ARTESYN LCM300
300 Watts Bulk Front End
Advanced Energy’s Artesyn LCM300 series provide for a very
wide range of AC-DC embedded power requirement. Featuring
high build quality with robust screw terminals, long life, and
typical full-load efficiency of greater than 91 percent, these units
are ideal for use in industrial and medical applications. They are
backed by a comprehensive set of industrial and medical safety
approvals and certificates. Variable-speed ‘Smart Fans’ draw
on software controls developed by Advanced Energy to match
fan speed to the unit’s cooling requirement and load current.
Slowing the fan not only saves power but also reduces wear,
thus extending its life.
AT A GLANCE
Total Power:
300 W
Input Voltage:
85 to 264 VAC
# of Outputs:
Single
SPECIAL FEATURES
Compliance
EMI Class B
EN61000 Immunity
ꢀRoHS 3
310 W output power (350 W at 45 °C
for 24 V and 36 V models)
Low cost
ꢀPMBUS
1.61” x 4.0” x 7.0”
7.1 W/inꢀ
SAFETY
Industrial/Medical safety
-40 °C to 70 °C with derating
ꢀOptional 5 V @ 2 A housekeeping
ꢀHigh efficiency: 91% @ 230 VAC
ꢀVariable speed “Smart Fans”
ꢀDSP controlled
UL62368-1
508/1598/1433
60601-1 Ed 3
CSA
TUV
62368-1
62368-1
60601-1
China CCC
ꢀConformal coat option
ꢀWide adjustment range
ꢀMargin programming
ꢀOR-ing FET
CB Scheme Report/Cert
* Note: LCM300 tested according to the medical standard IEC
60601-1-2 4th Edition.
ꢀPMBus compliant
©2021 Advanced Energy Industries, Inc.
LCM300
ELECTRICAL SPECIFICATIONS
Input
Input range
90 - 264 VAC (Operating)
115/230 VAC (Nominal)
TERMINAL BLOCK
Frequency
47 - 63 Hz, Nominal 50/60
Input fusing
Internal 8 A fuses, both lines fused
≤ 20 A peak, cold start at 25 °C
0.98 typical, meets EN61000-3-2
Meets IEC 61000-3-2 requirements
5 Arms max input current, at 90 VAC
20 ms minimum for main O/P, at full rated load
> 91% typical at full load / 230 VAC nominal
< 0.3 mA at 240 VAC
Inrush current
Power factor
Harmonics
Input current
Hold up time
Efficiency
Leakage current
ON/OFF power switch
Power line transient
Isolation
N/A
MOV directly after the fuse
Isolation: PRI-Chassis 2500 VDC Basic
PRI-SEC 4000 VAC Reinforced 2xMOPP
SEC-Chassis 500 VDC
LCM300Q Efꢀciency Without the 5 Vsb
92.00
90.00
88.00
86.00
84.00
82.00
80.00
78.00
76.00
100 Vac
230 Vac
25
50
75
100
Loading %
2
advancedenergy.com
LCM300
ELECTRICAL SPECIFICATIONS (CONTINUED)
Output
Output rating
See table 1
0.5%
90 - 264 VAC
90 - 264 VAC
Set point
Total regulation range
Main output 2%
5 Vsb 1%
Combined line/load/transient when measured
at output terminal
Rated load
310 W (360 W for current Q and U variants)
Derate linear to 50% from 50 °C to 70 °C
No loss of regulation
Minimum load
Main output @ 0.0 A
5 Vsb @ 0.0 A
Output noise (PARD)
1% max p-p
Main output
100 mV max p-p
5 Vsb output
Measured with a 0.1 μF Ceramic and 10 μF
Tantalum Capacitor on any output, 20 MHz
Output voltage overshoot
Transient response
No overshoot/undershoot outside the regulation
band during on or off cycle
< 300 μSec
50% load step @ 1 A/μs
Step load valid between 10% to 100% of output
rating
