1110560000 [WEIDMULLER]
Mini Coupler / Mini Conditioner;型号: | 1110560000 |
厂家: | WEIDMULLER |
描述: | Mini Coupler / Mini Conditioner |
文件: | 总58页 (文件大小:2581K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Analogue Signal Processing
156
Analogue Signal Processing
The problem
particularly important to avoid mutual
interference of multiple sensor circuits,
for example, ground loops in interlinked ꢀCurrent transformer
measurement circuits. The wide range of ꢀVoltage transformer
products includes all functions for
converting separation and monitoring
signals. The different designs in
The product program
contains the following functions:
The real world can be measured in many
ways, for example, via temperature,
humidity, air pressure and so forth.
The parameters of these different physical
qualities change continuously. Elements
that monitor statuses and changes in sta-
tuses of a given environment, must reflect
these continual changes.
ꢀThermocouple conditioners for
resistance thermometers
ꢀFrequency signal conditioner
connection with the respective functions ꢀPotentiometer conditioner
cover practically all applications in
industrial measurement technology.
With these new products, Weidmüller
offers the possibility of taking into account ꢀAD/DA converter
the demands of modern automation
technology with the inclusion of analogue
signals. These products guarantee an
elementary function between signals from
the field and the further processing
systems. The mechanical characteristics
of these products correspond to those of
the well-known Weidmüller products and
are part of a continuous, ongoing
concept. The signal conditioners can be
combined together with other Weidmüller
products.
ꢀAC signal conditioner
ꢀBridge measurement conditioner
ꢀLimit value monitoring modules
Within the framework of industrial moni-
toring tasks, the statuses of an environ-
ment are monitored by using sensors.
These sensors should provide signals that
enable connected evaluating and monitor-
ing installations to draw detailed conclu-
sions concerning the status of, for exam-
ple, a production process. The sensor sig-
nals trace the continuous changes in the
monitored range. The signals can be in
analogue or digital form; which means in
normal cases, an electrical voltage or cur-
rent value is produced that corresponds
proportionally to the monitored physical
quantities. Increasing automation with the
intention of achieving or maintaining cer-
tain predetermined statuses makes the
processing of analogue values increasingly
important. This is also true of fields
beyond those where this has been neces-
sary and standard for a long time, for
example, processing technology in the
chemical industry. Standard electrical
signal values are the norm within the
framework of this
These products are categorised according
to functionality as pure signal conversion,
2-way-isolation, 3-way-isolation and as
passive separation.
They have been electrically and
mechanically designed to ensure that only
a minimum of wiring and maintenance
costs are necessary.
processing technology.
Current values from 0...20
mA, 4...20 mA or voltage
values from 0...10 V have
been introduced as
sensor output values for
differing physical
quantities. Weidmüller has
taken account the need
for increasing automation
with the processing of
these analogue signals,
and offers a wide range
of products that are
designed for handling
sensor signals.
This means, units are
made available for
standard signals (0...20
mA, 4...20 mA, 0...10 V)
that generate output
signal values proportional
to the variable input
signals, and at the same
time enable the safe
separation of, for
example, sensor circuits
of an evaluation circuit.
This safe separation is
157
Analogue Signal Processing
2-way-isolation separates the signals galvanically and decouples the measurement
circuits. In so doing it eliminates potential differences caused by long cable lengths and
common reference points. Furthermore, the galvanic isolation offers protection against
destruction by overvoltage, and against inductive and capacitive interferences.
3-way-isolation also decouples the supply voltage from the input and output circuits,
and enables the function with only one operating voltage.
The passive isolator offers a further elementary advantage; it needs no additional volt-
age supply. The supply to the modules ensues via the input circuit and is the trans-
ferred to the output. This current loop supply is distinguished by very low power con-
sumption.
There are a large number of products available for measuring temperatures. RTD
PT100 signals, in 2-, 3- and 4-wire technology, are converted to standardised 0 – 20
mA, 4 – 20 mA and 0 – 10 V signals.
The modules which can be connected to commercially available thermocouples have
cold junction compensation as standard. Furthermore, the modules amplify and linea-
rize the voltage signals from the thermocouple. This guarantees an exact conditioning
of analogue signals by eliminating sources of interference and errors.
Frequency converters convert frequencies to standard analogue signals. This
enables controllers connected in series to directly process impulse trains when making
speed or rotational speed measurements.
It is inconceivable to think about automation without analogue-digital-analogue
converters. To bring together the aforementioned analogue form of describing the envi-
ronment and the customary digital processing, within the framework of process moni-
toring, it is necessary to convert analogue signals into digital signals. Weidmüller offers
modules for the following standard input and output signals: 0...20 mA, 4...20 mA and
0...10 V. 8-bit and 12-bit digital modules are available. All modules have an added input
for making instantaneous measurements.
Current monitoring modules enable the monitoring of current values up to 60 A in
alternating or direct voltages. Over range or under range values trip the switching out-
put. Modules with analogue outputs enable the continuous monitoring of currents via
connected controls.
Voltage monitoring modules can be used to monitor direct and alternating voltages.
Voltage fluctuations, resulting from switching operations or network overloads, can be
reliably recognised and reported via the adjustable threshold function.
Modules for monitoring of revolutions and torque enable the control of cyclic move-
ments on conveyor belts, ventilators and pumps. The output responds after a set
amount of time, should the expected impulse not be received. The reliable potential-
free relay contact, signalises the interference to the responsible component group.
158
Design Overview
Mini Coupler / Mini Conditioner
DK Mini Coupler / MCZ Mini Conditioner
ꢀExtensive range of electronic functions
in terminal format
ꢀPluggable cross-connections with
mini conditioners
ꢀMini couplers with screw-in
cross-connection combs
ꢀMini couplers with screw
connections
ꢀMini conditioners with tension
clamp connections
WAVESERIES
WAVEANALOG / WAVEANALOG PRO / WAVECONTROL
ꢀPluggable PCB for fast service when
the configuration is changed
ꢀPluggable cross-connection in base socket
housing to distribute the power supply,
marking (CC) in the block diagram on
the head plate
ꢀPluggable connections with optional
screw or tension clamp connection
RS profiles
Analog-/Digital-Converters
ꢀMounts onto TS 32 and TS 35 mounting rails
ꢀOpen, cost-saving design
ꢀVariable housing width
159
Selection Table of Functions
Function
Areas of application
Description
Versions
Page
DC signal conditioners
Signal conditioning, signal isolation,
suppression of mass loops
DC input/fixed functions
and configurable inputs and
outputs
MCZ
WAVEANALOG
WAVEANALOG PRO 185
164
174-184
Motor current limitation, pressure
alarm, direct disconnection of
DC input/limit value
monitoring
DK
MCZ
172
173
connected modules, safety function
PT100 signal conditioners
Temperature monitoring, noise rejec-
tion, electrical decoupling of visualiza-
tion devices, suppression of mass
loops, heating and cooling monitoring,
overheating protection of motors
RTD input/fixed functions
and configurable inputs and
outputs
MCZ
WAVEANALOG
WAVEANALOG PRO 189
165
186-188
Thermocouple conditioners
Frequency signal conditioners
Temperature monitoring, noise rejec-
tion, electrical decoupling of visualiza-
tion devices, suppression of mass
loops, heating and cooling monitoring,
overheating protection of motors
Thermo input/fixed functions
and configurable inputs and
outputs
WAVEANALOG
WAVEANALOG PRO 191
190
Flow rate measurements, frequency
converter monitoring, speed measure-
ments, pulse processing
Input/fixed functions and
configurable inputs and
outputs
DK
MCZ
167-168
166
AD/DA converters
Current monitoring
Conditioning of voltage and current
signals in 8-bit/12-bit digital form
8-bit AD/DA converter
12-bit AD/DA converter
RS
210-213
Motor current monitoring,
emergency lighting monitoring
AC input/measuring of
sinusoidal and non sinusoidal
signals up to 60A
DKI
WAVECONTROL
SMSI
172
196-199
200-203
Voltage monitoring
Under and overvoltage monitoring,
operating status indication
One and three-phase
overvoltage
SMSU
204-205
Motion and rotational
speed monitoring
Downtime monitoring, conveyor-drive
monitoring, monitoring of fans, pumps
or pistons
PNP/NPN or NAMUR
input/switching output
DKLW
SMS
169
206
Namur switching amplifier
Setpoint device
Switching amplifier
Namur input/switching output
EGV
207
208
Testing measuring distances, defined
input of analogue values
1 control input/+/-set value/
analogue output
EMA/SW24
160
Selection Table
Function
Input
Output
Galvanic Voltage supply
isolation
Setting
Module
width/mm type
Connection
Cat. No.
Page
0…20mA
0…20mA
yes
Without auxiliary pwr.
current loop supply
from input
Fixed
6
Tens. clamp 8411190000
164
DC/DC
0…20mA
0…20mA
0…20mA
0…20mA
0…20mA
0…20mA
yes
Without auxiliary pwr.
current loop supply
from input
Without auxiliary pwr.
current loop supply
from input
19.2…28.8Vdc/
Voltage supply of
both sides
Fixed
17.5
17.5
12.5
17.5
Screw/
tens. clamp 8444960000
(1-channel)
Screw/
tens. clamp 8463590000
(2-channel)
8444950000/ 174
yes
Fixed
8463580000/ 174
2-way
Fixed
Screw/
tens. clamp 8445080000
8445070000/ 176
0…20mA
0…20mA
0…20mA
0…20mA
0…20mA
4…20mA
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540190000
Screw/
tens. clamp 8447170000
Screw/
tens. clamp 8446990000
8540180000/ 178
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
8447160000/ 181
19.2…28.8Vdc/
Voltage supply of
both sides
Fixed
12.5
17.5
8446970000/ 176
0…20mA
0…20mA
0…20mA
4…20mA
4…20mA
0…10V
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540260000
Screw/
tens. clamp 8447200000
Screw/
tens. clamp 8447030000
8540250000/ 181
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
8447190000/ 181
19.2…28.8Vdc/
Voltage supply of
both sides
Fixed
12.5
17.5
8447020000/ 176
0…20mA
0…20mA
4…20mA
0…10V
0…10V
0…20mA
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540280000
Screw/
tens. clamp 8447230000
Screw/
tens. clamp 8444990000
8540270000/ 178
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
Fixed 12.5
8447220000/ 181
19.2…28.8Vdc/
Voltage supply of
output side
8444980000/ 175
4…20mA
4…20mA
4…20mA
0…20mA
0…20mA
4…20mA
yes
18…30Vdc
Fixed/10 kHz 17.5
Fixed/20 kHz 17.5
Screw/
tens. clamp 8540210000
Screw/
tens. clamp 8447260000
Screw/
tens. clamp 8445020000
8540200000/ 179
3-way
2-way
18…30Vdc
8447250000/ 182
19.2…28.8Vdc/
Voltage supply of
output side
Fixed
12.5
17.5
8445010000/ 175
4…20mA
4…20mA
4…20mA
4…20mA
4…20mA
0…10V
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540190000
Screw/
tens. clamp 8447170000
Screw/
tens. clamp 8445050000
8540180000/ 178
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
8447160000/ 182
19.2…28.8Vdc/
Voltage supply of
output side
Fixed
12.5
17.5
8445040000/ 175
4…20mA
4…20mA
0…10V
0…10V
0…10V
0…20mA
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540240000
Screw/
tens. clamp 8447290000
Screw/
tens. clamp 8447080000
8540230000/ 179
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
8447280000/ 182
19.2…28.8Vdc/
Voltage supply of
both sides
Fixed
12.5
17.5
8447050000/ 177
0…10V
0…10V
0…10V
0…20mA
0…20mA
4…20mA
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540320000
Screw/
tens. clamp 8447320000
Screw/
tens. clamp 8447110000
8540310000/ 180
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
8447310000/ 183
19.2…28.8V/
Voltage supply of
both sides
Fixed
12.5
17.5
8447100000/ 177
0…10V
0…10V
0…10V
4…20mA
4…20mA
0…10V
yes
18…30Vdc
Fixed/10 Hz
Screw/
tens. clamp 8540300000
Screw/
tens. clamp 8447350000
Screw/
tens. clamp 8447140000
8540290000/ 180
3-way
2-way
18…30Vdc
Fixed/20 kHz 17.5
Fixed 12.5
8447340000/ 183
19.2…28.8Vdc/
Voltage supply of
both sides
8447130000/ 177
161
Selection Table
Function
Input
Output
Galvanic Voltage supply
isolation
Setting
Module
width/mm type
Connection
Cat. No.
