MM-0637A-50C [JMK]
Operating Voltage = 48 Vdc Operating Current = 50 Amperes; 工作电压= 48伏直流工作电流= 50安培型号: | MM-0637A-50C |
厂家: | JMK INC. |
描述: | Operating Voltage = 48 Vdc Operating Current = 50 Amperes |
文件: | 总1页 (文件大小:48K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MM-0637A-50C
Operating Voltage = 48 Vdc
LOAD
LINE
Operating Current = 50 Amperes
Operating Temperature Range = -40 to 50 C
Dielectric Withstanding Voltage
Line to Line: 707 Vdc for 1 minute
Line to Case: 2250 Vdc for 1.0 min
Order P/N:
MM-0637A-50C
Safety Agency Approvals
EN
60 950
R
INSERTION LOSS vs. FREQUENCY
MM-0637A-50C
C
US
70
60
50
40
This compact filter is intended to provide noise reduction
for telecommunications DC power. The filter is non-
polarized and the insertion loss is specified at full load.
DM
CM
30
20
If modifications are needed to suppress transients, or if
more severe temperature operating parameters are re-
quired, call or e-mail our Engineering Dept. They will be
more than happy to assist you.
10
0
.04
1
4
.01
.1
.4
10
40
100
.02
.07
.2
.7
2
7
20
70
FREQUENCY (MEGAHERTZ)
3.56
3.16
1.18
0.60
Ø0.220 (2x)
2.60
0.50
1.25
2.25
Ø0.630 (4 PL)
0.85
2.60
.25-20 UNC-2A (4 PL)
USA
EUR
JMK Inc 15 Caldwell Dr. Amherst, NH 03031 PH: 603 886-4100
email: info@jmkfilters.com
JMK Inc Glasgow G13 1DN Scotland UK PH: 44-(0) 7785310729 FX: 44-(0) 141 589 1884
FX: 603 886-4115
相关型号:
MM-0787-100B
The Mm-0787-100B filter is designed for use with large computer or motor installations where heavy current is drawn continuously.
JMK
MM-0787-60B
Operating Voltage = 250/480 V~, 50 / 60 Hz Operating Voltage = 125/208 V~, 50 - 400 Hz
JMK
MM-0787-80B
Operating Voltage = 250/480 V~, 50 / 60 Hz Operating Voltage = 125/208 V~, 50 - 400 Hz
JMK