Recovery time to within 1% of set point at onset
of transient
Max units in parallel
Short circuit protection
Remote sense
Up to 10
Protected, no damage to occur
Bounce mode
Compensation up to 500 mV
Standard per safety requirements
Analog sharing control
Output isolation
Forced load sharing
Overload protection (OCP)
To within 10% of all shared outputs
105% to 125%
120% to 170%
Main output
5 Vsb output
Overvoltage protection (OVP)
125% to 145%
110% to 125%
12 V output
5 Vsb output
ENVIRONMENTAL SPECIFICATIONS
Operating temperature
Storage temperature
Humidity
-40 °C to +70 °C, linear derating to 50% from 50 °C to 70 °C
-40 °C to +85 °C
10 to 90%, non-condensing. Operating. Conformal coat option available
< 45 dBA, 80% load at 40 °C; Fan Off when unit is inhibited
Fan noise
Altitude
Operating - 16,405 feet (5000m)
Storage - 30,000 feet
Shock
MIL-STD-810F 516.5, Procedure I, VI. Storage
MIL-STD-810F 514.5, Cat. 4, 10. Storage
Vibration
advancedenergy.com
3
LCM300
ORDERING INFORMATION
Nominal
Output
Voltage Set
Point
Current
Output
Ripple
P/P (0-50 ˚C)
Max
Continuous
Power
Combined
Line/Load
Regulation
Model
Number*
Set Point
Tolerance
Adjustment
Range
Output
Min
Max
LCM300L
LCM300N
LCM300Q
LCM300U
LCM300W
12 V
15 V
24 V
36 V
48 V
12 V
15 V
24 V
36 V
48 V
0.5%
0.5%
0.5%
0.5%
0.5%
9.6 - 14.4 V
14.25 - 19.5 V
19.2 - 28.8 V
28.8 - 43.2 V
43.0 - 60.0 V
0 A
0 A
0 A
0 A
0 A
25.0 A
20.0 A
12.5 A
8.4 A
120 mV
150 mV
240 mV
240 mV
280 mV
310 W
310 W
310 W
310 W
310 W
2%
2%
2%
2%
2%
6.3 A
*Note: 14.5 A rating on LCM300Q-T and 9.7 A on LCM300U-T when max temp does not exceed 45C (Total Power = 350 W)
LCMXXXXY
-
A
-
B
-
C
-
###
Case Size
Input Termination
Acoustic Noise
Option Codes
Hardware Code
1-Phase input where XXXX =
300 = 1.61” x 4.0” x 7.0”, 300 W
Blank = Standard
Blank = No Options
Factory Assigned for
Modiefied Standards
T = Terminal Block
1 = Conformal Coat
4 = 5 V Standby
5 = Opt 1 + 4
Voltage Code Y =
Code
L
12
15
24
36
48
N
Q
U
W
PN 602-000180-0000
SCR-PP MC M4X0.7
W/E-T-W
INPUT TERMINAL BLOCK
LED (AC OK)
POS SK4
NEG SK5
LED (DC OK/FAIL)
Signal Output Signal Connectors (SK2)
SK2 Mating Connector: JST Part Number PHDR-20VS;
Contact Pins: JST Part Number SPHD-001T-P0.5
SK2 SIGNAL CONNECTOR-20WAY
LED INDICATORS
2 provided are clearly visible up to a 45 degree offset from vertical with office environment ambient lighting. The status
is reflected in the indicator color.
e DC_OK LED LED shall light green if the DC output is within specification, and should be off if the output falls out
of specification.
e AC_OK LED LED is green if the AC is within specification and off when out of specification. Note: With 5 V
standby, Green also indicates that PSU is in standby mode/output off.
CONTROL SIGNALS
AC_OK Open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
DC_OK Open collector 0.5 V maximum at 10 mA. Both emitter and collector access provided.
DC_OK will de-assert when output is loss due to OCP, OVP, OTP, or Fan Fault (for -N option).
PS_INHIBIT/ENABLE Signal 0.0 - 0.5 V contact closure, output OFF (output ON for LCM300U-T-4-401).