Page
0…10V
0…10V
0…10V
0…10V
yes
18…30Vdc
18…30Vdc
20…253Vdc
Fixed/10 Hz
17.5
Screw/
8540330000/ 180
tens. clamp 8540340000
Screw/ 8447370000/ 184
tens. clamp 8447380000
3-way
Fixed/20 kHz 17.5
Variable voltage Variable voltage yes
DIP switch
12.5
Screw/
8560740000/ 185
and current
and current
Potentiometer
tens. clamp 8560750000
(+/-20mV…+/-200V,
(-10V…+10V,
+/-0.1mA…+/-100mA) -20mA…+20mA)
PT100/
(4)…20mA
no
no
no
no
no
no
no
yes
19.2…28.8Vdc
19.2…28.8Vdc
DIP switch
12.5
12.5
6
Screw/
tens. clamp 8432220000
Screw/
tens. clamp 8432190000
Tens. clamp 8425720000
8432210000/ 186
PT100/
2-wire
PT100/
2-wire
PT100/
3-wire
PT100/
3-wire
PT100/0
4-wire
PT100/
4-wire
PT100/
2-/3-/4-conduct. 0…20mA
0…10V
DIP switch
Potentiometer
Fixed
8432180000/ 186
RTD/DC
4…20mA
0(4)…20mA
0…10V
current loop supply
in output
19.2…28.8Vdc
165
DIP switch
Potentiometer
DIP switch
Potentiometer
DIP switch
Potentiometer
DIP switch
Potentiometer
DIP switch
Potentiometer
12.5
12.5
12.5
12.5
17.5
Screw/
tens. clamp 8432160000
Screw/
tens. clamp 8432130000
Screw/
tens. clamp 8432280000
Screw/
tens. clamp 8432250000
8432150000/ 187
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
18…30Vdc
8432090000/ 187
(4)…20mA
0…10V
8432270000/ 188
8432240000/ 188
0…10V
Screw/
tens. clamp 8560710000
8560700000/ 189
Ni100
4…20mA
Potentiometer:
min. 0…100Ω
max. 0…100kΩ
R: 0…450Ω
K, J, T, E, N,
R, S, B
Thermo/DC
Thermo
K, J, T, E, N,
R, S, B
0…10V
no
19.2…28.8Vdc
18…30Vdc
DIP switch
12.5
17.5
Screw/
tens. clamp 8432310000
8432300000/ 190
0…20mA
4…20mA
0…10V
0…20mA
4…20mA
0(4)…20mA
Thermocouples
K, J, T, E, N,
R, S, B
0...50/100/500Hz
0…1/5/10/16kHz
0...50/100/500Hz
0…1/5/10/16kHz
0...50/100/500Hz
0...1/5/10/16kHz
0…20mA
yes
DIP switch
Potentiometer
Screw/
tens. clamp 8560730000
8560720000/ 191
no
no
no
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
DIP switch
DIP switch
DIP switch
6
6
6
Screw
Screw
Screw
Screw
8311870001
8311870001
8283810000
8258870000
168
168
168
Frequency/DC
0(4)…20mA
0…10V
0...1/5/10/16kHz
0...1/5/10/16kHz
0...1/5/10/16kHz
no
no
no
21.6…26.4Vdc
21.6…26.4Vdc
current loop supply
in input
DIP switch
DIP switch
DIP switch
6
6
6
167
166
167
0…20mA
4…20mA
Tens. clamp 8461480000
Screw 8081330000
4…20mA
0...1/5/10/16kHz
no
current loop supply
in input
DIP switch
6
Tens. clamp 8461490000
166
0…10V
0…10V
Variable,
programmable
0…20mA
0...1/5/10/16kHz
0...1/5/10/16kHz
Switching output
PNP
Switching output
PNP 2-channel
Switching output
PNP 2-channel
Switching output
PNP 2-channel
Switching output
PNP 2-channel
8-bit
8-bit
8-bit
8-bit
12-bit
12-bit
12-bit
12-bit
no
no
no
21.6…26.4Vdc
21.6…26.4Vdc
19.2…28.8Vdc
DIP switch
DIP switch
Fixed
6
6
12
Screw
Tens. clamp 8461470000
Screw
Screw
8242040000
167
166
170-
171
172
8248340000
8031320000
Limit value
monitoring
no
no
no
no
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
Potentiometer
Potentiometer
6
6
6
6
0…20mA
0…10V
0…10V
Tens. clamp 8227350000
Screw 8019640000
Tens. clamp 8260280000
173
172
173
DIP switch
Potentiometer
DIP switch
Potentiometer
Fixed
Fixed
Fixed
Fixed
Fixed
0…20mA
4…20mA
0…10V
no
no
no
no
no
no
no
no
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
70
70
70
70
70
70
70
70
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
1160561001
1168561001
1160361001
1122361001
1168461001
1169161001
1168361001
1168261001
210
210
210
210
212
212
212
212
AD convert.
0…20mA
4…20mA
0…10V
Fixed
Fixed
Fixed
162
Selection Table
Function
Input
Output
Galvanic Voltage supply
isolation
Setting
Module
width/mm type
Connection
Cat. No.
Page
8-bit
8-bit
8-bit
8-bit
12-bit
12-bit
12-bit
12-bit
0…1/5/10 Aac
0…1/5/10 Aac
0…20/40/60 Aac 1)
0…20/40/60 Aac 1)
0…1/5/10 Aac
0…1/5/10 Aac
0…1/5/10 Aac
0…1/5/10 Aac
0…5/10 Aac
0…20mA
4…20mA
0…10V
no
no
no
no
no
no
no
no
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
2-way
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
19.2…28.8Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
12…30Vdc
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP switch
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
DIP sw./P*
Fixed
70
70
70
70
70
70
70
70
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
6
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Tens. clamp 8516570000
Screw 8513340000
Tens. clamp 8526600000
Screw 8523400000
Tens. clamp 8523410000
Screw 8528650000
Tens. clamp 8528660000
Screw 8526610000
Tens. clamp 8526620000
Screw 8545830000
Tens. clamp 8545840000
Screw 8513330000
1165860000
1169260000
1160760000
1123360000
1166060000
1165960000
1166160000
1160860000
8516560000
211
211
211
211
213
213
213
213
196
196
196
196
197
197
197
197
198
198
198
198
199
199
DA convert.
0…20mA
4…20mA
0…10V
Current
monitoring
1)
1)
2)
2)
3)
3)
4)
4)
12…30Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
18…30Vdc
0…5/10 Aac
0…20/25/30 Aac 4)
0…20/25/30 Aac 4)
0…20/40/60 Aac 4)
0…20/40/60 Aac 4)
Tens. clamp 8526590000
Screw
0.1…2A
Switching output no
PNP
1…50mAdc
40…250mAdc
40…250mAdc
0.2…2.2Aac
1…5Aac
1…5Aac
1…5Aac
40...250mAdc
40...250mAdc
0.2...2.2Aac
1…5Aac
Opto-coupler
Opto-coupler
Opto-coupler
Opto-coupler
21.6…26.4Vuc
5…48Vdc
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
no
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
10…250Vdc
21.6…26.4Vuc
207…253Vac
18…27Vac
Op. point
Op. point
Op. point
Op. point
Fixed
Fixed
Fixed
Op. point
Op. point
Op. point
Fixed
Op. point
Op. point
Op. point
Op. point
Op. point
Op. point
Op. point
Op. point
Op. point
Potentiometer
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
Screw
1157160000
1156360000
1156460000
1157360000
1112160000
8026930000
1112060000
1156660000
1159960000
1156960000
1112260000
0555060000
0555160000
1156760000
1157660000
1157760000
1157860000
1160160000
1156560000
1178760000
1110560000
200
200
201
201
201
201
201
202
202
203
203
205
205
204
204
205
205
205
205
205
206
LED
NO 1-channel
NO 1-channel
NO 1-channel
NO 1-channel
CO 1-channel
CO 1-channel
CO 1-channel
CO 1-channel
CO 1-channel
CO 1-channel
NO 1-channel
NO 2-channel
NO/NC
Voltage
monitoring
1-24Vdc
1-230Vuc
18…24Vac
36…48Vac
83…110Vac
165…220Vac
200…260Vac
3 phase 165...230Vac
3 phase 165...230Vac
P. / N. switching
24Vdc
36…53Vac
83…121Vac
165…253Vac
200…299Vac
165…230Vac
165…230Vac
195.5…241.5Vac
Rotational-
motion and
r.p.m. monitoring
CO 1-channel
Namur switch Namur
amplifier Namur
Setpoint device 0…24V
NO 1-channel
PNP/NPN
10.5…+10.5V
no
no
yes
21.6…26.4Vdc
21.6…26.4Vdc
21.6…26.4Vdc
no
no
22.5
22.5
22.5
Screw
Screw
Screw
1120360000
1122460000
1172660000
207
207
208
Potentiometer
1) Switch output / 1 changeover contact
2) 0…10 V, 0 (4)…20 mA switchable
3) 4…20 mA / current loop supply
4) Switch output / 1 changeover contact
5) 0…10 V, 0 (4)…20 mA switchable
DIP switch./P* = DIP switch / Potentiometer
163
Passive Isolator
MCZ CCC 0…20 mA/0…20 mA
This module is a reasonably priced passive
separator for galvanically separating standard
0.4...20 mA signals.
It draws its power from the measurement signal
and requires no further auxiliary power.
The measurement signal is transmitted 1:1. The
module is distinguished by its low power con-
sumption as well as a response current <100 µA.
Block diagram
Working resistance diagram
UE (V)
IE = IA = 20 mA
15
3
100
500
RB (Ω)
Ordering data
Type
Cat. No.
for TS 35
MCZ CCC 0…20 mA/0…20 mA
without power supply
8411190000
Technical data
Input
0…20 mA (max. 15 V)
Response current
< 100 µA
Voltage drop
2.5…3 V (at 20 mA)
50 mA, 15 V
Max. overload capacity at input
Output
0…20 mA (max. 10 V)
Set time (T99)
Residual ripple
approx. 5 ms at 500 Ω working resistance impedance
< 10 mVeff
Chopper frequency
Transmission error
Temperature effect
approx. 200 kHz
< 0.1 % from end value, + 0.05 % from mean/100 Ω working resistance
< 50 ppm/K from measurement value for working resistance 0 Ω
Voltage strength
Input/output
510 Veff
EMC
EMVG
EN 50081-1
EN 50082-2
CE, UL, CSA
Approvals
Ambient temperature
- assembled without spacing
- assembled with 20 mm spacing
Storage temperature
Conductor
-25 °C…+40 °C
-25 °C…+50 °C
-40 °C …+85 °C
AWG 22…12
1.5 mm2
Conductor cross-section
Overall width
6 mm
Dimensions and accessories see
Page 305
164
RTD Thermocouple Conditioners
MCZ PT100/3 CLP
• for 2 and 3 wire sensors
0…100 °C
/ 0…120 °C / 0…150 °C / 0…200 °C / 0…300 °C
-50…+150 °C / -40…100 °C
The temperature module converts measurement
values from a PT 100 into analogue measure-
ment signals. The module supplies the sensor
with power. The module is distinguished by its
accuracy and linearity.
Block diagram
Type
Cat. No.
Ordering data
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
MCZ PT100/3 CLP
0…100 °C
8425720000
8483680000
8604420000
8473010000
8473020000
8473000000
8604430000
for TS 35
0…120 °C
0…150 °C
0…200 °C
0…300 °C
-50…+150 °C
-40…100 °C
Technical data
Input
PT 100 (according to IEC 751)
3-wire / 2-wire*
each 50 Ω
Connection
Max. wire resistance
Leadwire resistance effect
Supply current
max. 0.006 °C/Ω
0.8 mA
4…20 mA**
Output
750 Ω at 24 V
Load
max:30V/min:9V+20mA x RL
max: 1.5 V at 100 Hz
10 ms
Supply voltage
Residual ripple of supply voltage
Set time
Type. 0.2 % max. 0.5 % v. FSR
<0.1 % v. FSR
Accuracy
Linearity
max. 250 ppm/°C
Temperature coefficient
yes
Open circuit recognition
EMVG
EMC
EN 50081-1
EN 50082-2
CE, UL, CSA
Approvals
0 °C…+50 °C
-20 °C…+85 °C
AWG 22…12
1.5 mm2
Ambient temperature
Storage temperature
Conductor
Conductor cross-section
Overall width
6 mm
** current loop supplied
Page 305
*
Putting a bridge between Pins 4 and 5
Dimensions and accessories see
165
Frequency Signal Conditioners
MCZ VFC
MCZ CFC
MCZ CFC
• Tension clamp connection
• LED-Display
0…10 V
0…20 mA
4…20 mA CLP
• Adjustable frequency output
The option of reading-in the analogue signals
from the field via counter inputs of the control is
made possible by converting the analogue sig-
nals in to frequencies. It is recommended that
twisted and shielded 2-wire cables are used.
Block diagram/settings
MCZ VFZ 0…10 V and MCZ CFC 0…20 mA
1
2
0
1
0
0
3
0
0
1
0
4
0
0
0
1
DIP switch
0…16 kHz
0…8 kHz
0…4 kHz
0…1 kHz
1
0
0
0
MCZ CFC 4…20 mA CLP
1
2
0
1
0
0
3
0
0
1
0
4
0
0
0
1
DIP switch
3.2…16 kHz
1.6…8 kHz
0.8…4 kHz
0.2…1 kHz
1
0
0
0
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
for TS 35
W
MCZ VFC
8461470000
MCZ CFC
8461480000
MCZ CFC
8461490000
Technical data
Input ranges
0…10 V
0…20 mA
4…20 mA LP*
50 mA
Overload limits, input
Input resistance
Voltage drop, input
Output
30 V
50 mA
100 kΩ
50 Ω
1 V at 20 mA
5.8…6.4 at 20 mA
Output frequency, end value
Frequency adjustment
Readjustment range
Output level
1 kHz, 4 kHz, 8 kHz, 16 kHz
DIL switch
1 kHz, 4 kHz, 8 kHz, 16 kHz
DIL switch
1 kHz, 4 kHz, 8 kHz, 16 kHz
DIL switch
10 %, internal
10 %, internal
10 %, internal
PNP, Ub- 0.7 V
max. 20 mA
PNP, Ub- 0.7 V
max. 20 mA
PNP, Ub- 0.7 V
max. 20 mA
Output current
Display
LED, pulsing
LED, pulsing
LED, pulsing
Supply voltage
24 Vdc 10 %
14 mA, w/o load
200 mA
24 Vdc 10 %
14 mA w/o load
200 mA
24 Vdc 20 %
Power consumption
Making current limit
Polarisation protection
14 mA w/o load
yes
yes
yes
Accuracy
0.2 % v. FSR
0.2 % v. FSR
0.15 % v. FSR
< 250 ppm/°C
Temperature coefficient
< 250 ppm/°C
< 250 ppm/°C
Coordination of insulation according to EN 50178
Voltage strength input/output
Rated voltage
1 kVdc
1 kVdc
100 V
100 V
150 V
Rated surge voltage
1.5 kV
1.5 kV
2.5 kV
Overvoltage category
III
III
III
Voltage strength I/O to mounting rail
Operating temperature
4 kVeff/ 1 min
0 °C…+50 °C
-25 °C…+85 °C
6 mm
4 kVeff/ 1 min
0 °C…+50 °C
-25 °C…+85 °C
6 mm
4 kVeff/ 1 min
0 °C…+50 °C
-25 °C…+85 °C
6 mm
Storage temperature
Overall width
Conductor cross-section
1.5 mm2
1.5 mm2
1.5 mm2
Dimensions and accessories see
Page 305
Page 305
Page 305
*
without DC/DC converter
input supply vie current loop
166
Frequency Signal Conditioners
DKA U/f
DKA I/f
DKA I/f*
• Screw connection
• LED-Display
• Adjustable frequency output
For EMC reasons, frequency processing mod-
ules must be used in conjunction with shielded
cables. This measure prevents interference of
analogue and frequency signals by other signal
cables and vice versa.
