DRC-40A [MEANWELL]

40W Single Output with Battery Charger (UPS Function);
DRC-40A
型号: DRC-40A
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

40W Single Output with Battery Charger (UPS Function)

电池
文件: 总5页 (文件大小:267K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
40W Single Output with Battery Charger (UPS Function)  
DRC-40 series  
Bauart gepruft  
Sicherheit  
egelma ge  
od  
o s  
be wac  
g
www.tuv.com  
ID 2000000000  
LPS  
Features  
Applications  
Universal AC input / Full range  
Protections: Short circuit / Overload / Over voltage  
Battery low protection / Battery reverse polarity protection  
by fuse  
Security system  
Emergency lighting system  
Alarm system  
DC UPS system  
Can be installed on DIN rail TS-35/7.5 or 15  
Alarm signal for AC OK and Battery low  
(via TTL open collector, optional via relay)  
Cooling by free air convection  
Pass LPS  
Central monitoring system  
Access systems  
LED indicator for power on  
100% full load burn-in test  
3 years warranty  
Description  
DRC-40 is a 40W AC/DC DIN rail type security power supply series. In addition to the primary output, there  
is a charger output with a smaller rated current, enabling the backup power supply application the security  
access systems require. DRC-40 accepts the universal input between 90VAC and 264VAC, and supplies  
13.8VDC and 27.6VDC at output, respectively. With the efficiency up to 87%, it can operate with air  
convection cooling under -30through 70. In addition to the key protection features such as overload  
protection, over voltage protection, battery low cut off, and battery reverse polarity protection (by fuse),  
the alarm signal for AC OK and battery low signaling is provided, via TTL open collector output for the  
standard model ( via relay contact output as the optional model), to facilitate the system design.  
Model Encoding  
DRC - 40 A  
Output voltage  
Output wattage  
Series name  
File Name:DRC-40-SPEC 2015-03-12  
40W Single Output with Battery Charger (UPS Function)  
DRC-40 series  
SPECIFICATION  
MODEL  
DRC-40A  
DRC-40B  
OUTPUT NUMBER  
CH1  
CH2  
13.8V  
1A  
CH1  
CH2  
DC VOLTAGE  
13.8V  
1.9A  
27.6V  
27.6V  
0.5A  
RATED CURRENT  
CURRENT RANGE  
RATED POWER  
0.95A  
0 ~ 2.9A  
40.02W  
--------  
0 ~ 1.45A  
40.02W  
200mVp-p  
CH1:24 ~ 30V  
±1.0%  
±0.5%  
±0.5%  
--------  
RIPPLE & NOISE (max.) Note.2 120mVp-p  
--------  
--------  
OUTPUT  
VOLTAGE ADJ. RANGE  
CH1:12 ~ 15V  
VOLTAGE TOLERANCE Note.3 ±1.0%  
--------  
--------  
--------  
--------  
--------  
--------  
LINE REGULATION  
LOAD REGULATION  
±0.5%  
±0.5%  
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC  
800ms, 50ms/115VAC at full load  
HOLD UP TIME (Typ.)  
VOLTAGE RANGE  
50ms/230VAC  
90 ~ 264VAC  
47 ~ 63Hz  
86%  
10ms/115VAC at full load  
127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]  
FREQUENCY RANGE  
EFFICIENCY (Typ.)  
AC CURRENT (Typ.)  
87%  
INPUT  
0.8A/115VAC  
0.6A/230VAC  
INRUSH CURRENT (Typ.) COLD START 30A/115VAC  
60A/230VAC  
105 ~ 150% rated output power  
OVERLOAD  
Protection type : Hiccup mode, recovers automatically after fault condition is removed  
CH1:14.49 ~ 18.63V CH1:28.98 ~ 37.26V  
Protection type : Shut down o/p voltage, re-power on to recover  
10±0.5V  
PROTECTION  
OVER VOLTAGE  
20±1V  
BATTERY CUT OFF  
AC OK  
Open collector output, CONTACT : AC OK ; CUT OFF : AC Fail ; max. rating : 50V/30mA  
Open collector output, CUT OFF : Battery ; CONTACT : Battery Low ; max. rating : 50V/30mA  
FUNCTION  
BATTERY LOW  
Battery low voltage : < 11V  
Battery low voltage : < 22V  
-30 ~ +70(Refer to "Derating Curve")  
20 ~ 90% RH non-condensing  
-40 ~ +85, 10 ~ 95% RH  
WORKING TEMP.  
WORKING HUMIDITY  
STORAGE TEMP., HUMIDITY  
TEMP. COEFFICIENT  
VIBRATION  
ENVIRONMENT  
±0.03%/(0 ~ 55) on CH1 output  
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
UL60950-1, TUV EN60950-1 approved  
SAFETY STANDARDS  
WITHSTAND VOLTAGE  
ISOLATION RESISTANCE  
EMC EMISSION  
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC  
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH  
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3  
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A  
536.6K hrs min. MIL-HDBK-217F (25)  
SAFETY &  
EMC  
(Note 5)  
EMC IMMUNITY  