4
advancedenergy.com
LCM300
PIN ASSIGNMENT
Signals
Name Description
Pin Number(s)
+Vout
Power rail
SK4
SK5
GND
Power GND
Amps per pin
Signals
Name Description
Pin Number(s)
A2
EEPROM Address
1
2
3
4
5
6
7
8
-VPROG
A1
Return connection of external supply for Margin Programming
EEPROM Address
-Vsense
ISHARE
A0
Remote Sense Return
Load share voltage
EEPROM Address
SDA1
+VPROG
SCL1
+Vsense
5VSB
GND
Serial Data Signal (IꢁC)
Positive connection of external supply for Margin Programming
Serial Clock Signal (IꢁC)
9
Remote Sense Positive
5V standby
10
11
12
13
14
15
16
17
18
19
20
2 A
5V standby Return
2 A
5VSB
5V standby
N/A
G_DCOK_C
GPIOA6
Global DCOK Collector
EEPROM Write Protect
Global DCOK Emitter (GND)
Return Ground for output signal and IꢁC communication
Global ACOK Collector
G_DCOK_E
GND
G_ACOK_C
INH_EN
Turn Off Main Output
G_ACOK_E
Global ACOK Emitter (GND)
Note: Mating connector for SK2 is:
LANDWIN: PN 2050S2000 Housing and PN 2053T021V Contact
CIVILUX: PN CI0120SD000 Housing and PN CI01TD21PE0 Contact
advancedenergy.com
5
LCM300
MECHANICAL DRAWINGS
177,8 0,5
Weight: 1.76 lbs (0.8 Kg)
11,15 REF
MOUNTING LOCATIONS SCREW
PENETRATION DEPTH IS 3.0 mm MAX.
RECOMMENDED SCREW TORQUE:
M3.5 x 0.6P = 6 - 8kgf-cm
M4.0 x 0.7P = 8 - 10kgf-cm
PRODUCT LABEL
AIR FLOW DIRECTION
PN 602-000180-0000
SCR-PP MC M4X0.7
W/E-T-W
INPUT TERMINAL BLOCK
LED (AC OK)
POS SK4
NEG SK5
LED (DC OK/FAIL)
148,7 0,5
SK2 SIGNAL CONNECTOR-20WAY
S-M3-OZ1 (8 PLACES)
(2X) 29,1 0,5
(2X) 119,6 0,5
Airflow direction
6
advancedenergy.com
LCM300
Accessories
PIN 20
PIN 2
PIN 19
PIN 3
PIN 1
300 5 mm
Order kit part number 73-788-001 for control connector interface with .3m wires attached attached
PIN 19
PIN 20
PIN 3
PIN 1
PIN 2
Order kit part number 73-788-002 for control connector interface with unloaded housing and 20 pins
Miscellaneous Specifications
Burn-In
100% Burn-in at 45 °C, at 80 - 90 % load. Duration of burn-in determined by Quality Assurance Procedures.
MTBF
The power supply has a minimum MTBF of 300K hours using the Bell core 332, issue 6 specification @ 25 °C
and 40 °C, ambient, at full load. With the power supply installed in a system in a 25 °C ambient environment and
operating at full load, capacitor life shall be 5 years at 50 °C, minimum for ALL electrolytic capacitors contained
within this power supply. The power supply shall demonstrate a MTBF level of > 500,000 hours.
Quality Assurance
Full QAV testing shall be conducted in accordance with Artesyn Embedded Power Standards with reports
available upon request.
Warranty
Artesyn Embedded Power shall warrant the power supply to be free of defects in materials and workmanship for
a minimum period of three years from the date of shipment, when operated within specifications. The warranty
shall be fully transferable to the end owner of the equipment powered by the supply.
advancedenergy.com
7
ABOUT ADVANCED ENERGY
Advanced Energy (AE) has devoted more than three
decades to perfecting power for its global customers. AE
designs and manufactures highly engineered, precision
power conversion, measurement and control solutions for
mission-critical applications and processes.
Our products enable customer innovation in complex
applications for a wide range of industries including
semiconductor equipment, industrial, manufacturing,
telecommunications, data center computing, and medical.
With deep applications know-how and responsive service
and support across the globe, we build collaborative
partnerships to meet rapid technological developments,
propel growth for our customers, and innovate the future
of power.
For international contact information,
visit advancedenergy.com.
Specifications are subject to change without notice. Not responsible
for errors or omissions. ©2021 Advanced Energy Industries, Inc. All rights
reserved. Advanced Energy®, AE® and Artesyn™ are U.S. trademarks
of Advanced Energy Industries, Inc.
powersales@aei.com (Sales Support)
productsupport.ep@aei.com (Technical Support)
+1 888 412 7832
ENG-LCM300-235-01.07.15.21
相关型号:
©2020 ICPDF网 联系我们和版权申明