Block diagram/settings
DKA U/f and DKA I/f
1
2
0
1
0
0
3
0
0
1
0
4
0
0
0
1
DIP switch
0…16 kHz
0…8 kHz
0…4 kHz
0…1 kHz
1
0
0
0
Ordering data
for TS 32
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Y
for TS 35
W
with combi foot TS 32/TS 35
Technical data
DKA U/f
0…10 V
8242040000
DKA I/f
8258870000
DKA I/f *
4…20 mA
50 mA
8081330000
Input ranges
0…20 mA
Overload limits, input
Input resistance
Voltage drop, input
Output
100 V
50 mA
100 kΩ
50 Ω
max. 320 Ω at 20 mA
1 V at 20 mA
max. 6.4 V at 20 mA
Output frequency, end value
Frequency adjustment
Readjustment range
Output level
1 kHz, 4 kHz, 8 kHz, 16 kHz
DIL switch
1 kHz, 4 kHz, 8 kHz, 16 kHz
DIL switch
5 kHz (1…5 kHz)
10 %, internal
PNP, Ub- 0.7 V
max. 20 mA
10 %, internal
PNP, Ub- 0.8 V
max. 20 mA
Ub- 3 V
Output current
max. 20 mA
Display
LED, pulsing
LED, pulsing
Decoupling diode
present
present
present
Supply voltage
24 Vdc 10 %
14 mA, w/o load
200 mA
24 Vdc 10 %
14 mA w/o load
200 mA
19.2…28.8 Vdc
<13 mA w/o load
Power consumption
Making current limit
Polarisation protection
yes
yes
yes
Accuracy
0.2 % v. FSR
<250 ppm/°C
0.2 % v. FSR
<250 ppm/°C
0.15 % v. FSR
<250 ppm/°C 2
Coordination of insulation to DIN VDE 0160, Draft 11/94
Voltage strength input/output
Rated voltage
1 kVdc
1 kVdc
4 kVeff
150 V
Rated surge voltage
2.5 kV
Overvoltage category
III
Voltage strength to mounting rail
Operating temperature
4 kVeff
4 kVeff
4 kVeff
0 °C…+50 °C
-25 °C…+60 °C
6 mm
0 °C…+50 °C
-25 °C…+60 °C
6 mm
0 °C…+50 °C
-25 °C…+60 °C
6 mm
Storage temperature
Overall width
Conductor cross-section
0.5…4 mm2
0.5…4 mm2
0.5…4 mm2
Accessories
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
8268870000
End plate
AP DK5
Page 305
8268870000
AP DK5
Page 305
8268870000
AP DK5
Page 305
Dimensions and accessories see
*
without DC/DC converter
Input current loop supplied
167
Frequency Signal Conditioners
DKA f/U
DKA f/I
• Screw connection
• LED-Display
• Adjustable frequency output
• multiplex capable
For EMC reasons, frequency processing mod-
ules must be used in conjunction with shielded
cables. This measure prevents interference of
analogue and frequency signals by other signal
cables and vice versa.
Block diagram/settings
1
0
2
0
0
1
1
1
0
1
0
X
X
3
0
0
0
0
1
1
1
1
X
X
4
X
X
X
X
X
X
X
X
0
1
DIP switch
0…50 Hz
0…100 Hz
0…500 Hz
0…1 kHz
0…5 kHz
0…10 kHz
0…16 kHz
1
0
1
0
1
1
0
X
X
Customer specific
0…20 mA / 0…10 V
4…20 mA / 2…10 V
Ordering data
for TS 32
Type
Cat. No.
Type
Cat. No.
Y
for TS 35
W
with combi foot TS 32/TS 35
Technical data
DKA f/U
8283810001
DKA f/I
8311870001
Input ranges
0…50/100/500 Hz
0…1/5/10/16 kHz
0…50/100/500 Hz
0…1/5/10/16 kHz
Overload limits, input
Input resistance
Voltage drop, input
Output
10 kΩ
10 kΩ
0/2…10 V
DIL switch
0/4…20 mA
DIL switch
Output frequency, end value
Frequency adjustment
Readjustment range
Output level
Output current
Display
Decoupling diode
Supply voltage
24 Vdc 10 %
32 mA + ILoad
24 Vdc 10 %
32 mA + ILoad
Power consumption
Making current limit
Polarisation protection
yes
yes
Accuracy
0.5 % (8-bit resolution)
0.5 % (8-bit resolution)
Coordination of insulation to DIN VDE 0160, Draft 11/94
Voltage strength input/output
Rated voltage
2.5 kV
2.5 kV
Rated surge voltage
Overvoltage category
Voltage strength to mounting rail
Operating temperature
4 kVeff
4 kVeff
0 °C…+50 °C
-25 °C…+60 °C
6 mm
0 °C…+50 °C
-25 °C…+60 °C
6 mm
Storage temperature
Overall width
Conductor cross-section
0.5…4 mm2
0.5…4 mm2
Dimensions and accessories see
Page 305
Page 305
168
Monitoring Revolutions
DK LW
If only one revolution limit is to be evaluated, the
potentiometer for fmax must be set to end stop
or the potentiometer for fmin to left stop. Then
only the other is in each case active for setting
the limit value.
Block diagram/settings
Ordering data
Type
Cat. No.
for TS 32
for TS 35
Y
W
DK LW
8258680000
Technical data
Input
Initiators, NPN or PNP
Number of inputs
Input frequency
Range selection
Fine adjustment
Input nominal level
Overload limits
Switching threshold
Pulse duration
1
10 - 6250 U/min.
3 switchable revolutions ranges: 10-130, 100-1300, 1000-7800 r.p.m.
2 potentiometers for upper/lower revs limit
24 Vdc = High, O V = Low
30 Vdc
High >18 V, Low <7 V
>0.5 ms
Input current
approx. 3.5 mA (24 V)
yes
Reverse polarity protection
Output
Optional PNP or NPN
Function
Output active, if f within set revs limit
Output level
Output current
Decoupling diode
Status LED
Ub- 1.8 V
20 mA max.
yes
green LED
no
Short-circuit proof
Operating voltage
24 V –10 % + 20 %
Power consumption
Reverse polarity protection
Galvanic isolation
<10 mA, w/o load, without initiator
yes
no
Voltage strength to mounting rail
Operating temperature
Storage temperature
Overall width
4 kVeff
0…+50 °C
-40…+60 °C
12 mm
0.5…4 mm2
Conductor cross-section
Insulation stripping length
Others
7 mm
Initiator power supply via module possible
Accessories
Type
Cat. No.
End plate
AP DKT4
Page 278
0687560000
Dimensions and accessories see
169
Preprocessing Logic
DK PL
•Screw connection
•logic function and time function
combined
•individually programmable
(further functions on request)
Block diagram
Ordering data
for TS 32
Type
Cat. No.
Y
W
on request
DK PL
for TS 35
8248340000*
Technical data
Logical function
Number of inputs
Input nominal level
Overload limits
Programmable, see note
5
24 Vdc = High, 0 V = Low
30 Vdc
Switching threshold
Pulse duration
High >18 V, Low <7 V
>1 ms
Input current
approx. 1.5 mA per input (24 V)
Output
PNP
Output level
Ub- 1 V
20 mA max.
no
Output current
Decoupling diode
Status LED
green LED
no
Short-circuit proof
Operating voltage
24 V 20 %
<10 mA
yes
Power consumption
Reverse polarity protection
Galvanic isolation
no
Voltage strength to mounting rail
4 kVeff
Operating temperature
Storage temperature
0 °C…+50 °C
-40 °C…+60 °C
Overall width
12 mm
0.5…4 mm2
Conductor cross-section
Insulation stripping length
7 mm
Accessories
Type
Cat. No.
End plate
AD DKT4
0687560000
8248340002
Ordering example: RS FLIP-FLOP
Dimensions see
Page 278
*
(not programmed - function next page)
170
Remark:
The module is programmed according to customers specifications.
Up to 5 inputs can be linked with various logic and timer functions,
e.g.: AND, OR, EXOR, NAND, NOR, EXNOR, delay elements, etc.
The output is either low or high active.
824834 0006 DKPL
Input 1: FOUT = FIN
824834 0001 DKPL
824834 0003 DKPL - Frequency divider
Inputs 1- 5 determine the divider factor
A = (E1 OR E2) AND (E3 OR E4) AND E5
Input 2: FOUT = FIN 10
State
Input
3
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
Output
Input 1 = divider factor 1: FOUT = FIN
Input 2 = divider factor 2: FOUT = FIN
1
2
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
4
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
2
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
6
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
1
Input 5 = divider factor 5: FOUT = FIN 5; FIN max. = 12 kHz
Input
Output
2
Input
Output
6
3
6
1
2
3
4
5
fout = fin
4
1
2
3
4
5
fout = fin
fout = fin / 10
5
fout = fin / 2
fout = fin / 50
6
fout = fin / 3
fout = fin / 100
7
fout = fin / 4
fout = fin / 1000
8
fout = fin / 5
Note: A new divider factor can only be
used if the operating voltage is switched
9
Note: An new divider factor can only be
used if operating voltage is switched off.
fin max. = 12 kHz
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
off.
fin max. = 3 kHz
Input
Input
Output
Output
824834 0004 DKPL
824834 007 DKPL
Input
Input 1: Signal A of an incremental generator
Input 2: Signal B 90 is shifted
Input 3: Enable High Active
Output
1
L
2
L
L
3
X
X
X
X
4
X
X
X
X
5
X
X
X
X
Out
No function
f = 1 Hz
f = 10 Hz
f = 1 Hz
Input 4: Output signal inverts High Active
Input 5: No function
H
L H
H H
Output: For each slope of signal A or B, the output is set to
20 - 30 Us.
L -> 0 V or connection open
H -> +24 …30 Vdc
(I.e.: FOUT = 4xFIN
)
FIN max. 1 kHz
X -> no effect on output function, L or H
Connection
Description
Signal A 90 ° leading Fmax = 1 kHz
Signal B 90 ° following Fmax = 1 kHz
Output is released
Input
1
2
3
4
5
6
A
824834 0008 DKPL
B
Output
Enable
Invert
Input
Output
Output signal invert
1
H
L
2
H
H
No function
H
L
fout = 4 x fA/B (max. 4 kHz)
Input
824834 0002 DKPL
824834 0010 DKPL
Output
Inputs 1 and 2 have the function of a RS FLIP-FLOP
Inputs 3, 4 and 5 have no function
RS FLIP-FLOP with superior S - input (connection 2)
Input connections 3, 4 and 5 must have 0 V or remain open!
Input
Output
6
Connection 1 Logic
R-Input
Connection 2
S-Input
Logic
Connection 6 Logic
Output
2
0
0
1
1
1
0
1
0
1
Nofunction
0 (is stored)
0 V or open
L
0 V or open
L
previous
state
is stored
No change of stored state
No change of stored state
1 (is stored)
+24 Vdc
H
L
0 V or open
+24 Vdc
L
H
H
0 V
L
Inputs 3,
4 and 5 no
function
No change of stored state
0 V or open
+24 Vdc
+24 Vdc
+24 Vdc
H
H
H
+24 Vdc
Outp.
Input
824834 0005 DKPL
824834 0501 DKPL
Output
Length of input signal between 80 and 100 ms.
Length of output signal 100 ms, only 2 pulses,
Relation pulse-interruption 1:1.
The module allows the input frequency at connection 1
(0...max. 50 kHz) to be divided with 2 fixed divider factors.
Depending on connection 2, the output frequency is transmit-
ted from output connection 6.
The positive slope of the input signal has to be analysed. Only
input E1 is used.
Connections 3, 4 and 5 have no function.
Connect. 2 Logic
Factor
Inp. frequency
Connection 1
0…30 kHz
Outp. frequency
Connection 2
0…400 Hz
0 V or open
24 Vdc
L
75
27
H
0…10.8 kHz
0…400 Hz
171
Threshold Monitoring
DKSC 0-10 V
DKSC 0-20 mA
DKI 2A
Current sensor
• Screw connection
• Mounts onto on mounting rail
• Wide spectrum of functions
• In part, individually adjustable
Block diagram/settings
S1
on
S2
on
off
X
DIP switch
10…100 mV
30 mV…1 V
300 mV…10 V
on
off
Ordering data
for TS 32
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Y
W
DKI 2A
DKI 2A
8017400000
8017410000
for TS 35
with combi foot TS 32/TS 35
Technical data
DKSC 0-10 V
8019640000
DKSC 0-20 mA 8031320000
Input signal
0…10 V
0(4)…20 mA
50 Ω
0.1…2 A
125 mV at 2 A
no
Input resistance
60 kΩ
Voltage drop, input
Cut-off frequeny
1 V
100 Hz
100 Hz
Switchable input range
Switching point settings
DIL switch for 3 ranges
2 threshold Uth 1 and Uth 2
with 2 front potentiometers
each 1 %
2 threshold Uth 1 and Uth 2
with 2 front potentiometers
each 1 %
Fixed:ON >90 mA
OFF <50 mA
Hysteresis
Output
double switch output
per PNP, Ub- 1.2 V
50 mA
double switch output
per PNP, Ub- 1.2 V
50 mA
single switch output
PNP, Ub-0.1 V
20 mA
Output level
Output current
Function
Uin <Uth1: output 1 active
Uin >Uth2: output 2 active
no
Iin <Ith1: output 1 active
Iin >Ith2: output 2 active
no
Status LED
green LED
18…30 Vdc
approx. 10 mA
no
Operating voltage
24 Vdc 20 %
approx. 15 mA
no
24 Vdc 20 %
approx. 15 mA
no
Power consumption
Galvanic isolation
Voltage strength to mounting rail
4 kVeff
4 kVeff
4 kVeff
Operating temperature
Storage temperature
Overall width
0 °C…+50 °C
-25 °C…+60 °C
6 mm
0 °C…+50 °C
-25 °C…+60 °C
6 mm
-25 °C…+50 °C
-40 °C…+85 ° C
6 mm
Conductor cross-section
0.5…4 mm2
0.5…4 mm2
0.5…4 mm2
EMC resistance
Burst acc. to EN 61000-4-4
Input/outputs
Power supply
Test severity 4, self restoring
Test severity 4, self restoring
Test severity 4
ESD acc. to EN 61000-4-2
Contact discharge
Air discharge
Test severity 3
Accessories
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
0687560000
End plate
AP DK5
8268870000
AP DK5
8268870000
AP DKT4
Dimensions see
172
Page 278
Page 278
Page 278
Threshold Monitoring
MCZ SC 0…10 Vdc
MCZ SC 0…20 mA
The Setpoint Controller allows cost effective units
to be built for monitoring analogue signals. An
upper and lower limit value, which covers the en-
tire signal range, can be set by the user via
2 potentiometers. The respective statuses of the
upper and lower limit value are indicated at the 2
digital outputs (upper limit value under/over flow;
lower limit value under/over flow).
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
for TS 35
MCZ SC 24 V/0…10V
8260280000
MCZ SC 24 V/0…20 mA
8227350000
Technical data
Voltage supply
Supply voltage
Supply current
24 Vdc 20 %
15 mA
24 Vdc 20 %
15 mA
Input
Input voltage
0…10 V
0.5…20 mA
50 Ω
Input resistance
Voltage drop at full scale
Max. input current
Cut-off frequeny
60 kΩ
1 V
40 mA
100 Hz
100 Hz
Transmission behaviour
S1
on
on
off
S2
on
off
x
Temperature coefficient Tk
500 ppm max.
Temperature coefficient Tk 250 ppm max.
Threshold voltage ranges of Uth
10…100 mV
0.03…1 V
0.3…10 V
250 ppm max.
250 ppm max.
