals  
Input Terminals  
CONNECTION DIAGRAMS  
MASTER CONNECTION  
Master Station  
Slave Station  
Slave Station  
+
+
+
TR  
TR  
TR  
Terminating  
Resistor  
TR  
TR  
TR  
+
+
SHIELD  
JP  
JP  
JP  
JP  
Terminating  
Short Bar  
FG  
FG  
Note: Be sure to use the terminator(s) located at both ends of the modules.  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 3/6  
http://www.m-system.co.jp/  
MODEL: R7FN-TS4  
TERMINAL ASSIGNMENTS  
■ INPUT TERMINAL ASSIGNMENT  
10  
11  
12  
13  
14  
NC  
15  
16  
17  
18  
+IN0 –IN0 +IN1 –IN1  
+IN2 –IN2 +IN3 –IN3  
1
2
3
4
5
6
7
8
9
+CJ0 –CJ0 +CJ1 –CJ1  
NC  
+CJ2 –CJ2 +CJ3 –CJ3  
NO. ID  
FUNCTION  
+CJ0 CJC + 0  
–CJ0 CJC – 0  
NO. ID  
FUNCTION  
1
2
3
4
5
6
7
8
9
10 +IN0 T/C + 0  
11 IN0 T/C – 0  
12 +IN1 T/C + 1  
13 –IN1 T/C – 1  
+CJ1 CJC + 1  
–CJ1 CJC – 1  
NC No connection  
+CJ2 CJC + 2  
–CJ2 CJC – 2  
+CJ3 CJC + 3  
–CJ3 CJC – 3  
14  
NC No connection  
15 +IN2 T/C + 2  
16 –IN2 T/C – 2  
17 +IN3 T/C + 3  
18 –IN3 T/C – 3  
NETWORK, POWER SUPPLY TERMINAL ASSIGNMENT  
4
5
6
7
-
TR+ TR +24V 0V  
1
2
3
-
JP+ JP  
FG  
NO.  
1
ID  
JP+  
JP–  
FG  
FUNCTION, NOTES  
Terminating resistor  
Terminating resistor  
FG  
2
3
4
TR+  
TR–  
+24V  
0V  
Network  
5
Network  
6
Power input (24V DC)  
Power input (0V)  
7
DATA CONVERSION  
INPUT RANGE AND DATA CONVERSION (FACTORY DEFAULT SETTING)  
Engineering unit value °C or K is multiplied by 10 and expressed in 16 bits. °F data is represented in engineering unit  
value, without multiplication. Negative value is represented in 2’s complements.  
• Input TYPE K Thermocouple  
Converted Data, Decimal  
Converted Data, Hex  
Input Value  
≤ -272°C  
-150°C  
-2720  
-1500  
13700  
14720  
F560  
FA24  
3584  
3980  
1370°C  
≥ 1472°C  
14720 (3980)  
13700 (3584)  
-272 -150  
1370 1472  
(°C)  
-1500 (FA24)  
-2720 (F560)  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 4/6  
http://www.m-system.co.jp/  
MODEL: R7FN-TS4  
I/O DATA DESCRIPTIONS  
ANALOG INPUT  
• Di  
• Do  
15  
0
0
15  
0
0
ADD.n  
CH0  
CH1  
Unused  
Unused  
15  
15  
ADD.n+1  
15  
0
0
15  
15  
0
0
ADD.n+2  
CH2  
CH3  
Unused  
Unused  
15  
ADD.n+3  
The data is 16-bit binary.  
Negative value is represented in 2’s complements.  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
115 (4.53)  
17 (.66)  
54 (2.13)  
DIN RAIL  
35mm wide  
4
5
6
7
10 11 12 13 14 15 16 17 18  
1
2
3
1
2
3
4
5
6
7
8
9
30 (1.18)  
[5 (.20)]  
6 (.24)  
6 (.24)  
7–M3 SCREW  
TERMINALS  
for FLEX NETWORK, POWER  
18–M3 SCREW  
TERMINALS  
for INPUT  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 5/6  
http://www.m-system.co.jp/  
MODEL: R7FN-TS4  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
Note: In order to improve EMC performance, bond the FG terminal to ground.  
Caution: FG terminal is NOT a protective conductor terminal.  
Isolation  
Input Circuit  
Input Circuit  
Input Circuit  
Input Circuit  
10  
11  
1
+IN0  
–IN0  
+CJ0  
–CJ0  
4
5
TR+  
TR–  
Comm.  
Circuit  
INPUT 0  
INPUT 1  
INPUT 2  
INPUT 3  
1
2
3
6
7
JP+  
JP–  
2
12  
13  
3
+IN1  
−IN1  
+CJ1  
−CJ1  
FG  
24V DC  
0V  
4
Input  
Circuit  
15  
16  
6
+IN2  
–IN2  
+CJ2  
–CJ2  
7
+IN3 17  
–IN3 18  
+CJ3  
–CJ3  
8
9
5
14  
Input Connection Example  
T/C  
+
+INn  
-INn  
-
+
CJn  
CJC  
CENSOR  
-CJ  
n
Specifications are subject to change without notice.  
R7FN-TS4 SPECIFICATIONS  
ES-7808-B Rev.0 Page 6/6  
http://www.m-system.co.jp/  

相关型号:

R7FN-TS4-R

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-TS4-R/Q

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YS2

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YS2-R

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YS2-R/Q

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YV2

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YV2-R

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FN-YV2-R/Q

Remote I/O R7 Series FLEX NETWORK I/O MODULE
MSYSTEM

R7FS124762A01CLM

32-bit ARM Cortex-M0 microcontroller
RENESAS

R7FS124763A01CFL

RISC MICROCONTROLLER
RENESAS

R7FS124763A01CFM

32-bit ARM Cortex-M0 microcontroller
RENESAS

R7FS124763A01CNB

32-bit ARM Cortex-M0 microcontroller
RENESAS