LDC120-24P [BEL]

Extremely compact size;
LDC120-24P
型号: LDC120-24P
厂家: BEL FUSE INC.    BEL FUSE INC.
描述:

Extremely compact size

文件: 总4页 (文件大小:657K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
LDC120 Series is a single phase high performance ultra compact DIN  
Rail Power Supply with active PFC, ideal for many applications.  
Its compact size, high efficiency, excellent reliability together with easy  
installation makes it ideal for various industrial applications.  
LDC120 Series is Class I isolation device suitable for SELV and PELV  
circuitry and is designed to be mounted on DIN rail and installed inside  
a protective enclosure.  
High efficiency  
Extremely compact size  
Active PFC for optimal efficiency  
Overload 150%  
Up to 60°C operating temperature with no derating  
Constant Current or Hiccup mode limitation, user settable  
Wide range of output voltage  
Easy parallelable for power increase  
Includes models with internal ORing  
Only 35 mm width aluminum enclosure  
Industrial Control  
Communication  
Instrumentation Equipment  
2
LDC120 Series  
LDC120-24  
LDC120-24P  
LDC120-48  
LDC120-48P  
120 - 240 VAC (110 - 345 VDC)  
120 - 240 VAC (110 - 345 VDC)  
120 - 240 VAC (110 - 345 VDC)  
120 - 240 VAC (110 - 345 VDC)  
24 VDC  
24 VDC  
48 VDC  
48 VDC  
5 A  
5 A  
Includes internal ORing diode  
Includes internal ORing diode  
2.5 A  
2.5 A  
Technical parameters are typical, measured in laboratory environment at 25°C and 240 VAC / 50 Hz, at nominal values, after minimum  
5 minutes of operation.  
Rated, UL certified  
Operating  
120 240 VAC  
90 - 264 VAC  
Input AC Voltage Range  
Input DC Voltage Range  
Input Frequency Range  
Rated  
110 - 345 VDC  
47 - 63 Hz  
Vin = 120 VAC 1.4 A  
Vin = 240 VAC 0.7 A  
Input AC Current  
Input DC Current  
Vin = 110 VDC 1.4 A  
Vin = 345 VDC 0.5 A  
Power Factor Correction  
Inrush Peak Current  
Active  
> 0.9  
45 A  
Touch (Leakage) Current  
Internal Protection Fuse  
0.5 mA  
Not user replaceable  
3.15 AT  
It is strongly recommended to provide external surge  
arresters (SPD) according to local regulations.  
Fuse 4 AT or MCB 4 A C curve  
Recommended External Protection  
PARAMETER  
DESCRIPTION / CONDITION  
SPECIFICATION  
Output Power  
120 W  
LDC120-24 / LDC120-24P  
LDC120-48 / LDC120-48P  
LDC120-24 / LDC120-24P  
LDC120-48 / LDC120-48P  
LDC120-24 / LDC120-24P  
LDC120-48 / LDC120-48P  
LDC120-24 / LDC120-24P  
LDC120-48 / LDC120-48P  
24 VDC (11.5 - 29 VDC)  
Rated Voltage  
(Adjustable Voltage Range)  
48 VDC (23 - 56 VDC)  
5 A  
Continuous Current  
2.5 A  
7.5 A  
3.75 A  
15 A  
7.5 A  
Overload Limit (Constant Current Mode)  
Overload Limit (Hiccup mode) (max. 5 s)  
LDC120-24  
LDC120-24P  
LDC120-48  
LDC120-48P  
1%  
3%  
0.5%  
1.5%  
Load Regulation  
Ripple & Noise1  
Hold-up Time  
60 mVpp  
Vin = 120 VAC 20 ms  
Vin = 240 VAC 30 ms  
Overload, short circuit, with constant current  
Thermal protection  
Input undervoltage lockout  
Protections  
Output overvoltage  
LDC120-24 / LDC120-24P  
LDC120-48 / LDC120-48P  
33 VDC  
68 VDC  
Output Over Voltage Protection  
tech.support@psbel.com  
3
LDC120 Series  
DC OK - green LED  
OVERLOAD - red LED  
Status Signals  
DC OK - dry contact (NO, 24 VDC / 1 A)  
Possible for power or redundancy (with external ORing  
module)  
P (models) - include internal ORing circuit  
LDC120-24 / LDC120-48  
LDC120-24P / LDC120-48P  
LDC120-24 / LDC120-48  
