SPP40SP1120SN [EATON]

SurgePOD™ PRO UL Listed Type 1 surge protective devices;
SPP40SP1120SN
型号: SPP40SP1120SN
厂家: Eaton All Rights Reserved.    Eaton All Rights Reserved.
描述:

SurgePOD™ PRO UL Listed Type 1 surge protective devices

文件: 总4页 (文件大小:1378K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Effective April 2018  
Technical Data 10033  
Supersedes February 2016  
SurgePOD™ PRO UL Listed Type 1 surge  
protective devices  
Features:  
•ꢀ  
These SPDs are easily selected and installed on  
the loadside or lineside of the service entrance  
overcurrent protective device  
2011/65/EU  
•ꢀ  
Voltage specific models precisely match and  
protect electrical systems and equipment better  
than one-size-fits-all” SPDs  
•ꢀ  
•ꢀ  
•ꢀ  
•ꢀ  
Thermal disconnect technology eliminates the  
need for additional fusing  
Compact UV resistant NEMA® 4X enclosure for  
indoor or outdoor installation  
easyID™ LED status indicator provides surge  
protection status at a glance  
Two year warranty  
Specifications:  
Ratings  
•ꢀ  
See ratings and specifications tables on page 2  
Catalog symbols:  
Agency information  
UL® Listed Type 1 1449 4th Edition  
•ꢀ  
SPP40SP_  
•ꢀ  
•ꢀ  
•ꢀ  
CSA (120-480 V)  
Description:  
RoHS compliant  
Bussmann™ series SurgePOD™ PRO Type  
1 surge protective devices are suitable for  
installation on both the loadside or lineside of the  
service entrance overcurrent protective device.  
Catalog numbers  
SPP40SP1120SN  
SPP40SP2240PN  
Volts AC System type  
120  
240  
Single-phase  
Split-phase  
SurgePOD PRO SPDs are available in popular  
voltage and system specific versions to match  
common residential and light commercial electrical  
system and equipment requirements. They deliver  
superior surge protection using MOV thermal  
disconnect technology that eliminates the need for  
additional overcurrent protection.  
SPP40SP3240DLG 240  
SPP40SP3480DLG 480  
SPP40SP3208WYG 208  
SPP40SP3480WYG 480  
SPP40SP3600WYG 600  
3-phase Delta  
3-phase Wye  
Parallel connection to the electrical system permits  
the SurgePOD PRO SPD to be installed on panels  
of any amp rating.  
Technical Data  
SurgePOD™ PRO UL ListedType 1 surge protective devices  
Effective April 2018  
SurgePOD PRO ratings and specifications:  
Voltages and system types  
Max. Continuous  
Nominal system voltage  
(Vac)  
Operating Voltage AC  
Catalog number  
(MCOV) (VC)  
System type  
Connection points  
SPP40SP1120SN  
SPP40SP2240PN  
SPP40SP3240DLG  
SPP40SP3480DLG  
SPP40SP3208WYG  
SPP40SP3480WYG  
120  
120/240  
240  
480  
208  
150  
150  
320  
550  
150  
320  
Single-phase 2 wire  
Split-phase 3 wire  
Three-phase Delta 3 wire + G  
Three-phase Delta 3 wire + G  
Three-phase Wye 3 wire + G  
Three-phase Wye 3 wire + G  
2
3
4
4
4
4
480  
Specifications  
For all SurgePOD PRO units  
Values  
200 kA  
10 kA  
Short Circuit Current Rating (SCCR)  
Nominal In  
Maximum Imax  
Discharge current (8x20µs)  
40 kA  
Response time (ns) tA  
Frequency  
<25ns  
50/60 Hz  
Operating state/fault indication  
Conductor length/gauge  
Bi-color LED - green (good) / red (replace)  
18 inches, 10 AWG stranded tinned copper  
Mounting  
Chase nipple / bracket*  
Enclosure/flammability ratings  
Degree of protection (installed state)  
SPD install location  
NEMA 4X - UL 94-5VA  
IP20 (finger-safe)  
Indoor/outdoor  
Circuit location  
Lineside or loadside of service entrance overcurrent protective device  
UL Type 1 1449 4th Edition  
Standard  
Agency information  
UL Listed, CSA Certified**, RoHS compliant  
2 Years†  
Warranty  
Operating temperature range  
Maximum operating altitude  
-40°C to +65°C  
12000 ft.  
*
Customer-supplied bracket.  
** 600 V Wye version not CSA Certified.  
See Bussmann series SPD limited warranty statement (3A1502) for details at www.cooperbussmann.com/Surge.  
Voltage Protection Ratings (VPRs)  
Voltage Protection Ratings (VPRs)  
Nominal system voltage  
(Vac_  
Catalog number  
SPP40SP1120SN  
MCOV (VC) (Vac)  
L-N  
700  
700  
L-L  
L-G  
120  
150  
150  
320  
550  
150  
320  
420  
SPP40SP2240PN  
SPP40SP3240DLG  
SPP40SP3480DLG  
SPP40SP3208WYG  
SPP40SP3480WYG  
SPP40SP3600WYG*  
120V/240  
240  
1200  
2500  
3000  
1200  
2500  
2500  
1200  
1800  
700  
1200  
1500  
480  