Setting of switching threshold
Hysteresis of switching threshold
Function of output 1
via 2 potentiometers (12 turns)
1 % of the end value
via 2 potentiometers (12 turns)
1 % of the end value
active High for UInput < Uth1 (set via P1)
active High for UInput > Uth2 (set via P2)
active High for IInput < Ith1 (set via P1)
active High for IInput > Ith2 (set via P2)
Function of output 2
Response time
< 250 µs (switch threshold at 90% of the max. input signal;
< 250 µs (switch threshold at 90% of the max. input signal;
RL ≤ 1 kΩ)
RL ≤ 1 kΩ)
Output
2 channel switching PNP
max. 50 mA
2 channel switching PNP
max. 50 mA
Output current per output
Voltage drop at output transistor
< 1.2 V at 50 mA
< 1.2 V at 50 mA
Insulation coordination/safe separation to EN 50178
Separation input / output
none
none
Dielectric strength I/O to mounting rail
4 kVeff / 1 min
4 kVeff / 1 min
Ambient temperature
Storage temperature
Conductor
0 °C…+50 °C
-25 °C…+60 °C
AWG 22…12
1.5 mm2
0 °C…+50 °C
-25 °C…+60 °C
AWG 22…12
1.5 mm2
Conductor cross-section
Approvals
CE, UL, CSA
6 mm
CE, UL, CSA
6 mm
Overall width
Dimensions and accessories see
Page 305
Page 305
173
Passive Isolator DC/DC
CCC LP (1 channel)
CCC LP (2 channel)
WAVEANALOG DC/DC
0(4) ... 20 mA / 0(4) ... 20 mA
0(4) ... 20 mA / 0(4) ... 20 mA
ꢀ input loop powered
ꢀ galvanic isolation
ꢀ 1-, 2-channel versions
ꢀ low power consumption
ꢀ safe separation
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection 1 channel
Tension clamp connection 1 channel
Screw connection 2 channel
Tension clamp connection 2 channel
Input/output
WAS5 CCC LP
WAZ5 CCC LP
8444950000
8444960000
WAS5 CCC LP
WAZ5 CCC LP
8463580000
8463590000
0(4) ... 20 mA / 0(4) ... 20 mA
0(4) ... 20 mA / 0(4) ... 20 mA
Technical data* (per channel)
Input signal
0 ... 20 mA (4 ... 20 mA)
0 ... 20 mA (4 ... 20 mA)
Input voltage max.
Input current max
Operating current
Voltage drop
18 V
18 V
50 mA
< 100 µA
50 mA
< 100 µA
approx. 3 V at R = 0 Ω
approx. 3 V at R = 0 Ω
L
L
I
in
= 20 mA
I = 20 mA
in
approx. 13 V at R = 500 Ω
approx. 13 V at R = 500 Ω
L
L
at I = 20 mA
in
at I = 20 mA
in
Output signal
0 ... 20 mA (4 ... 20 mA)
≤ 500 Ω
0 ... 20 mA (4 ... 20 mA)
≤ 500 Ω
Load resistance
Accuracy at Tu=23 °C
Influence of load resistance
< 0.1% of FS
< 0.1% of FS
< 0.1% from measurement value
per 100 Ω load resistance
50 ppm / K of FS
< 0.1% from measurement value
per 100 Ω load resistance
50 ppm / K of FS
Temperature coefficient
Set time
4.5 ms at 500 Ω working resistance
4.5 ms at 500 Ω working resistance
Residual ripple
< 20 mV
< 20 mV
eff
eff
Chopper frequency
approx. 170 kHz
approx. 170 kHz
General
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
-25 °C ... +70 °C
-40 °C ... +80 °C
92.4 / 112.5 / 17.5
CE, UL, CSA, GL
-25 °C ... +70 °C
-40 °C ... +80 °C
92.4 / 112.5 / 17.5
CE, UL, CSA, GL
Coordination of insulation according to EN 50178, 04/98 (safe separation)
Rated voltage
300 V
300 V
Rated surge voltage
6 kV
6 kV
Overvoltage category
III
III
Contamination class
2
2
Clearance and creepage distance
Isolation voltage, voltage strength
Input/output, channel / channel
Input/output to mounting rail
Standards/specifications
EMC standards
≥ 5.5 mm
≥ 5.5 mm
4 kV / 1 s
eff
4 kV / 1 s
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
EN 50178 (safe separation)
EN 50081, EN 50082,
EN 55011
EN 50178 (safe separation)
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308
174
DC/DC-Signal Conditioners
CCC DC
4 ... 20 mA / 4 ... 20 mA
CCC DC
4 ... 20 mA / 0 ... 20 mA
CVC DC
4 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC
ꢀvoltage supply on output side
ꢀ2-way-isolation
ꢀanalogue signal conditioning
ꢀgalvanic isolation between
input/output signal
ꢀInput loop powered
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS4 CCC DC 8444980000
WAZ4 CCC DC 8444990000
4 ... 20 mA / 4...20 mA
WAS4 CCC DC 8445010000
WAZ4 CCC DC 8445020000
4 ... 20 mA / 0 ... 20 mA
WAS4 CVC DC 8445040000
WAZ4 CVC DC 8445050000
4 ... 20 mA / 0 ... 10V
Technical data*
Input signal
4 ... 20 mA
4 ... 20 mA
4 ... 20 mA
7 V
Input voltage max.
Input current max
Output signal
7 V
7 V
25 mA
25 mA
25 mA
4 ... 20 mA
0 ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≤ 500 Ω
≥ 1 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2% of FS
0.2% of FS
0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 20 ms)
≥ 15 Hz (typ. 20 Hz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
Power consumption
< 32 mA at I = 20 mA
out
< 32 mA at I = 20 mA
out
< 20 mA at I = 10 mA
out
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
≤ 2 A
≤ 2 A
≤ 2 A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
2
Clearance and creepage distance
Isolation voltage, voltage strength
Input/output to mounting rail
≥ 3 mm
≥ 3 mm
≥ 3 mm
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308
Page 298 + 308
175
DC/DC-Signal Conditioners
CCC DC
0 ... 20 mA / 0 ... 20 mA
CCC DC
0 ... 20 mA / 4 ... 20 mA
CVC DC
0 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC
ꢀvoltage supply on both sides
ꢀ2-way-isolation
ꢀanalogue signal conditioning
ꢀgalvanic isolation between
input/output signal
ꢀcross-connectable voltage supply
via cross-connectorss
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS4 CCC DC 8445070000
WAZ4 CCC DC 8445080000
0 ... 20 mA / 0 ... 20 mA
WAS4 CCC DC 8446970000
WAZ4 CCC DC 8446990000
0 ... 20 mA / 4 ... 20 mA
WAS4 CVC DC 8447020000
WAZ4 CVC DC 8447030000
0 ... 20 mA / 0 ... 10 V
Technical data*
Input signal
0 ... 20 mA
0 ... 20 mA
0 ... 20 mA
Input current max
Input resistance
25 mA
25 mA
25 mA
50 Ω
50 Ω
50 Ω
Output signal
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≤ 500 Ω
≥ 1 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2% of FS
0.2% of FS
0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 16 ms)
≥ 15 Hz (typ. 25 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 16 ms)
≥ 15 Hz (typ. 25 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 16 ms)
≥ 15 Hz (typ. 25 Hz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
Power consumption input
Power consumption output
Current carrying capacity of cross-connection
Operating temperature
< 11 mA at I = 20 mA
< 11 mA at I = 20 mA
< 11 mA at I = 20 mA
in
in
in
< 32 mA at I = 20 mA
out
< 32 mA at I = 20 mA
out
< 20 mA at I = 10 V
out
≤ 2 A
≤ 2 A
≤ 2 A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
Storage temperature
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
2
Clearance and creepage distance
Isolation voltage, voltage strength
Input/output to mounting rail
≥ 3 mm
≥ 3 mm
≥ 3 mm
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
Page 298 + 308
*TU = 23 °C single module
176
DC/DC Signal Conditioners
VCC DC
0 ... 10 V / 0 ... 20 mA
VCC DC
0 ... 10 V / 4 ... 20 mA
VVC DC
0 ... 10 V / 0 ... 10 V
WAVEANALOG DC/DC
ꢀvoltage supply on both sides
ꢀ2-way-isolation
ꢀanalogue signal conditioning
ꢀgalvanic isolation between
input/output signal
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS4 VCC DC 8447050000
WAZ4 VCC DC 8447080000
0 ... 10 V / 0 ... 20 mA
WAS4 VCC DC 8447100000
WAZ4 VCC DC 8447110000
0 ... 10 V / 4 ... 20 mA
WAS4 VVC DC 8447130000
WAZ4 VVC DC 8447140000
0 ... 10 V / 0 ... 10 V
Technical data*
Input signal
0 ... 10 V
0 ... 10 V
0 ... 10 V
Input voltage max.
Input resistance
15 V
15 V
15 V
500 kΩ
500 kΩ
500 kΩ
Output signal
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≤ 500 Ω
≥ 1 kΩ
Accuracy at Tu=23°C
Temperature coefficient
Response time
0.2% of FS
0.2% of FS
0.2% of FS
≤ 250 ppm / K of FS
≤ 30 ms (typ. 25 ms)
≥ 13 Hz (typ. 17 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 25 ms)
≥ 13 Hz (typ. 17 Hz)
≤ 250 ppm / K of FS
≤ 30 ms (typ. 25 ms)
≥ 13 Hz (typ. 17 Hz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
(19.2 ... 28.8 Vdc)
Power consumption input
Power consumption output
Current carrying capacity of cross-connection
Operating temperature
< 11 mA at U = 10 V
< 11 mA at U = 10 V
< 11 mA at U = 10 V
in
in
in
< 32 mA at I = 20 mA
out
< 32 mA at I = 20 mA
out
< 20 mA at I = 10 mA
out
≤ 2 A
≤ 2 A
≤ 2 A
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
0 °C ... +55 °C (mounted)
-20 °C ... +85 °C
92.4 / 112.5 / 12.5
CE, UL, CSA
Storage temperature
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
2
Clearance and creepage distance
Isolation voltage, voltage strength
Input/output to mounting rail
≥ 3 mm
≥ 3 mm
≥ 3 mm
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308
Page 298 + 308
177
W
NE
DC/DC Signal Conditioners
CCC
0 ... 20 mA / 0 ... 20 mA
CCC
0 ... 20 mA / 4 ... 20 mA
CVC
0 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC
ꢀ3-way-isolation
ꢀanalogue signal conditioning
ꢀindication LED
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Ordering data
WAS5 CCC
WAZ5 CCC
8540180000* WAS5 CCC
8540190000* WAZ5 CCC
8540250000
8540260000
WAS5 CVC
WAZ5 CVC
8540270000
8540280000
Screw connection
Tension clamp connection
Input/output
0 ... 20 mA / 0 ... 20 mA
0 ... 20 mA / 4 ... 20 mA
0 ... 20 mA / 0 ... 10 V
Technical data**
Input signal
0 ... 20 mA
25 mA
0 ... 20 mA
25 mA
0 ... 20 mA
25 mA
Input current max
Input resistance
≤ 110 Ω
0 ... 20 mA
≤ 600 Ω
0.2%
≤ 110 Ω
4 ... 20 mA
≤ 600 Ω
0.2%
≤ 110 Ω
0 ... 10 V
≥ 1 kΩ
Output signal
Load resistance
0.2%
Accuracy at Tu=23 °C
Temperature coefficient
Response time
250 ppm / K
≤ 45 ms
10 Hz
250 ppm / K
≤ 45 ms
10 Hz
250 ppm / K
≤ 45 ms
10 Hz
Cut-off frequeny (-3 dB)
General
24 Vdc 25%
24 Vdc 25%
24 Vdc 25%
Voltage supply
(18 Vdc ... 24 Vdc ... 30 Vdc)
(18 Vdc ... 24 Vdc ... 30 Vdc)
(18 Vdc ... 24 Vdc ... 30 Vdc)
< 1.5 W at I = 20 mA
out
< 1.5 W at I = 20 mA
out
< 1.3 W at I = 5 mA
out
Power consumption
≤ 2 A
≤ 2 A
≤ 2 A
Current carrying capacity of cross-connection
Operating temperature
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
Storage temperature
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
2
2
2
Contamination class
≥ 3 mm
≥ 3 mm
≥ 3 mm
Clearance and creepage distance
Coupling capacity
1 nF
1 nF
1 nF
Input / output to supply
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
EN 50178
EN 50178
EN 50178
Standards/specifications
EMC standards
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Page 298 + 308
Page 298 + 308
Page 298 + 308
Dimensions and accessories see
** TU = 23 °C single module
* Input/output 4 ... 20 mA/4 ... 20 mA possible
178
NEW
DC/DC Signal Conditioners
CCC
4 ... 20 mA / 0 ... 20 mA
CVC
4 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC
ꢀ3-way-isolation
ꢀanalogue signal conditioning
ꢀindication LED
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 CCC
8540200000
8540210000
WAS5 CVC
8540230000
8540240000
WAZ5 CCC
WAZ5 CVC
4 ... 20 mA / 0 ... 20 mA
4 ... 20 mA / 0 ... 10 V
Technical data
Input signal
4 ... 20 mA
25 mA
4 ... 20 mA
25 mA
Input current max
Input resistance
≤ 110 Ω
0 ... 20 mA
≤ 600 Ω
0.2%
≤ 110 Ω
0 ... 10 V
≥ 1 kΩ
Output signal
Load resistance
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2%
250 ppm / K
≤ 45 ms
10 Hz
250 ppm / K
≤ 45 ms
10 Hz
Cut-off frequeny (-3 dB)
General*
Voltage supply
24 Vdc 25%
24 Vdc 25%
(18 Vdc ... 24 Vdc ... 30 Vdc)
(18 Vdc ... 24 Vdc ... 30 Vdc)
Power consumption
< 1.5 W at I = 20 mA
out
< 1.3 W at I = 5 mA
out
Current carrying capacity of cross-connection
Operating temperature
≤ 2 A
≤ 2 A
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
Storage temperature
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308
179
W
NE
DC/DC Signal Conditioners
VCC
0 ... 10 V / 0 ... 20 mA
VCC
0 ... 10 V / 4 ... 20 mA
VVC
0 ... 10 V / 0 ... 10 V
WAVEANALOG DC/DC
ꢀ3-way-isolation
ꢀanalogue signal conditioning
ꢀindication LED
ꢀcross-connectable voltage
supply via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 VCC
WAZ5 VCC
8540310000
8540320000
WAS5 VCC
WAZ5 VCC
8540290000
8540300000
WAS5 VVC
WAZ5 VVC
8540330000
8540340000
0 ... 10 V / 0 ... 20 mA
0 ... 10 V / 4 ... 20 mA
0 ... 10 V / 0 ... 10 V
Technical data*
Input signal
0 ... 10 V
15 V
0 ... 10 V
15 V
0 ... 10 V
15 V
Input voltage max.