LDC120-24P / LDC120-48P  
Parallel Connection2  
Efficiency  
> 90%  
> 89%  
< 13.5 W  
< 15 W  
Dissipated Power  
1
Ripple and Noise are measured with 20MHz bandwidth, probe terminated with a 0.1μF MKP parallel capacitor.  
Pay attention, set the current limitation mode jumper on C.C. mode when connecting more units in parallel.  
2
NOTE: Power rating, losses, efficiency, ripple, thermal behaviour and start-up may change outside of the nominal rated input range.  
Contact factory for details.  
UL certified up to 60°C  
Operating Temperature  
- 35° to + 70°C  
(Start-up type tested: - 35°C)3  
Storage Temperature  
Derating  
- 40° to + 80°C  
- 1.2 W / °C over 60°C  
5 - 95% RH  
Humidity  
Non condensing  
Life Time Expectancy  
At 25°C ambient, full load  
74640 h (8.5 years)  
Overvoltage Category  
Pollution Degree  
III (EN50178)  
2 (IEC60664-1)  
Protection Class  
Class I  
Input to Output  
Input to Ground  
Output to Ground  
UL508 (certified)  
EN60950 (reference)  
EN50178 (reference)  
EN55011 (CISPR11)  
EN55022 (CISPR22)  
EN61000-3-2  
EN61000-4-2  
EN61000-4-3  
EN61000-4-4  
EN61000-4-5  
4.2 kVDC  
2.2 kVDC  
0.75 kVDC  
Isolation Voltage  
Safety Standards & Approvals  
Class B  
Class B  
Class A  
Level 3  
Level 3  
Level 3  
Level 3  
Level 2  
Emission  
EMC Standards  
Immunity  
EN61000-4-11  
Protection Degree  
Vibration Sinusoidal  
EN60529  
IP20  
5-17.8 Hz: ±1.6 mm; 17.8-500 Hz:  
2 g 2 Hours / axis (X,Y,Z)  
IEC 60068-2-6  
30 g 6 ms, 20 g 11 ms;  
3 bumps / direction, 18 bumps total  
Shock  
IEC 60068-2-27  
3
Possible with load derating.  
Weight  
450 g  
Dimensions (W x H x D)  
Mounting Rail  
35 x 103 x 104 mm  
IEC 60715/H15/TH35-7.5(-15)  
2.5 mm²  
Connection Terminals  
Case Material  
Screw type pluggable (24 - 12 AWG)  
Aluminum  
North America  
+1 408 785 5200  
Asia-Pacific  
+86 755 298 85888  
Europe, Middle East  
+353 61 225 977  
© 2016 Bel Power Solutions & Protection  
BCD.00683_AB  
4
LDC120 Series  
AC/DC input  
1
2
3
4
5
6
7
DC output (load)  
Diagnostic Output (dry contact, NC output OK)  
Green LED: Output OK  
Red LED: Overload  
Output voltage adjustment  
Selectable limitation mode (Hiccup mode, C.C. mode)  
INPUT CONNECTION  
OUTPUT CONNECTION  
Single phase:  
L = Line  
N = Neutral  
+ = Positive DC  
- = Negative DC  
= Earth ground  
DC:  
Signaling:  
L = + Positive DC  
N = - Negative DC  
= Earth ground  
DC OK: dry contact  
NO  
COM  
Figure 1. Mechanical Drawing  
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems,  
equipment used in hazardous environments, or nuclear control systems.  
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the  
date manufactured. Specifications are subject to change without notice.  
tech.support@psbel.com  

相关型号:

LDC120-48

Extremely compact size
BEL

LDC120-48P

Extremely compact size
BEL

LDC1300

Electric Fuse, Time Delay Blow, 1300A, 600VAC, 600VDC, 200000A (IR), Inline/holder,
LITTELFUSE

LDC1312

2 通道、12 位、通用电感数字转换器
TI

LDC1312-Q1

2 通道、12 位、通用汽车类电感数字转换器
TI

LDC1312DNTR

2 通道、12 位、通用电感数字转换器 | DNT | 12 | -40 to 125
TI

LDC1312DNTT

2 通道、12 位、通用电感数字转换器 | DNT | 12 | -40 to 125
TI

LDC1312QDNTRQ1

2 通道、12 位、通用汽车类电感数字转换器 | DNT | 12 | -40 to 125
TI

LDC1312QDNTTQ1

2 通道、12 位、通用汽车类电感数字转换器 | DNT | 12 | -40 to 125
TI

LDC1314

4 通道、12 位、通用电感数字转换器
TI

LDC1314-Q1

4 通道、12 位、通用汽车类电感数字转换器
TI

LDC1314QRGHRQ1

4 通道、12 位、通用汽车类电感数字转换器 | RGH | 16 | -40 to 125
TI