208  
480  
600  
*
Not CSA Certified.  
Eaton.com/bussmannseries  
2
SurgePOD™ PRO UL ListedType 1 surge protective devices  
Technical Data 10033  
Effective April 2018  
Dimensions — in  
Wiring connections  
L (Black)  
1-1/16” Dia.  
1-11/16”  
Black  
N (White)  
3-3/8”  
White  
1-11/16”  
Single-phase  
120 V (L-N) 2 Wire  
2-1/16”  
4-1/8”  
2-1/16”  
Must be installed within 10 feet (3 m) of a bonded neutral-ground  
connection per IEEE C62.41-1991.  
Catalog number: SPP40SP1120SN  
3-3/16”  
4-1/16”  
L1 (Black)  
7/8”  
N (White)  
Black  
Black  
Mounting  
L2 (Black)  
SurgePOD PRO is a panel mount device. It may also be mounted  
using a customer supplied bracket or directly onto a female threaded  
conduit fitting.  
White  
Two-pole with Neutral (split-phase)  
120 V (L-N) / 240 V (L1-L2), single-phase (split) center tap  
For installations at or less than 10 feet (3 m) from the transformer.  
Catalog number: SPP40SP2240PN  
For NEMA 4X installation,  
install appropriate, customer-  
supplied gasket between  
SurgePOD™ PRO  
SPD and enclosure wall.  
L1 (Black)  
L2 (Black)  
Tighten locknut to  
Black  
20.3 lb-in (2.3N•m)  
Black  
Black  
L3 (Black)  
GND (Green)  
Green  
Wye + Ground  
208, 480 V (L-L) 3 wire Wye + Ground  
Catalog numbers: SPP40SP3208WYG, SPP40SP3480WYG,  
SPP40SP3600WYG  
L1 (Black)  
L2 (Black)  
Black  
L3 (Black)  
Black  
Black  
GND (Green)  
Green  
Delta + Ground  
240, 480 V (L-L) 3 wire Delta + Ground  
Catalog numbers: SPP40SP3240DLG, SPP40SP3480DLG  
Eaton.com/bussmannseries  
3
Technical Data 10033  
SurgePOD™ PRO UL ListedType 1 surge protective devices  
Effective April 2018  
easyID LED status indicator  
The easyID LED status indicator will illuminate when the unit is  
properly installed and the system or equipment being protected is  
energized. The following LED color/status indicates:  
GREEN LED = Good  
•ꢀ  
The circuit is energized and protected.  
RED LED = Replace  
•ꢀ  
The circuit is energized and unprotected.  
•ꢀ  
The unit needs replacing.  
LED is Out / Unlit:  
•ꢀ  
The circuit is most likely de-energized  
•ꢀ  
The units leads are disconnected  
•ꢀ  
The unit is damaged  
Authorized personnel should follow all  
prescribed lockout/tagout and safety  
procedures in troubleshooting the cause for  
the above conditions. Opening SurgePOD  
PRO enclosure will void UL listing and  
warranty.  
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are  
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the  
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit  
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once  
a product has been selected, it should be tested by the user in all possible applications.  
Eaton  
1000 Eaton Boulevard  
Cleveland, OH 44122  
Eaton.com  
Bussmann Division  
Eaton, Bussmann, SurgePOD and easyID are  
114 Old State Road  
valuable trademarks of Eaton in the U.S. and  
Ellisville, MO 63021  
other countries. You are not permitted to use  
United States  
the Eaton trademarks without prior written  
Eaton.com/bussmannseries  
consent of Eaton.  
Follow us on social media to get the  
latest product and support information.  
© 2018 Eaton  
All Rights Reserved  
Printed in USA  
NEMA is a registered trademark of the  
National Electrical Manufacturers Association.  
Publication No. 10033 — BU-SB13071  
April 2018  
UL is a registered trademark of the  
Underwriters Laboratories, Inc.  

相关型号:

SPP40SP2240PN

SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
COOPER

SPP40SP2240PN

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP3208WYG

SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
COOPER

SPP40SP3208WYG

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP3240DLG

SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
COOPER

SPP40SP3240DLG

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP3480DLG

SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
COOPER

SPP40SP3480DLG

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP3480WYG

SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
COOPER

SPP40SP3480WYG

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP3600WYG

SurgePOD™ PRO UL Listed Type 1 surge protective devices
EATON

SPP40SP4208WYNG

SURGEPOD PRO TYPE1 SPD FOR 208 W
ETC