Input resistance
typ. 100 kΩ
0 ... 20 mA
≤ 600 Ω
0.2%
typ. 100 kΩ
4 ... 20 mA
≤ 600 Ω
0.2%
typ. 100 kΩ
0 ... 10 V
≥ 1 kΩ
Output signal
Load resistance
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2%
250 ppm / K
≤ 45 ms
10 Hz
250 ppm / K
≤ 45 ms
10 Hz
250 ppm / K
≤ 45 ms
10 Hz
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 25%
24 Vdc 25%
24 Vdc 25%)
(18 Vdc ... 24 Vdc ... 30 Vdc)
(18 Vdc ... 24 Vdc ... 30 Vdc)
(18 Vdc ... 24 Vdc ... 30 Vdc)
Power consumption
< 1.5 W at I = 20 mA
out
< 1.5 W at I = 20 mA
out
< 1.3 W at I = 5 mA
out
Current carrying capacity of cross-connection
Operating temperature
≤ 2 A
≤ 2 A
≤ 2 A
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
0 °C ... +55 °C
when mounted horizontally
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
Storage temperature
Dimensions L / H / W mm
Approvals
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
Page 298 + 308
*TU = 23 °C single module
180
DC/DC Signal Conditioners
CCC HF
0 ... 20 mA / 0 ... 20 mA
CCC HF
0 ... 20 mA / 4 ... 20 mA
CVC HF
0 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC 20 kHz
ꢀ3-way-isolation
ꢀtransmission frequency 20 kHz
ꢀanalogue signal conditioning
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 CCC HF 8447160000* WAS5 CCC HF 8447190000
WAZ5 CCC HF 8447170000* WAZ5 CCC HF 8447200000
WAS5 CVC HF 8447220000
WAZ5 CVC HF 8447230000
0 ... 20 mA / 0 ... 10 V
0 ... 20 mA / 0 ... 20 mA
0 ... 20 mA / 4 ... 20 mA
Technical data**
Input signal
0 ... 20 mA
0 ... 20 mA
0 ... 20 mA
Input current max
Input resistance
50 mA
50 mA
50 mA
50 Ω
50 Ω
50 Ω
Output signal
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≤ 500 Ω
≥ 2 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Response time
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 25% (18 ... 30 Vdc)
24 Vdc 25% (18 ... 30 Vdc)
24 Vdc 25% (18 ... 30 Vdc)
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
< 1.5 W at I = 20 mA
out
< 1.5 W at I = 20 mA
out
< 1.3 W at I = 5 mA
out
≤ 2 A
≤ 2 A
≤ 2 A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
Page 298 + 308
**TU = 23 °C single module
* Input/output 4 ... 20 mA/4 ... 20 mA possible
181
DC/DC Signal Conditioners
CCC HF
4 ... 20 mA / 0 ... 20 mA
CVC HF
4 ... 20 mA / 0 ... 10 V
WAVEANALOG DC/DC 20 kHz
ꢀ3-way-isolation
ꢀtransmission frequency 20 kHz
ꢀanalogue signal conditioning
ꢀcross-connectable voltage supply
via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 CCC HF
WAZ5 CCC HF
4 ... 20 mA / 0 ... 20 mA
8447250000
8447260000
WAS5 CVC HF
WAZ5 CVC HF
4 ... 20 mA / 0 ... 10 V
8447280000
8447290000
Technical data*
Input signal
4 ... 20 mA
4 ... 20 mA
Input current max
Input resistance
50 mA
50 mA
50 Ω
50 Ω
Output signal
0 ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≥ 2 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Response time
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
< 0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 25% (18 ... 30 Vdc)
24 Vdc 25% (18 ... 30 Vdc)
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
< 1.5 W at I = 20 mA
out
< 1.3 W at I = 5 mA
out
≤ 2 A
≤ 2 A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
*TU = 23 °C single module
182
DC/DC Signal Conditioners
VCC HF
0 ... 10 V / 0 ... 20 mA
VCC HF
0 ... 10 V / 4 ... 20 mA
WAVEANALOG DC/DC 20 kHz
ꢀ3-way-isolation
ꢀtransmission frequency 20 kHz
ꢀanalogue signal conditioning
ꢀcross-connectable voltage
supply via cross-connectors
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 VCC HF
WAZ5 VCC HF
0 ... 10 V / 0 ... 20 mA
8447310000
8447320000
WAS5 VCC HF
WAZ5 VCC HF
0 ... 10 V / 4 ... 20 mA
8447340000
8447350000
Technical data*
Input signal
0 ... 10 V
0 ... 10 V
Input voltage max.
Input resistance
15 V
15 V
500 kΩ
500 kΩ
Output signal
0 ... 20 mA
4 ... 20 mA
Load resistance
≤ 500 Ω
≤ 500 Ω
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2% of FS
0.2% of FS
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
Cut-off frequeny (-3 dB)
General
Voltage supply
24 Vdc 25% (18 ... 30 Vdc)
24 Vdc 25% (18 ... 30 Vdc)
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
< 1.5 W at I = 20 mA
out
< 1.5 W at I = 20 mA
out
≤ 2 A
≤ 2 A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082
EN 55011
Dimensions and accessories see
*TU = 23 °C single module
Page 298 + 308
Page 298 + 308
183
W
NE
DC/DC Signal Conditioners
VVC HF
0 ... 10 V / 0 ... 10 V
VVC HF
-10 ... +10 V / -10 ... +10 V
WAVEANALOG DC/DC 20 kHz
ꢀ3-way-isolation
ꢀtransmission frequency 20 kHz
ꢀanalogue signal conditioning
ꢀcross-connectable voltage
supply via cross-connectors
Approvals:
Approvals:
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 VVC HF
WAZ5 VVC HF
0 ... 10 V / 0 ... 10 V
8447370000
8447380000
WAS5 VVC HF
WAZ5 VVC HF
10 V / 10V
8561610000
8587000000
Technical data*
Input signal
0 ... 10 V
-10 … + 10 V
15 V
Input voltage max.
Input resistance
15 V
500 kΩ
500 kΩ
Output signal
0 ... 10 V
-10 … + 10 V
≥ 2 kΩ
Load resistance
≥ 2 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Response time
0.2% of FS
0.2% of measurement range
≤ 250 ppm / K of measurement range
≤ 40 µs (typ. 30 µs)
≤ 250 ppm / K of FS
≤ 40 µs (typ. 30 µs)
≥ 15 kHz (typ. 20 kHz)
Cut-off frequeny (-3 dB)
≥ 15 kHz (typ. 20 kHz)
General
Voltage supply
24 Vdc 25% (18 ... 30 Vdc)
24 Vdc 25% (18 ... 30 Vdc)
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Dimensions L / H / W mm
Approvals
< 1.3 W at I = 5 mA
out
< 1.3 W at I = 5 mA
out
≤ 2 A
≤ 2 A
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, UL, CSA
0 °C ... +55 °C
-20 °C ... +85 °C
92.4 / 112.5 / 17.5
CE, cUL
Coordination of insulation according to EN 50178, 04/98
Rated voltage
300 V
4 kV
III
300 V
4 kV
III
Rated surge voltage
Overvoltage category
Contamination class
2
2
Clearance and creepage distance
Coupling capacity
≥ 3 mm
≥ 3 mm
Input / output to supply
1 nF
1 nF
Isolation voltage, voltage strength
Input/output to mounting rail
4 kV / 1 min
eff
4 kV / 1 min
eff
Standards/specifications
EMC standards
EN 50178
EN 50178
EN 50081, EN 50082,
EN 55011
EN 50081, EN 50082,
EN 55011
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
*TU = 23 °C single module
184
W
NE
DC/DC Signal Conditioners (Configurable)
Adjustment help WAVETOOL
PRO DC/DC
WAVEANALOG PRO DC/DC
The service tool enables quick and uncompli-
cated configuration of WAVEANALOG PRO.
Download from Internet:
ꢀuniversally adjustable via DIP switch
ꢀadjustment help via Internet
ꢀ3-way-isolation
ꢀvoltage supply from 20 - 230 V ac/dc
ꢀlow power loss
ꢀadjustable transmission frequency
ꢀindication LED
http://www.weidmueller.de
→ Products → Downloads (see page 192)
Switch position/setting options
Switch
Input
S1
S2
Input range
0 … 60 mV
0 … 100 mV
0 … 150 mV
0 … 300 mV
0 … 500 mV
0 … 1 V
1
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
2
3
4
1
2
3
4
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Approvals:
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Block diagram
ꢁ
ꢁ
ꢁ
0 … 5 V
ꢁ
ꢁ
0 … 10 V
0 … 100 V
0 … ~0.3 mA
0 … 1 mA
0 … 5 mA
0 … 10 mA
0 … 20 mA
0 … 50 mA
0 … 20 mA*
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Ordering data
Type
Cat. No.
ꢁ
ꢁ
Screw connection
WAS4 PRO DC/DC
WAZ4 PRO DC/DC
configurable
8560740000
8560750000
Tension clamp connection
Input/output
*Offset conversion not calibrated
Technical data*
Input (adjustable)
Voltage uni-/bipolar adjustable
Voltage calibrated ranges
Switch S2
4
20 mV ... 200 V
calibrated ranges
ꢁ
0 … 60 mV, 0 … 100 mV, 0 … 150 mV, 0 … 300 mV,
0 … 500 mV, 0 … 1V, 0 … 5V, 0 … 10 V, 0 … 100 V
Span pot. activated: input range x 0.33 ... x 3.30
Current uni-/bipolar adjustable
Current calibrated ranges
0.1 mA ... 100 mA
0 … 0.3 mA, 0 … 1 mA, 0 … 5 mA, 0 … 16 mA,
0 … 20 mA, 0 … 50 mA
Switch
S1
Output
S3
Input resistance
Output range
0 … 10 V
2 … 10 V
5
ꢁ
ꢁ
ꢁ
6
7
1
ꢁ
ꢁ
ꢁ
ꢁ
2
ꢁ
ꢁ
ꢁ
ꢁ
at current input range < 5 mA / > 5 mA
at voltage input
approx. 100 Ω / approx. 5 Ω
approx. 1 MΩ
Input capacity
0 … 5 V
ꢁ
ꢁ
at current input
approx. 1 nF
1 … 5 V
Voltage input range < 500 mV / > 500 mV
Overload capacity
approx. 1 nF / approx. 500 pF
0 … 20 mA
4 … 20 mA
ꢁ
ꢁ
at current input range < 5 mA / > 5 mA
Voltage input range < 500 mV / > 500 mV
Output (adjustable)
< 75 mA / < 300 mA
max. < 20 mA / < 3 mA continuous current
Offset
S1
9
S2
5
Voltage uni-/bipolar adjustable
Voltage calibrated ranges
Current uni-/bipolar adjustable
Current calibrated ranges
Offset
0 … 10 V
(in % of output voltage)
8
ꢁ
ꢁ
10
0 … 10 V, 2 … 10 V, 0 … 5 V, 1 … 5 V
0 … 20 mV
0 %
ꢁ
-100 %
ꢁ
0 … 20 mA, 4 … 20 mA
-50 %
ꢁ
ꢁ
ꢁ
-100%, -50%, 0%, 50%, 100% of measuring span of the
chosen output range
+50 %
ꢁ
+100 %
ꢁ
ꢁ
Load
Zero pot. activated: additional 25 %
at output current
at output voltage
Offset
< 12 V (600 Ω at 20 mA)
< 10 mA (1 KΩ at 10 V)
20 µA and. 10 mV
Switch S3
3
Residual ripple
< 10 mVeff
Bandwidth 10 kHz
Bandwidth 10 Hz
Adjustment zero pot.
Adjustment span pot.
Gain error
+25% measuring span of the chosen output range
0.33 ... 3.30 x end value of chosen input range
< 0.1% of FS
ꢁ
Set range can be documented on side of housing.
Temperature coefficient
Cut-off frequeny
General
< 60 ppm/K of FS
> 10 kHz, < 10 Hz switch
ꢁ= on
= off
Voltage supply
20 ... 230 V ac/dc +10%
approx. 1 W
Power consumption
Frequency range
Operating temperature
Storage temperature
Factory setting
48 ... 62 Hz
-10 °C ... +70 °C
-40 °C ... +85 °C
0 ... 10 V / 0 ... 10 V 10 Hz
92.4 / 112.5 / 12.5
approx. 100 g
Dimensions L/H/B mm
Weight
Approvals
CE, cUL, GL
Coordination of insulation according to EN 50178, 04/98
Rated voltage
600 V
Rated surge voltage
Overvoltage category
Contamination class
Test voltage
5 kV, 1.2/50 us, acc. to IEC 255-4
Dimensions and accessories
see page 298 + 308
III
2
4 KVeff input against output against auxiliary power
Standards/specifications
EMC standards
EN 50178
DIN EN 61326, EN 61326/A1, EN 50081-2, EN 61000-6-2
*TU = 23 °C single module
185
RTD Signal Conditioners
Switch position/setting options
PT100/2
0(4) ... 20 mA
PT100/2
0 ... 10 V
WAVEANALOG RTD
Tmin
0 C°
1
2
ꢁ
3
ꢁ
Span
40 … 50 °C
50 … 75 °C
75 … 110 °C
110 … 165 °C
165 … 245 °C
245 … 360 °C
360 … 540 °C
540 … 800 °C
4
5
6
ꢀ2-wire technology
ꢀconfigurable temperature range
-200 °C ... +800 °C
ꢀConfigurable output current range
0 ... 20 mA / 4 ... 20 mA
ꢀcross-connectable voltage supply
via cross-connectors
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
-10 C°
-20 C°
-40 C°
-60 C°
-80 C°
-100 C°
-200 C°
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Output1)
Range
1) only modules with
current output
7
0 … 20 mA
4 … 20 mA
Approvals:
ꢁ
ꢁ= on
= off
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WTS4 PT100/2 C 8432210000
WTZ4 PT100/2 C 8432220000
PT100/2 / 0(4) ... 20 mA
*
*
WTS4 PT100/2 V 8432180000*
WTZ4 PT100/2 V 8432190000*
PT100/2 / 0 ... 10 V
Technical data***
Input signal
PT100/2-wire
-200 ... +800 °C
1.45 mA
PT100/2-wire
-200 ... +800 °C
1.45 mA
Temperature range
Supply current
Conductor resistance
Output signal
0(4) ... 20 mA
0 ... 10 V
Load resistance
≤ 500 Ω
≥ 1 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Measurement range ≥ 200 K
0.5% of measurement range
0.5% of measurement range
≤ 200 ppm / °C
≤ 200 ppm / °C
(typ. 80 ppm / °C)
(typ. 80 ppm / °C)
100 K ≤ measurement range < 200 K
40 K ≤ measurement range < 100 K
≤ 250 ppm / °C
(typ. 100 ppm / °C)
≤ 500 ppm / °C
≤ 250 ppm / °C
(typ. 100 ppm / °C)
≤ 500 ppm / °C
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
< 48 mA at Iout = 20 mA
≤ 2 A
(19.2 ... 28.8 Vdc)
< 38 mA at Iout = 10 mA
≤ 2 A
Power consumption
Current carrying capacity of cross-connection
Operating temperature
0 °C ... +55 °C
-20 °C ... +85 °C
0 °C ... +55 °C
-20 °C ... +85 °C
Storage temperature
Standards/specifications
EMC standards
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
Dimensions L / H / W mm
Approvals
92.4 / 112.5 / 12.5
CE, UL, CSA
92.4 / 112.5 / 12.5
CE, UL, CSA
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
*
without balancing
*** TU = 23 °C single module
Preconfigured modules
Output
Aids
ꢀVoltage supply 24 Vdc, 50 mA
Input
0 … 20 mA
4 … 20 mA
0 … 10 V
Screw connection
0 … 100 °C
special balancing
0 … 100 °C
special balancing
8432210001
8432219999**
8432220001
8432229999**
8432210011
8432180001
8432219999**
8432220011
8432229999**
8432189999**
8432190001
8432199999**
ꢀSimulator for PT 100 or precision-resistance-decade
Tension clamp connection
ꢀAmpere-/voltmeter which can be calibrated to an
accuracy of >0.1 % of the end value.
