HICM150G-S120125-C2U [HITRON]
5x3 inch Compact size;型号: | HICM150G-S120125-C2U |
厂家: | HITRON ELECTRONICS CORPORTION |
描述: | 5x3 inch Compact size |
文件: | 总2页 (文件大小:375K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
H HiTRON
Universal input AC-DC Medical and ITE application open frame
internal switching power supplies convection-cooled
150 Watts green power single output HICM150G series
Features
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
ꢀ
5x3 inch Compact size
No load power consumption <0.5 W
Very High Efficiency up to 94%
150 W Convection/200 W Forced-cooled
U-Bracket or Box format optional
Medical and ITE application
Class I and Class II construction
Specification
Input
General
Input Voltage
Input Frequency
Input Current
90-264VAC
Efficiency
Typical 94% (depending on model)
85KHz
47-63Hz
Switching Frequency
Dielectric Withstand
Circuit Topology
Transient Response
Typical 1.5A at 115VAC
Typical 0.8A at 230VAC
Typical 14.5A rms at 230VAC
Typical 0.92 at 230VAC
V-H connector or equivalent
IEC60601-1 and IEC60950-1
LLC circuit
Inrush Current
Power Factor
Output voltage returns in less than
0.01mS for a 25% load change
Available
Input Connector
Power Fail
Earth Leakage Current Less than 0.1mA
Remote ON/OFF
Power Density
Construction
Available
No-load Power
Less than 0.5W
6.9W / Cubic Inch
U-Bracket and Box format optional
Output
Output Connector
Line Regulation
Load Regulation
Total Regulation
Noise & Ripple
Adjustability
V-H connector or equivalent
Typical 0.1%
Environmental
Operating Temperature
(Refer to the derating chart)
Storage Temperature
Cooling
-20°C to +70°C derate from 100%
load at +50°C to 60% at +70°C
-25°C to +85°C
Typical ±1.5%
Typical ±3%
Typical 1% peak to peak
Available
Convection-cooled: 150W
Forced-cooled: 200W with 10CFM
10-95% RH, non-condensing
5-95% RH
Hold-up Time
Protection
Over Voltage
Over Load
20mS min. at 230VAC
Operating Humidity
Storage Humidity
Safety/EMC
Emissions (conducted)
Harmonic Current
Safety Standard
Built-in (Latch)
Typical set about 185-200% of
rating output wattage
Installed by NTC
CISPR EN55011 & EN55022 Class B
IEC61000-3-2
Over Temperature
IEC60601-1 Class I and Class II
IEC60950-1 Class I and Class II
Notes:
(1) All measurements are at nominal input, full load, and +25°C unless otherwise specified.
(2) Load regulation is measured at 115VAC or 230VAC in percentage to indicate the change in output voltage as the load varied from half load to full load (±%).
(3) The power supply is considered a component installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
(4) Due to requests in market and advances in technology, specifications subject to change without notice.
Edited on June 1, 2016
-1-
Output voltage & current rating chart
Single Output
V1 ★ @
Fan Output
Model No.
(Model no. for example
Typ.
Max.
(Forced-cooled)
Min.
Volt.
Typ.
Volt.
Please refer to note 1 & 2)
(Convection-cooled)
12.50A
12.50A
12.50A
12.50A
6.25A
HICM150G-S120125-C1U
HICM150G-S120125-C1B
HICM150G-S120125-C2U
HICM150G-S120125-C2B
HICM150G-S240625-C1B
HICM150G-S240625-C2U
HICM150G-S280536-C1B
HICM150G-S360417-C1B
HICM150G-S360417-C2U
HICM150G-S480314-C1U
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
12V
12V
12V
12V
24V
24V
28V
36V
36V
48V
48V
16.70A
16.70A
16.70A
16.70A
8.35A
8.35A
7.15A
5.56A
5.56A
4.17A
4.17A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
0.5A
12V
12V
12V
12V
12V
12V
12V
12V
12V
12V
12V
6.25A
5.36A
4.17A
4.17A
3.14A
HICM150G-S480314-C2B
3.14A
Symbol: ★ “OVP” built-in “@” Adjustable
Notes: (1) Please add suffix to model number to define IEC protection classes: add “-C1” for Class I version (with AC-GND), and “-C2” for Class II version (without AC GND).
Please add suffix to model number to define type: add “-B” for enclosure (metal box) version, and “-U” for U-Bracket version.
For example: HICM150G-S120125-C1B is for Class I and Metal Box version; HICM150G-S120125-C2U is for Class II and U-bracket version.
(2) Other output voltages are available. Please contact sales for details.
(3) 10CFM fan-cooling is required if the output wattage is 200Watt.
Mechanical Dimensions (Note: All dimensions are in mm[inch])
Derating Chart
Pin assignment
Assignment
AC-Line
Pin No. (Class I) Pin No. (Class II)
P1-L
P1-L
AC-Neutral
AC-Ground
V1
P1-N
P1-N
N/A
GND
P2-4,5,6
P2-1,2,3
P3-1
P2-4,5,6
P2-1,2,3
P3-1
DC COM
Power Fail
Remote ON/OFF P3-2
P3-2
RTN
P3-3
P4-1
P4-2
P3-3
FAN +
P4-1
FAN -
P4-2
Note: 10 CFM fan cooling is required if total output power is 200W.
Notes: (1)Remote ON/OFF: P3-2 & P3-3 must be shorted to switch on the output.
(2) Mating connector: P1: CVILUX CI5203S0000/P2: JST B6P-VH
Edited on June 1, 2016
-2-
相关型号:
©2020 ICPDF网 联系我们和版权申明