MTBF  
40*90*100mm (W*H*D)  
OTHERS DIMENSION  
PACKING  
0.3Kg; 42pcs/13.6Kg/0.82CUFT  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.  
3. Tolerance : includes set up tolerance, line regulation and load regulation.  
NOTE  
4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.  
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed  
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power  
supplies.” (as available on http://www.meanwell.com)  
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded  
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.  
File Name:DRC-40-SPEC 2015-03-12  
40W Single Output with Battery Charger (UPS Function)  
DRC-40 series  
Block Diagram  
AC OK  
Bat. Low  
ALARM  
CIRCUIT  
EMI FILTER  
&
RECTIFIER  
RECTIFIERS  
POWER  
+V  
I/P  
&
SWITCHING  
-V  
FILTER  
Bat. +  
DETECTION  
Bat. -  
CIRCUIT  
PWM  
Battery Charger  
&
Back up Control  
O.L.P.  
CONTROL  
O.V.P.  
Derating Curve  
Static Characteristics  
100  
90  
80  
70  
60  
50  
40  
100  
80  
230VAC  
Input only  
60  
40  
20  
-30  
-20  
0
15  
30  
40  
50 55 60  
70  
(VERTICAL)  
90 100 125 135 145 155 165 175 180 200 230 264  
INPUT VOLTAGE (V) 60Hz  
AMBIENT TEMPERATURE ()  
File Name:DRC-40-SPEC 2015-03-12  
40W Single Output with Battery Charger (UPS Function)  
DRC-40 series  
Suggested Application  
1.Backup connection for AC interruption  
(1) Please refer to Fig1.1 for suggested connection.  
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.  
The battery starts to supply power to the load when AC mains fails.  
A : 12V  
B : 24V  
Battery  
Load  
-
-
+
+
Bat+  
Bat-  
V+  
V-  
DC OK  
+
+V ADJ  
Fig 1.1 Suggested system connection  
2.Alarm signal for AC OK and battery low  
(1) Alarm signal is sent out through " AC OK " & " Battery Low " pins.(TTL open collector output is provided for standard model, and relay contact output is provided as  
optional model.)  
(2) An external voltage source is required for this function. The maximum applied voltage is 50V and the maximum sink current is 30mA. Please refer to Fig 2.2.  
(3) Table2.1 explains the alarm function built in the power supply  
Function  
Description  
Output of alarm  
The signal is "Low" when the power supply turns ON.  
Low (0.3V max. at 30mA)  
AC OK  
High or open (External applied voltage 50V max.)  
Low (0.3V max. at 30mA)  
The signal turns to be "High" when the power supply turns OFF.  
The signal is "Low" when the voltage of battery is under A:11V, B:22V.  
The signal is "High" when the voltage of battery is above A:11V, B:22V.  
Battery Low  
High or open (External applied voltage 50V max.)  
Table 2.1 Explanation of alarm signal  
AC OK (Battery low)  
R
V
Pin6(Pin8) Short with output -V External voltage and R  
(The max. Sink is 30mA and 50V)  
Fig 2.2 Internal circuit of AC OK (Battery Low), via TTL open collector  
File Name:DRC-40-SPEC 2015-03-12  
40W Single Output with Battery Charger (UPS Function)  
DRC-40 series  
Mechanical Specification  
Case No.962A Unit:mm  
40  
100  
3.81×7  
8
7 6 5 4 3 2 1  
TB2  
DC OK  
+
+V ADJ  
TB1  
3
2
1
7.5 7.5  
Terminal Pin No. Assignment (TB1):  
Pin No. Assignment  
1
2
3
AC/L or DC+  
AC/N or DC-  
FG  
Terminal Pin No. Assignment (TB2):  
Pin No. Assignment Pin No. Assignment  
1
2
3
-V  
+V  
4
Bat. -  
AC OK  
5,6  
7,8  
Bat. +  
Bat. Low  
Installation Instruction  
This series fits DIN rail TS35/7.5 or TS35/15.  
(This diagram is for reference. The rail is not included with unit.)  
Back View  
File Name:DRC-40-SPEC 2015-03-12  

相关型号:

DRC-40B

40W Single Output with Battery Charger (UPS Function)
MEANWELL

DRC-60

60W Single Output with Battery Charger (UPS Function)
MEANWELL

DRC-60A

60W Single Output with Battery Charger (UPS Function)
MEANWELL

DRC-60B

60W Single Output with Battery Charger (UPS Function)
MEANWELL

DRC-644-L-1

Digital-to-Resolver Converter
ETC

DRC-644-L-1-R

Digital-to-Resolver Converter
ETC

DRC-644-L-3

Digital-to-Resolver Converter
ETC

DRC-644-L-3-R

Digital-to-Resolver Converter
ETC

DRC020

Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF

DRC020-107

Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF

DRC020-113

Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF

DRC020-125

Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF