ECP225PS48 [XPPOWER]
150/225 W Convection/ Forcedcooled; 二百二十五分之一百五十W¯¯对流/强制?冷却![ECP225PS48](http://pdffile.icpdf.com/pdf1/p00194/img/icpdf/ECP225_1098723_icpdf.jpg)
型号: | ECP225PS48 |
厂家: | ![]() |
描述: | 150/225 W Convection/ Forcedcooled |
文件: | 总2页 (文件大小:410K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
225 Watts
ECP Series
xppower.com
•
•
•
•
•
•
•
Low 1” Profile with 2.5” x 5” Footprint
150/225 W Convection/ Forcedꢀcooled
High Efficiency ꢀ up to 95%
Medical & ITE Approvals
Builtꢀin Fan Supply
<0.5 W No Load Input Power
3 Year Warranty
Specification
Input
General
Efficiency
Isolation
• See table
Input Voltage
• 85-264 VAC, Derate from 100% at 90 VAC
to 90% at 85 VAC
• 47-63 Hz
• 2.2 A typical at 115 VAC, 1.1 A typical at
230 VAC
• 120 A max at 230 VAC, cold start at 25 °C
• >0.95 at full load
• 4000 VAC Input to Output
1500 VAC Input to Ground
1500 VAC Output to Ground
• Primary to Secondary: 2 MOPP
Primary to Earth: 1 MOPP
Secondary to Earth: 1 MOPP
• 12/18 W/in convection/forced-cooled,
• PFC: 70-130 KHz, PWM: 50-80 KHz
• >300 kHrs to MIL-HDBK-217F at 25 °C, GB
Input Frequency
Input Current
Protection Level
Inrush Current
Power Factor
3
Power Density
Switching Frequency
MTBF
Earth Leakage Current • <230 µA at 264 VAC, 60 Hz
No Load Input Power • <0.5 W
Input Protection
• Internal T3.15A/250VAC fitted in line and
neutral
Environmental
Operating Temperature • -20 °C to +70 °C derate from 100% load
at 50 °C to 50% load at 70 °C
Output
Cooling
• Convection cooled: 150 W
Forced cooled: 225 W with 10 CFM
Output Voltage
• See tables
Operating Humidity
Operating Altitude
Storage Temperature • -40 °C to +85 °C
• 5% to 90% RH, non condensing
• 5000 m
Output Voltage Trim
Initial Set Accuracy
Minimum Load
•
•
5%
1% at 50 % load
• No minimum load requirement
• 2 s max
Shock
• IEC68-2-27, 30 g, 11 ms half sine, 3 times
in each of 6 axes
Start Up Delay
Vibration
• IEC68-2-6, 10-500 Hz, 2 g 10 mins /
sweep. 60 mins for each of 3 axes
Start Up Rise Time
Hold Up Time
• 55 ms typical
• 10 ms minimum at full load and 115 VAC
20 ms typical at 150 W, 13 ms typical at
225 W
EMC & Safety
Emissions
• EN55022/11, Level B conducted &
Level A radiated
• EN61000-3-2 Class A
EN61000-3-2 Class C for load >145 W
• EN61000-3-3
• EN61000-4-2, 8 kV air, 4 kV contact,
Perf Criteria A
• EN61000-4-3, 3 V/m, Perf Criteria A
• EN61000-4-4, level 3, Perf Criteria A
• EN61000-4-5, installation class 3,
Perf Criteria A
Line Regulation
•
•
0.5% max
0.5% max
Load Regulation
Transient Response
Harmonic Currents
• 4% maximum deviation, recovering to less
than 1% within 500 µs for 25% step load
• 1% max pk-pk, 20 MHz bandwidth,
(see note 2)
Voltage Flicker
ESD Immunity
Ripple & Noise
Radiated Immunity
EFT/Burst
Surge
Overvoltage Protection • 110% - 140% of nominal voltage on main
output. Recycle mains to reset.
• 110-170%
Overload Protection
Short Circuit Protection • Trip and restart (hiccup)
Thermal Protection
Conducted Immunity
Dips & Interruptions
• EN61000-4-6, 3 V, Perf Criteria A
• EN55024, 30% 10 ms,
• Measured internally. Auto resetting.
• 0.02%/°C
Temperature
Coefficient
60%, 100 ms, 100%, 5000 ms
Perf Criteria A, A, B for high line,
A, B, B for low line at full load,
EN60601-1-2, 30% 500 ms, 60% 100 ms,
100% 10 ms, 100% 5000 ms,
Perf Criteria A, A, A, B for high line,
A, B, A, B for low line at full load
Fan Supply
• 12 V at 500 mA
Safety Approvals
• UL60950-1, IEC60950-1, EN60950-1,
ANSI/AAMI ES 60601-1, IEC60601-1,
EN60601-1
ECP225
Models and Ratings
Output Current
Convection-cooled Forced-cooled(1)
Ripple and Noise
pk-pk(2)
Output Voltage
Fan Output
Efficiency(3)
Model Number(4)
12.0 V
15.0 V
24.0 V
28.0 V
48.0 V
12.50 A
10.00 A
6.25 A
5.36 A
3.10 A
18.75 A
15.00 A
9.38 A
8.04 A
4.69 A
120 mV
150 mV
240 mV
280 mV
480 mV
12 V/0.5 A
12 V/0.5 A
12 V/0.5 A
12 V/0.5 A
12 V/0.5 A
93%
93%
94%
94%
94%
ECP225PS12
ECP225PS15
ECP225PS24
ECP225PS28
ECP225PS48
Notes
1. Requires 10 CFM.
2. Measured with 20 MHz bandwidth and 10 µF electrolytic capacitor in parallel
with 0.1 µF ceramic capacitor
3. Minimum average efficiencies measured at 25%, 50%, 75% & 100% of
225 W load and 230 VAC input.
4. 3” x 5” Footprint available for OEM quantities, add suffix ‘-3X5’to part eg.
ECP225PS24-3X5.
Mechanical Details
CN1 - Input Connector
Pin 1
Pin 2
Pin 3
Neutral
Not Fitted
Line
5.00 (127.0)
4.75 (120.6)
Mates with JST housing
VHR-3N and JST Series
SVH-21T-P1.1 crimp terminals
0.25 (6.35) Faston ground tab
VR
8
Mounting holes marked with
must be connected to safety earth
2.25
(57.1)
CN2 - Output Connector
CN2
CN3
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
-Vout
-Vout
-Vout
-Vout
+Vout
+Vout
+Vout
+Vout
2.50
(63.5)
3
1
1
CN1
2
1
Mounting Screw
Holes 4 Places
0.134 (Ø3.4 0.3)
Mates with JST housing
VHR-8N and JST Series
SVH-21T-P1.1 crimp terminals
0.06
(1.60)
0.83
(21.0)
1.00
(25.4)
CN3 - Fan Connector
Pin 1
Pin 2
Fan -
Fan +
Mates with Molex housing
22-01-1022 and 2759 crimp terminals
0.11
(2.80)
Notes
1. All dimensions shown in inches (mm).
Tolerance: 0.02 (0.5)
2. Weight: 0.51 lbs (230 g) approx.
Derating Curve
100
80
60
40
20
0
-20
-10
0
40
Ambient Temperature (ºC)
50
60
70
80
10
20
30
11-Feb-13
相关型号:
©2020 ICPDF网 联系我们和版权申明