**You must indicate the temperature range when ordering
Please indicate additional output signal of current output
186
RTD Signal Conditioners
Switch position/setting options
PT100/3
0(4) ... 20 mA
PT100/3
0 ... 10 V
WAVEANALOG RTD
Tmin
0 C°
1
2
ꢁ
3
ꢁ
Span
40 … 50 °C
50 … 75 °C
75 … 110 °C
110 … 165 °C
165 … 245 °C
245 … 360 °C
360 … 540 °C
540 … 800 °C
4
5
ꢁ
6
ꢁ
ꢀ3-wire technology
ꢀconfigurable temperature range
-200 °C ... +800 °C
ꢀconfigurable output current range
0 ... 20 mA / 4 ... 20 mA
ꢀcross-connectable voltage supply
via cross-connectors
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
-10 C°
-20 C°
-40 C°
-60 C°
-80 C°
-100 C°
-200 C°
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Output1)
Range
1) only modules with
current output
7
0 … 20 mA
4 … 20 mA
Approvals:
ꢁ
ꢁ= on
= off
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WTS4 PT100/3 C 8432150000
WTZ4 PT100/3 C8432160000
PT100/3 / 0(4) ... 20 mA
*
*
WTS4 PT100/3 V 8432090000*
WTZ4 PT100/3 V 8432130000*
PT100/3 / 0 ... 10 V
Technical data***
Input signal
PT100/3-wire
-200 ... +800 °C
1.45 mA
PT100/3-wire
-200 ... +800 °C
1.45 mA
Temperature range
Supply current
Conductor resistance
Output signal
≤ 50 Ω
≤ 50 Ω
0(4) ... 20 mA
≤ 500 Ω
0 ... 10 V
Load resistance
≥ 1 kΩ
Accuracy at Tu=23 °C
Temperature coefficient
Measurement range ≥ 200 K
0.5% of measurement range
0.5% of measurement range
≤ 200 ppm / °C
(typ. 80 ppm / °C)
≤ 250 ppm / °C
(typ. 100 ppm / °C)
≤ 500 ppm / °C
(typ. 200 ppm / °C)
≤ 200 ppm / °C
(typ. 80 ppm / °C)
≤ 250 ppm / °C
(typ. 100 ppm / °C)
≤ 500 ppm / °C
(typ. 200 ppm / °C)
100 K ≤ measurement range < 200 K
40 K ≤ measurement range < 100 K
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
< 48 mA at Iout = 20 mA
≤ 2 A
(19.2 ... 28.8 Vdc)
< 38 mA at Iout = 10 mA
≤ 2 A
Power consumption
Current carrying capacity of cross-connection
Operating temperature
0 °C ... +55 °C
-20 °C ... +85 °C
0 °C ... +55 °C
-20 °C ... +85 °C
Storage temperature
Standards/specifications
EMC standards
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
Dimensions L / H / W mm
Approvals
92.4 / 112.5 / 12.5
CE, UL, CSA
92.4 / 112.5 / 12.5
CE, UL, CSA
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
*
without balancing
*** TU = 23 °C single module
Preconfigured modules
Output
Aids
ꢀVoltage supply 24 Vdc, 50 mA
Input
0 … 20 mA
4 … 20 mA
0 … 10 V
Screw connection
0 … 100 °C
special balancing
0 … 100 °C
special balancing
8432150001
8432159999**
8432160001
8432169999**
8432150011
8432090001
8432159999**
8432160011
8432169999**
8432099999**
8432130001
8432139999**
ꢀSimulator for PT 100 or precision-resistance-decade
Tension clamp connection
ꢀAmpere-/voltmeter which can be calibrated to an
accuracy of >0.1 % of the end value.
** You must indicate the temperature range when ordering
Please indicate additional output signal of current output
187
RTD Signal Conditioners
Switch position/setting options
PT100/4
0(4) ... 20 mA
PT100/4
0 ... 10 V
WAVEANALOG RTD
Tmin
0 C°
1
2
ꢁ
3
ꢁ
Span
40 … 50 °C
50 … 75 °C
75 … 110 °C
110 … 165 °C
165 … 245 °C
245 … 360 °C
360 … 540 °C
540 … 800 °C
4
5
6
ꢀ2-, 3- and 4-wire technology
ꢀconfigurable temperature range
-200 °C ... +800 °C
ꢀconfigurable output current range
0 ... 20 mA / 4 ... 20 mA
ꢀcross-connectable voltage supply
via cross-connectors
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
-10 C°
-20 C°
-40 C°
-60 C°
-80 C°
-100 C°
-200 C°
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Output 1)
Range
PT 100
7
8
9
ꢁ
10
ꢁ
0 … 20 mA
4 … 20 mA
2 - wire
3 - wire
4 - wire
ꢁ
Approvals:
ꢁ
ꢁ
ꢁ
ꢁ
1) only modules with current output
ꢁ= on
= off
Block diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
Screw connection
WTS4 PT100/4 C 8432270000
WTZ4 PT100/4 C 8432280000
PT100/4 / 0(4) ... 20 mA
*
WTS4 PT100/4 V 432240000*
WTZ4 PT100/4 V 432250000*
PT100/4 / 0 ... 10 V
Tension clamp connection
Input/output
*
Technical data***
Input signal
PT100/4-wire
-200 ... +800 °C
1.45 mA
PT100/4-wire
-200 ... +800 °C
1.45 mA
Temperature range
Supply current
Conductor resistance
Output signal
≤ 50 Ω (3- & 4-wire)
0(4) ... 20 mA
≤ 500 Ω
≤ 50 Ω (3- & 4-wire)
0 ... 10 V
Load resistance
≥ 1 kΩ
Accuracy at Tu=23 °C
100 K ≤ measurement range < 600 K
Measurement range ≤ 100 K
Measurement range ≥ 600 K
Temperature coefficient
Measurement range ≥ 200 K
0.1% of measurement range
0.1 K
0.1% of measurement range
0.1 K
0.2% of measurement range
0.2% of measurement range
≤ 200 ppm / °C
(typ. 80 ppm / °C)
≤ 225 ppm / °C
(typ. 90 ppm / °C)
≤ 450 ppm / °C
(typ. 180 ppm / °C)
≤ 200 ppm / °C
(typ. 80 ppm / °C)
≤ 225 ppm / °C
(typ. 90 ppm / °C)
≤ 450 ppm / °C
(typ. 180 ppm / °C)
100 K ≤ measurement range < 200 K
40 K ≤ measurement range < 100 K
General
Voltage supply
24 Vdc 20%
24 Vdc 20%
(19.2 ... 28.8 Vdc)
< 48 mA at Iout = 20 mA
≤ 2 A
(19.2 ... 28.8 Vdc)
< 38 mA at Iout = 10 mA
≤ 2 A
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
0 °C ... +55 °C
-20 °C ... +85 °C
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
0 °C ... +55 °C
-20 °C ... +85 °C
EN 50178, IEC 751
EN 50081, EN 50082,
EN 55011
Standards/specifications
EMC standards
Dimensions L / H / W mm
Approvals
92.4 / 112.5 / 12.5
CE, UL, CSA
92.4 / 112.5 / 12.5
CE, UL, CSA
Dimensions and accessories see
Page 298 + 308
Page 298 + 308
*
without balancing
*** TU = 23 °C single module
Preconfigured modules
Output
Aids
Input
0 … 20 mA
4 … 20 mA
0 … 10 V
ꢀVoltage supply 24 Vdc, 50 mA
Screw connection
0 … 100 °C
special balancing
0 … 100 °C
special balancing
8432270001
8432279999**
8432280001
8432289999**
8432270011
8432240001
8432249999**
8432250001
8432259999**
ꢀSimulator for PT 100 or precision-resistance-decade
Tension clamp connection
8432280011
ꢀAmpere-/voltmeter which can be calibrated to an
accuracy of >0.1 % of the end value.
** Please indicate the temperature range and the sensor type (2-, 3- or 4-wire).
Please indicate additional output signal of current output
188
W
NE
RTD-Signal Isolating Transformer (Configurable)
ꢁ= on
= off
Adjustment help
WAVETOOL
Selection of input
PRO RTD
WAVEANALOG PRO RTD
Switch 1
Input
ꢀmeasurement from PT 100,
Ni 100, R, potentiometer
ꢀuniverally adjustable via DIP switch
ꢀ3-way-isolation
ꢀstatus LED
ꢀlinearization
This service tool
enables quick and
uncomplicated config-
uration of
WAVEANALOG PRO.
Download from
Internet:
1
2
ꢁ
ꢁ
3
ꢁ
ꢁ
ꢁ
ꢁ
PT100 2-wire
PT100 3-wire
PT100 4-wire.
ꢁ
ꢁ
ꢁ
ꢁ
R
2-wire
NI100 2-wire
NI100 3-wire
NI100 4-wire
Potentiometer
ꢁ
ꢁ
ꢀcross-connectable voltage supply
via cross-connectors
http:
//www.weidmueller.de
→ Products →
Downloads
Selection of minimum input values
Approvals:
Switch 1
(see page 192)
ꢀmin
Rmin
Pot.min
4
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
5
ꢁ
ꢁ
ꢁ
ꢁ
6
ꢁ
ꢁ
7
0°C
0 Ω
10 Ω
20 Ω
20 Ω
30 Ω
40 Ω
50 Ω
60 Ω
70 Ω
80 Ω
90 Ω
100 Ω
150 Ω
200 Ω
0%
ꢁ
Block diagram
-10°C
-20°C
-25°C
-30°C
-40°C
-50°C
-60°C
-70°C
-80°C
-90°C
-100°C
-150°C
-200°C
10%
20%
25%
30%
40%
50%
60%
70%
80%
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Ordering data
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WAS5 PRO RTD
WAZ5 PRO RTD
configurable
8560700000
8560710000
ꢁ
ꢁ
Technical data*
Special range
Input (adjustable)
PT100/2-/3-/4-wire: -200°C to 850°C
Ni100 : -60°C to +250°C
Selection of the measurement range
Potentiometer: min: 0…100Ω / max:0…100kΩ
Resistance: 0 ... 450Ω /
Switch 2
T
R
pot.
1
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
2
3
ꢁ
ꢁ
ꢁ
ꢁ
4
5
Output (adjustable)
Output voltage
40K
50K
20Ω
25Ω
20%
25%
30%
35%
40%
45%
50%
55%
60%
62.5%
65%
70%
75%
80%
85%
90%
95%
100%
---
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
0...10 V
ꢁ
Offset voltage
max. 0.05 V
60K
30Ω
Load resistance
≥ 1 kΩ
70K
35Ω
Output current
0/4 ... 20 mA
80K
40Ω
ꢁ
ꢁ
Offset current
max. 100 µA
90K
45Ω
Load resistance
≤ 600 Ω
100K
110K
120K
125K
130K
140K
150K
160K
170K
180K
190K
200K
250K
300K
350K
400K
450K
500K
550K
600K
650K
700K
750K
800K
850K
900K
50Ω
Accuracy, slow/fast step response
PT 100,Ni 100: 0.3% of measurement range 0.8%,
Measurement range < 100 K / 0.3 K / 0.8 K
Potentiometer: 0.2% of FS / 0.3%
Resistance: 0.2% of FS / 0.3%
55Ω
60Ω
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
62.5Ω
65Ω
Step response (switchable via DIP switch)
typ.
fast
slow
70Ω
RTD, R
< 1.2 s
< 500 ms
< 2.2 s
< 1.1 s
75Ω
ꢁ
ꢁ
Potentiometer
80Ω
Temperature coefficient
measurement range ≥ 200 K ≤ 200 ppm / °C
100 K ≤ measurement range < 200 K ≤ 250 ppm / °C
40 K ≤ measurement range < 100 K ≤ 400 ppm / °C
50 Ω for 3- and 4-wire
85Ω
90Ω
95Ω
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Max. wire resistance:
100Ω
125Ω
150Ω
175Ω
200Ω
225Ω
250Ω
275Ω
300Ω
325Ω
350Ω
375Ω
400Ω
425Ω
450Ω
Influence of wire resistances:
Open circuit recognition:
Range of man. fine adjustment
Status LED:
max. + 0.25°C at 50 Ω wire resistance
Output signal > 10 V or > 20 mA, LED blinks
---
≥
5%, from ver. 1: ≥12.5%, potentiometer ≥ 12.5 %…25 %
---
ꢁ
ꢁ
Module active: LED lit / open circuit: LED blinks
Error: LED off
---
---
General
---
Supply voltage
18 Vdc ... 24 Vdc ... 30 Vdc
---
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Power consumption
Current carrying capacity of cross-connection
Operating temperature
Storage temperature
Factory setting
830 mW ... 880 mW ... 980mW @ Iout = 20 mA
---
≤ 2 A
---
0...55°C
---
-20...85°C
---
ꢁ
ꢁ
PT 100/3 0 ... 100 °C / 4 ... 20 mA
No manual fine adjustment; slow step response
92.4 / 112.5 / 17.5
---
---
Dimensions L/H/B mm
---
Weight
approx. 100 g
Approvals
CE, cUL, GL
Selection of output
Switch 2
Switching on the
Coordination of insulation according to DIN EN 50178, 04/98
manual fine adjustment
S.1
Rated voltage
300 V
4 kV
III
Output
0...10V
6
7
Surge voltage
ꢁ
man. adj..
