60W Single Output with Battery Charger (UPS Function)
DRC-60 series
Bauart gepruft
Sicherheit
egelma ge
od o s
be wac g
www.tuv.com
ID 2000000000
LPS
■
■
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
•
‧
‧
‧
‧
■
℃℃
■
File Name:DRC-60-SPEC 2014-1122
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
SPECIFICATION
MODEL
DRC-60A
DRC-60B
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
2.8A
13.8V
1.5A
27.6V
27.6V
0.75A
--------
RATED CURRENT
CURRENT RANGE
RATED POWER
1.4A
0 ~ 4.3A
59.34W
--------
0 ~ 2.15A
59.34W
200mVp-p
CH1:24 ~ 30V
±1.0%
±0.5%
±0.5%
RIPPLE & NOISE (max.) Note.2 120mVp-p
--------
--------
OUTPUT
VOLTAGE ADJ. RANGE
CH1:12 ~ 15V
VOLTAGE TOLERANCE Note.3 ±1.0%
--------
--------
--------
--------
--------
--------
LINE REGULATION
LOAD REGULATION
±0.5%
±0.5%
SETUP, RISE TIME Note.4 400ms, 50ms/230VAC
800ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC
90 ~ 264VAC
47 ~ 63Hz
86%
10ms/115VAC at full load
127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
88%
INPUT
1.3A/115VAC
0.8A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC
60A/230VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Hiccup mode, recovers automatically after fault condition is removed
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
10±0.5V
PROTECTION
FUNCTION
ENVIRONMENT
OVER VOLTAGE
20±1V
BATTERY CUT OFF
AC OK
Relay contact output, ON : AC OK ; OFF : AC Fail ; max. rating : 30V/1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; max. rating : 30V/1A
BATTERY LOW
Battery low voltage : < 11V
Battery low voltage : < 22V
-30 ~ +70℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
±0.03%/℃ (0 ~ 50℃) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
504.1K hrs min. MIL-HDBK-217F (25℃)
SAFETY &
EMC
(Note 5)
EMC IMMUNITY
MTBF
40*90*100mm (W*H*D)
0.3Kg; 42pcs/13.6Kg/0.82CUFT
OTHERS DIMENSION
PACKING
℃
NOTE
File Name:DRC-60-SPEC 2014-10-22
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
Block Diagram
AC OK
RL1
RL2
ALARM
CIRCUIT
Bat. Low
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
+V
-V
Bat. +
I/P
&
RECTIFIER
FILTER
DETECTION
Bat. -
CIRCUIT
PWM
Battery Charger
&
O.L.P.
CONTROL
O.V.P.
Back up Control
Derating Curve
Static Characteristics
100
90
80
70
60
50
40
100
80
230VAC
Input only
60
40
20
-30
-20
0
15
30
40
50
60
70
(VERTICAL)
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz
AMBIENT TEMPERATURE (℃)
File Name:DRC-60-SPEC 2014-10-22
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
Suggested Application
1.Backup connection for AC interruption
(1) Please refer to Fig1.1 for suggested connection.
The power supply charges the battery and provides energy to the load at the same time when AC mains is OK.
The battery starts to supply power to the load when AC mains fails.
A : 12V
B : 24V
Battery
Load
-
-
+
+
Bat+
Bat-
V+
V-
DC OK
+
+V ADJ
Fig 1.1 Suggested system connection
2.Alarm signal for AC OK and battery low
(1) Alarm Signal is sent out through " AC OK " & " Battery Low " pins via relay contact.
(2) An external voltage source is required for this function. The maximum applied voltage is 30V and the maximum sink current is 1A. Please refer to Fig 2.2.
(3) Table2.1 explains the alarm function built in the power supply
(4) AC OK signal (RL1,referring to Block Diagram) will go into hiccup mode when the overload protecton is activated.
Function
AC OK
Description
Output of alarm
Low or short
The signal is "Low" when the power supply turns ON.
High or open (External applied voltage 30V max.)
Low or short
The signal turns to be "High" when the power supply turns OFF.
The signal is "Low" when the voltage of battery is under A:11V, B:22V.
The signal is "High" when the voltage of battery is above A:11V, B:22V.
Battery Low
High or open (External applied voltage 30V max.)
Table 2.1 Explanation of alarm signal
AC OK (Battery low)
R
External voltage sorece (V) and resistor (R)
(The max. Sink is 1A and 30V)
V
Fig 2.2 Internal circuit of AC OK (Battery Low), via relay contact
File Name:DRC-60-SPEC 2014-10-22
60W Single Output with Battery Charger (UPS Function)
DRC-60 series
Mechanical Specification
Mechanical Specification
Case No.962A Unit:mm
40
100
3.81×7
8
7 6 5 4 3 2 1
TB2
DC OK
+
+V ADJ
TB1
3
2
1
7.5 7.5
Terminal Pin No. Assignment (TB1):
Pin No. Assignment
1
2
3
AC/L or DC+
AC/N or DC-
FG
Terminal Pin No. Assignment (TB2):
Pin No. Assignment Pin No. Assignment
1
2
3
-V
+V
Bat. +
4
5,6
7,8
Bat. -
AC OK
Bat. Low
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
(This diagram is for reference. The rail is not included with unit.)
Back View
File Name:DRC-60-SPEC 2014-10-22
相关型号:
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-107
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-113
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-125
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-130
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-145
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_1.jpg)
![](http://pdffile.icpdf.com/pdf1/p00195/img/page/DRC020_1102661_files/DRC020_1102661_2.jpg)
DRC020-394
Funk-Entstördrosseln Radio-Interference suppression chokes Selfs de déparasitage
EICHHOFF
©2020 ICPDF网 联系我们和版权申明