8
Overvoltage category
Contamination class
Clearance and creepage distance
Test voltage
0...20mA
4...20mA
off
on
2
ꢁ
ꢁ
3 mm
2 kVeff
Selection of
step set time
Standards/specifications
EMC standards
EN 50178, IEC751
Time of
S.2
8
EN 50081, EN50082, EN55011
Page 298 + 308
step response
Dimensions and accessories see
* TU = 23 °C single module
slow
fast
ꢁ
189
Thermo-Signal Conditioners
Switch position/setting options
Thermo Select
°C / 0 ... 20 mA,
WAVEANALOG Thermo
SW 1
2
ꢁ
ꢁ
SW 2
ꢀthermocouples K, J, T, E,
N, R, S, B configurable
ꢀtemperature range
-200 °C ... +1820 °C
ꢀno adjustment necessary
ꢀcold junction compensation
ꢀconfigurable output signal
ꢀcross-connectable voltage supply
via cross-connectors
Type
K
J
T
E
N
R
S
B
1
ꢁ
3
Span
100 C°
150 C°
200 C°
250 C°
300 C°
350 C°
400 C°
450 C°
500 C°
550 C°
600 C°
650 C°
700 C°
750 C°
800 C°
850 C°
900 C°
950 C°
1000 C°
1050 C°
1100 C°
1150 C°
1200 C°
1250 C°
1300 C°
1350 C°
1400 C°
1450 C°
1500 C°
1600 C°
1700 C°
1800 C°
1
2
3
4
5
4 ... 20 mA, 0 ... 10 V
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
SW 1
5
ꢁ
ꢁ
ꢁ
ꢁ
Tmin
0 C°
-10 C°
-20 C°
-30 C°
4
6
ꢁ
ꢁ
7
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Approvals:
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
-40 C°
-50 C°
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Block diagram
-100 C°
-150 C°
-200 C°
+50 C°
+100 C°
+150 C°
+200 C°
+250 C°
+500 C°
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Ordering data
Type
Cat. No.
Screw connection
Tension clamp connection
Input/output
WTS4 Thermo Select
WTZ4 Thermo Select
°C / 0 ... 20 mA
8432300000
8432310000
SW 2
7
Output
0 - 10 V
0 - 20 mA
4 - 20 mA
6
ꢁ
ꢁ
ꢁ
°C / 4 ... 20 mA
ꢁ
°C / 0 ... 10 V
Technical data*
Input signal
Types
Filter
off
on
8
Thermocoupler acc. to IEC584 (fully insulated)
K -200 ... +1372 °C
ꢁ
J -200 ... +1200 °C
ꢁ
ꢁ
= on
= off
T -200 ... +400 °C
E -200 ... +1000 °C
N -200 ... +1300 °C
R -50 ... +1760 °C
S -50 ... +1760 °C
B +50 ... +1820 °C
Output signal
0 ... 20 mA
Load resistance
Output signal
≤ 500 Ω
4 ... 20 mA
Load resistance
Output signal
≤ 500 Ω
0 ... 10 V
Load resistance
Accuracy at Tu = 23 °C
≥ 1 kΩ
Type K -200°C ...-150°C (5K + 0.1% of set range)
-150°C ...1200°C (3K + 0.1% of set range)
1200°C ...1372°C (4K + 0.1% of set range)
Type J -200°C ...-150°C (4K + 0.1% of set range)
-150°C ...1200°C (3K + 0.1% of set range)
Type T -200°C ...-150°C (5K + 0.1% of set range)
-150°C ...400°C (3K + 0.1% of set range)
Type E -200°C ...-150°C (4K + 0.1% of set range)
-150°C ...1000°C (3K + 0.1% of set range)
Type N -200°C ...-150°C (6K + 0.1% of set range)
-150°C ...1300°C (3K + 0.1% of set range)
Type R -50°C ...200°C (10K + 0.1% of set range)
200°C ...1760°C (6K + 0.1% of set range)
Type S -50°C ...200°C (10K + 0.1% of set range)
200°C ...1760°C (6K + 0.1% of set range)
Type B 50°C ...250°C (25K + 0.1% of set range)
250°C ...500°C (10K + 0.1% of set range)
500°C ...1820°C (6K + 0.1% of set range)
(200 ppm v. Span
Temperature coefficient
+ 0.075 K) /K
Response time without filter
Response time with filter
General
1.1 s
6 s
Voltage supply
24 Vdc 20% (19.2 ... 28.8 Vdc)
Power consumption
Current carrying capacity of cross-connection
Open circuit recognition
Operating temperature
Storage temperature
Standards/specifications
EMC standards
< 38 mA at I = 20 mA
out
≤ 2 A
LED blinks (output value: > 20 mA and. > 10 V)
0 °C ... +55 °C
-20 °C ... +85 °C
EN 50178, IEC584
EN 50081, EN 50082, EN 55011
92.4 / 112.5 / 12.5
Dimensions L / H / W mm
Approvals
CE, UL, CSA
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
190
W
NE
Thermo Signal Isolating Transformers (Configurable)
Adjustment help
WAVETOOL
Selection the
thermocoupler
SW1
Selection of minimum
temperature
SW1
PRO Thermo
WAVEANALOG PRO Thermo
ꢀ3-way-isolation
ꢀthermocouples
K, J, T, E, N, R, S, B configurable
ꢀtemperature range
-200 °C ... +1820 °C
ꢀno adjustment necessary
ꢀcold junction compensation
ꢀconfigurable output signal
ꢀcross-connectable voltage supply
via cross-connectors
This service tool
enables quick and
uncomplicated config-
uration of
WAVEANALOG PRO.
Download from the
Internet:
Type
K
1
2
ꢁ
ꢁ
3
ꢁ
ꢁ
ꢁ
ꢁ
ꢀmin
0°C
4
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
5
ꢁ
ꢁ
ꢁ
ꢁ
6
ꢁ
ꢁ
7
ꢁ
ꢁ
J
-10°C
T
ꢁ
ꢁ
ꢁ
-20°C
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
E
-30°C
N
ꢁ
ꢁ
-40°C
ꢁ
ꢁ
http:
R
-50°C
//www.weidmueller.de
→ Products →
Downloads
S
-100°C
-150°C
-200°C
+50°C
B
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Approvals:
(see page 192)
+100°C
+150°C
+200°C
+250°C
500°C
Block diagram
ꢁ
ꢁ
Special range
Selection of
temperature span
SW2
Selection of
output
Ordering data
Type
Cat. No.
SW2
Screw connection
Tension clamp connection
Input/output
WAS5 PRO Thermo
WAZ5 PRO Thermo
configurable
8560720000
8560730000
Span
100°C
150°C
200°C
250°C
300°C
350°C
400°C
450°C
500°C
550°C
600°C
650°C
700°C
750°C
800°C
850°C
900°C
950°C
1000°C
1050°C
1100°C
1150°C
1200°C
1250°C
1300°C
1350°C
1400°C
1450°C
1500°C
1600°C
1700°C
1800°C
1
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
2
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
3
ꢁ
ꢁ
ꢁ
ꢁ
4
ꢁ
ꢁ
5
Output
0...10V
6
7
ꢁ
ꢁ
0...20mA
4...20mA
Technical data*
Input (adjustable)
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Thermocouples acc. to EN 60584-1
Type K, J, E, N, R, S, B via DIP switch selectable
Type K -200°C ...-150°C (5K + 0.1% of set range)
-150°C ...1200°C (3K + 0.1% of set range)
1200°C ...1372°C (4K + 0.1% of set range)
Type J -200°C ...-150°C (4K + 0.1% of set range)
-150°C ...1200°C (3K + 0.1% of set range)
Type T -200°C ...-150°C (5K + 0.1% of set range)
-150°C ...400°C (3K + 0.1% of set range)
ꢁ
ꢁ
Accuracy at Tu = 23 °C
Switching on the
manual fine adjustment
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
SW1
man. adjust.
8
off
on
ꢁ
Type E -200°C ...-150°C (4K + 0.1% of set range)
-150°C ...1000°C (3K + 0.1% of set range)
Type N -200°C ...-150°C (6K + 0.1% of set range)
-150°C ...1300°C (3K + 0.1% of set range)
Type R -50°C ...200°C (10K + 0.1% of set range)
200°C ...1760°C (6K + 0.1% of set range)
Type S -50°C ...200°C (10K + 0.1% of set range)
200°C ...1760°C (6K + 0.1% of set range)
Type B 50°C ...250°C (25K + 0.1% of set range)
250°C ...500°C (10K + 0.1% of set range)
500°C ...1820°C (6K + 0.1% of set range)
ꢁ
ꢁ
Switching on the
filter function
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
SW2
Filter
off
8
on
ꢁ
ꢁ
ꢁ
Output (adjustable)
Output voltage
0...10 V
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
Offset voltage
Max. 0.05 V
Load resistance
≥ 1 KΩ
Output current
0/4 ... 20 mA
Offset current
max. 100 µA
ꢁ
ꢁ
Load resistance
≤ 600 Ω
Step response
max. 1.4 s
at connected filter function
Max. wire resistance
Open circuit recognition
Range of man. fine adjustment
Status LED:
max. 7.5 s
50 Ω for 3- and 4-wire
Output signal > 10 V or > 20 mA, LED blinks
ꢁ= on
= off
≥
5%
Module active: LED lights up / open circuit: LED blinks
Error: LED off
General
Coordination of insulation acc. to DIN EN 50178, 04/98
Supply voltage:
18 Vdc ... 24 Vdc ... 30 Vdc
Rated voltage
300 V
4 kV
III
Power consumption:
800 mV ... 850 mW ... 950 mW @ I output = 20 mA
Surge voltage
Current carrying capacity of cross-connection
≤ 2 A
Overvoltage category
Contamination class
Clearance & creep. distance
Test voltage
2
Operating temperature
Storage temperature
0 °C ... +55 °C
-20 ... +85 °C
3 mm
2 kVeff
Standards/specifications
EMC standards
EN 50178, IEC751
EN 50081, EN50082, EN55011
Factory setting
Type K 0 ... 1000 °C / 4 ... 20 mA; no filter;
No manual fine adjustment
92.4 / 112.5 / 17.5
100 g
Dimensions L/H/W mm
Weight
Approvals
CE, cUL, GL
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
191
W
NE
Adjustment Help WAVETOOL
The adjustment help – WAVETOOL –
Once the required input and output parameters have been
entered, the program determines the correct switch setting and
gives instructions for the electrical connection of the module.
Where necessary, it also determines and displays the required
calibration values. The entire process can be printed out or
saved as a PDF file for installation documentation purposes.
enables quick and uncomplicated configuration of
WAVEANALOG PRO DC,
WAVEANALOG PRT RTD,
WAVEANALOG PRO THERMO.
Menu for selecting the functions
Download from the Internet:
http://www.weidmueller.de Products Download
ꢂ
ꢂ
For configuring the current/voltage isolating transformer
For configuring the temperature signal isolating transformer
For configuring the thermo signal isolating transformer
Printout of protocol for the documentation
TOOL
WAVE
192
193
WAVECONTROL
Current monitoring
Monitoring flows of currents enables a
constant control of individual devices
and installation components.
The potential-free wire is inserted
through the module, allowing currents
up to 60 A ac/dc to be measured.
Quite often, there are high-frequency
parts of signals on the wire to be
measured. In order to be able to take
these parts of the signals into consid-
eration, so-called TRMS converters
(TRUE Root Mean Square) are con-
nected to the Hall sensors. This
enables measurements up to 2 kHz,
independent of the shape of the
curve.
Discrepancies or disruptions arising in
the electrical circuit can easily be eval-
uated as breakdowns. Targeted recti-
fying procedures can be taken.
The WAVECONTROL range of prod-
ucts convert sinusoidal/non-sinusoidal
AC/DC currents up to 60 A to stan-
dard analogue signals. The measure-
ment processes are based on 2 basic
principles.
One principle is alternating currents up
to 10 A ac and 50/60 Hz are mea-
sured using the transformer
process. The module is looped
directly into the measurement circuit.
A Hall-effect element comes in to
operation at 10 A ac/dc.
Fig.: Monitoring motor currents
Standard signals (0...20, 4...20 mA,
4...20 A current loop supply, 0...10 V)
or a switch output are on offer.
Monitoring a motor in a cooling system
Monitoring a pump in a sewage treatment plant
194
WAVECONTROL
Galvanically isolated measurement circuit
Measurements of direct and alternat-
ing currents possible
TRMS versions for measuring non
sinusoidal signals
Measurement range switch without
calibration
Relay version with selectable
hysteresis
Selectable working and closed-circuit
current process for defined statuses
(optional as normally open or normally
closed contact)
Error indication via LED indication
Less wiring costs thanks to cross-
connections
Very good marking options
Fast commissioning –
pluggable replacement PCBs
Connection technology – screw or
tension clamp via socket block
Tool-free mounting
Coding elements in the connections –
false plugging not possible
195
Current Monitoring
WAS2 CMR
WAZ2 CMR
WAS2 CMR
WAZ2 CMR
WAVECONTROL
ꢀcurrent ranges adjustable
via DIP switch
ꢀcross-connectable voltage
supply via cross-connectors
ꢀselectable hysteresis
1/5/10 A ac
selectable with
relay output
20/40/60A ac
selectable with
relay output
ꢀselectable working and
closed-circuit current principle
Approvals:
Block diagram
Ordering data
Screw connection
Tension clamp connection
Technical data*
Input
Type
Cat. No.
Qty.
1
Type
Cat. No.
Qty.
1
WAS2 CMR 1/5/10A ac
WAZ2 CMR 1/5/10A ac
8516560000
8516570000
WAS2 CMR 20/40/60A ac
WAZ2 CMR 20/40/60A ac
8513340000
8526600000
1
1
Input current
1A ac/5A ac/10A ac selectable (without additional adjustment)
50Hz/60Hz
20A ac/40A ac/60A ac selectable (without additional adjustment)
50Hz/60Hz
Input frequency
Pass through diameter
Measuring principle
Connection type
Measurement circuit voltage
8mm
transformer coupled
screw or tension clamp connection
250Vac
Contact-free current monitoring using Hall sensor
Push-through connection
400Vac, higher voltages dependent on wire insulation
Max. measuring circuit
Output
100A for 1s
dependent on wire cross-section
Contact set
1 changeover contact
1 changeover contact
Min. switching voltage
Max. switching voltage
Continuous current AC
Continuous current DC
Max. switching current
Min. switching current
Status LED
6Vdc/6Vac
6Vdc/6Vac
60Vdc/250Vac
60Vdc/250Vac
3A
3A
0.7A
0.7A
7A
7A
100mA
100mA
green LED
green LED
Threshold
10% ... 100% adjustable via front potentiometer
10% ... 100% adjustable via front potentiometer
Hysteresis
approx. 5% or approx. 10% selectable from set threshold
approx. 5% or approx. 10% selectable from set threshold
Temperature coefficient
Response time (10 ... 90%)
Working/closed-circuit current principle
Coordination of insulation acc. to DIN EN 50178, 04/98
Rated voltage
≤ 800 ppm/K
typ. 700 ms
selectable
≤ 250 ppm/K
typ. 700 ms
selectable
300V
4KV
lll
300V
4KV
lll
Surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
Test voltage
2
2
≥ 3 mm
4kV eff
≥ 3 mm
4kV eff
General
Supply
Supply voltage
21.6Vdc...24Vdc...26.4Vdc
21.6Vdc...24Vdc...26.4Vdc
Power consumption at rated voltage
8.3 mA (relay not switched)
23 mA (relay not switched)
24 mA (relay switched)
47 mA (relay switched)
Reverse polarity protection
Current carrying capacity of the cross-connection
Operating temperature range
Storage/transport
yes
yes
≤ 2 A
≤ 2 A
0 ... 50ºC
0 ... 50ºC
-20 ... +70ºC
-20 ... +70ºC
Factory setting
Input range: 5A ac; hysteresis 10%, working current principle
Input range :40A ac; hysteresis 10% working current principle
Dimensions L/H/B (mm)
Weight
92.4/112.4/22.5
150g
92.4/112.4/22.5
150g
Approvals
CE, cUL
CE, cUL
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
Page 298 + 308
196
Current Monitoring
WAS1 CMA
WAZ1 CMA
WAS1 LP CMA
WAZ1 LP CMA
WAVECONTROL
ꢀinput and output range
adjustable via DIP switch
ꢀno calibration required
ꢀcross-connectable voltage
supply via cross-connectors
1/5/10A ac selec-
table with
analogue output
0…20 mA /
4…20 mA
1/5/10 A ac
selectable with
analogue output
4…20 mA
loop powered
0…10 V
Approvals:
Block diagram
Ordering data
Screw connection
Tension clamp connection
Technical data*
Input
Type
Cat. No.
Qty.
1
Type
Cat. No.
Qty.
1
WAS1 CMA 1/5/10A ac
WAZ1 CMA 1/5/10A ac
8523400000
8523410000
WAS1 LP CMA 1/5/10A ac
WAZ1 LP CMA 1/5/10A ac
8528650000
8528660000
1
1
Input current
1 A ac/5 A ac/10 A ac selectable (without additional adjustment) 1A ac/5A ac/10A ac selectable (without additional adjustment)
Input frequency
50 Hz/60 Hz
50 Hz/60 Hz
Accuracy
0.5% FSR
0.5% FSR
Measuring principle
Connection type
Measurement circuit voltage
Max. measuring circuit
Output
transformer coupled
Screw or tension clamp connection
250 Vac
transformer coupled
Screw or tension clamp connection
250 Vac
100 A for 1s
100 A for 1s
Current/voltage selectable
0 ... 10 V
4 ... 20mA current loop supply
0 ... 20 mA
4 ... 20 mA
0 ... 10 V
Output voltage
Offset voltage
max. 0.05 V
≥1 K Ω
Load resistance
Output signal limit
Output current
Offset current
approx. 13 V and 24 mA
0/4 ... 20 mA
max.100 µA
≤ 600 Ω
approx. 24 mA
4 ... 20 mA
max. 100 µA
Load resistance
≤ 550 Ω (at 24 V) RL = (Vcc - 13V) / 20 mA
Dependent on voltage Vcc
green LED
Status LED
green LED
ON–> OK; blinks –> signal out of range; OFF –> Error
ON–> OK; blinks –> signal out of range; OFF –> Error
≤ 200 ppm/K
Temperature coefficient
Response time (10 ... 90%)
Coordination of insulation acc. to DIN EN 50178, 04/98
(safe separation)
≤ 200 ppm/K
typ. 700 ms
typ. 700 ms
Rated voltage
300V
6KV
300V
6KV
Surge voltage
Overvoltage category
Contamination class
lll
lll
2
2
Clearance and creepage distance
Test voltage
≥ 5.5 mm
4kV eff
≥ 5.5 mm
4kV eff
General
Supply
Supply voltage
21.6 Vdc...24 Vdc...26.4 Vdc
13 Vdc ... 30 Vdc
yes
Power consumption at rated voltage
Reverse polarity protection
40 mA at I = 20 mA
out
yes
Operating temperature range
Storage/transport
0 ... 50ºC
0 ... 50ºC
- 20 ... + 70ºC
0 ... 5A ac; 4 ... 20mA
72/92.4/22.5
150g
-20 ... +70ºC
0 ... 5A ac; 4 ... 20mA
72/92.4/22.5
150g
Factory setting
Dimensions L/H/W (mm)
Weight
Approvals
CE, cUL
CE, cUL
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
Page 298 + 308
197
Current Monitoring
WAS2 CMA
WAZ2 CMA
WAS2 CMA
WAZ2 CMA
WAVECONTROL
ꢀinput and output range
adjustable via DIP switch
ꢀno calibration required
ꢀtrue TRMS value measurements
ꢀhall sensor measurement
method
5/10A ac/dc
selectable with
analogue output
0 ... 20 mA/
4 ... 20 mA/
0 ... 10 V
20/25/30A ac/dc
selectable with
analogue output
0 ... 20 mA/
4 ... 20 mA/
0 ... 10 V
Approvals:
Block diagram
Input / Output
configurable
Ordering data
Screw connection
Tension clamp connection
Technical data*
Input
Type
Cat. No.
Qty.
1
Type
Cat. No.
Qty.
1
WAS2 CMA 20/25/30A uc
WAZ2 CMA 20/25/30A uc
8545830000
8545840000
WAS2 CMA 5/10A uc
WAZ2 CMA 5/10A uc
8526610000
8526620000
1
1
Input current
20/25/30 A uc selectable (without additional adjustment)
0 Hz - 2 kHz (True RMS to DC Converter)
1% (0Hz - 1KHz) Crest factor 3 FSR
2% (0Hz - 2KHz) Crest factor 5 FSR
Contact-free current monitoring using Hall sensor
Push-through connection
5 A uc/10 A uc selectable (without additional adjustment)
0 Hz - 2 kHz (True RMS to DC Converter)
1% (0 Hz - 1 kHz) Crest factor 3 FSR
2% (0 Hz - 2 kHz) Crest factor 5 FSR
Contact-free current monitoring using Hall sensor
Push-through connection
Input frequency
Accuracy
Measuring principle
Connection type
Pass through diameter
Measurement circuit voltage
8 mm
8 mm
400 Vac, higher voltages dependent on wire insulation
400 Vac, higher voltages dependent on wire insulation
Max. measuring circuit
Output
dependent on wire cross-section
dependent on wire cross-section
Current/voltage selectable
0 ... 10 V
0 ... 10 V
0 ... 20 mA
0 ... 20 mA
4 ... 20 mA
4 ... 20 mA
Output voltage
Offset voltage
Load resistance
Output signal limit
Output current
Offset current
Load resistance
Status LED
0 ... 10 V
0 ... 10 V
max. 0.08 V
max. 0.08 V
≥1 KΩ
≥1 KΩ
approx. 13 V and. 24 mA
approx. 13 V and. 24 mA
0/4 ... 20 mA
0/4 ... 20 mA
max.150 µA
max.150 µA
≤ 600 Ω
≤ 600 Ω
green LED
green LED
ON–> OK; blinks –> signal out of range; OFF –> Error
ON–> OK; blinks –> signal out of range; OFF –> Error
Temperature coefficient
Response time (10 ... 90%)
Coordination of insulation acc. to DIN EN 50178, 04/98
(safe separation)
≤ 650 ppm/K
≤ 650 ppm/K
typ.700 ms
typ. 700 ms
Rated voltage
300 V
6 KV
lll
300 V
6 KV
lll
Surge voltage
Overvoltage category
Contamination class
2
2
Clearance and creepage distance
Test voltage
≥ 5.5 mm
4 kV eff
≥ 5.5 mm
4 kV eff
General
Supply
Supply voltage
21.6 Vdc...24 Vdc...26.4 Vdc
21.6 Vdc...24 Vdc...26.4 Vdc
Power consumption at rated voltage
Reverse polarity protection
50 mA at I = 20 mA
out
50 mA at I = 20 mA
out
yes
yes
Operating temperature range
Storage/transport
0 ... 50 ºC
0 ... 50 ºC
-20 ... +70 ºC
0 ... 25 A uc; 4 ... 20mA
92.4/112.4/22.5
150g
-20 ... +70 ºC
0 ... 5A uc; 4 ... 20 mA
92.4/112.4/22.5
150 g
Factory setting
Dimensions L/H/B (mm)
Weight
Approvals
CE, cUL
CE, cUL
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
Page 298 + 308
198
Current Monitoring
WAS2 CMA
WAZ2 CMA
WAVECONTROL
ꢀinput and output range
adjustable via DIP switch
ꢀno calibration required
ꢀcross-connectable voltage
supply via cross-connectors
ꢀtrue TRMS value measurements
ꢀhall sensor measurement
method
40/50/60A ac/dc
selectable with
analogue output
0 ... 20 mA/
4 ... 20 mA/
0 ... 10 V
Approvals:
Block diagram
Ordering data
Screw connection
Tension clamp connection
Technical data*
Input
Type
Cat. No.
Qty.
1
WAS2 CMA 40/50/60A uc
WAZ2 CMA 40/50/60A uc
8513330000
8526590000
1
Input current
40/50/60A uc selectable (without additional adjustment)
0 Hz - 2 kHz (True RMS to DC Converter)
1% (0Hz - 1KHz) Crest factor 3 FSR
2% (0Hz - 2KHz) Crest factor 5 FSR
Contact-free current monitoring using Hall sensor
Push-through connection
Input frequency
Accuracy
Measuring principle
Connection type
Pass through diameter
Measurement circuit voltage
8 mm
400 Vac, higher voltages dependent on wire insulation
Max. measuring circuit
Output
dependent on wire cross-section
Current/voltage selectable
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
Output voltage
Offset voltage
Load resistance
Output signal limit
Output current
Offset current
Load resistance
Status LED
0 ... 10V
max. 0.08 V
≥ 1 kΩ
approx. 13 V and. 24 mA
0/4 ... 20 mA
max.150 µA
≤ 600 Ω
green LED
ON–> OK; blinks –> signal out of range; OFF –> Error
Temperature coefficient
Response time (10 ... 90%)
Coordination of insulation acc. to DIN EN 50178, 04/98
(safe separation)
≤ 650 ppm/K
type 700 ms
Rated voltage
300 V
6 KV
lll
Surge voltage
Overvoltage category
Contamination class
2
Clearance and creepage distance
Test voltage
≥ 5.5 mm
4 kV eff
General
Supply
Supply voltage
21.6 Vdc...24 Vdc...26.4 Vdc
Power consumption at rated voltage
Reverse polarity protection
50 mA at I
yes
= 20 mA
out
Operating temperature range
Storage/transport
0 ... 50ºC
-20 ... +70ºC
Factory setting
0 ... 50 A uc; 4 ... 20 mA
92.4/112.4/22.5
150 g
Dimensions L/H/W (mm)
Weight
Approvals
CE, cUL
Dimensions and accessories see
* TU = 23 °C single module
Page 298 + 308
199
Current Monitoring
SMSI DC O
• For AC/DC
• With and without adjustable switching threshold
• Opto-coupler output
With adjustable switching threshold
Up to 50 mA
Up to 250 mA
Block diagram/ timing diagram
This series is particularly suitable for
monitoring small currents from
50 mA to 5 A.
The adjustable switching threshold
activates optionally one relay-or opto-cou-
pler output each.
Ordering data
Type
Cat. No.
Type
Cat. No.
SMSI 0.05 DC O 1157160000 SMSI 0.25 DC O 1156360000
Technical data
Measurement circuit voltage
Max. permissible current in measurement circuit
Rated consumption – (W)
Rated consumption ~ (VA)
Adjustable switching threshold
Hysteresis between turn-on and turn-off point
Activation time tA
10 V… 250 Vdc
70 mA
10 V… 250 Vdc
350 mA
200 mW
750 mW
–
–
1 mA…50 mA
0.5 % (50 mA)…5 % (1 mA)
< 10 ms
40 mA…250 mA
2% (250 mA)…10% (40 mA)
< 3 ms
Reaction time tR
< 10 ms
< 3 ms
Voltage drop at input
< 4 V
< 3 V
Output voltage
5 V…50 Vdc
100 mA
5 V…50 V–
100 mA
Max. continuous output current
Saturation voltage
≤ 1.3 V
≤ 1.3 V
Auxiliary voltage
Auxiliary voltage rated consumption
Auxiliary voltage rated data
Adjustable
threshold
switching
on
Storage temperature
–25 °C…+60 °C
–25 °C…+60 °C
Ambient temperature
switching
off
–, assembled without spacing on TS
–, assembled with ≥ 20 mm spacing on TS
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
Hysteresis
Coordination of insulation according to VDE, Draft 11/94
Overvoltage category, input
II
I
Overvoltage category, output
II
I
Overvoltage category, input 1-input 2,
Output 1-output 2, input-output
Contamination class
III
2
III
2
Relay
Dimensions and connection data
see page 306 + 307
Fig. V
Fig. V
200
SMSI AC O
With adjustable switching threshold
SMSI AC O
Current monitoring units with transistor output up to 5 A
SMSI AC
Current monitoring with indicator up to 5 A
up to 250 mA
Up to 2.5 A
without switching threshold
without switching threshold
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
SMSI 5 AC
1112060000
SMSI 0.25 AC O 1156460000 SMSI 2.5 AC O 1157360000 SMSI 5 AC O
1112160000 SMSI 5 AC O
8026930000
5…250 Vac
10 V…250 Vac
300 mA
10 V…250 Vac
2.8 A
5…250 Vav
5…250 Vac
1 A…5 A
-
1 A…5 A
1 A…5 A
-
–
–
-
-
1075 mVA
40 mA…250 mA
≤ 5%
250 mVA
-
-
-
0.2 A…2.2 A
≤ approx. 35%
≤ 55 ms
-
-
-
-
-
-
≤ 40 ms
≤ 10 ms
≤ 20 ms
< 200 mV
24 Vuc 10%
100 mA
< 3.2 V
≤ 10 ms
≤ 20 ms
< 200 mV
5…48 Vdc
100 mA
< 1.6 V
-
≤ 15 ms
≤ 20 ms
< 200 mV
< 4.3 V~eff (I = 250 mA)
5 V…50 V–
100 mA
< 100 mV~eff (I = 10 A)
5 V…50 V–
100 mA
≤ 1.3 V
≤ 1.3 V
24 Vuc 10%
550 mW–/1150 mVA~
23 mA–/47 mA~
–40 °C…+60 °C
–25 °C…+60 °C
–25 °C…+60 °C
–40 °C…+60 °C
–40 °C…+60 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
II
I
II
I
II
I
II
I
II
I
III
2
III
2
III
2
III
2
III
2
Fig. II
Fig. V
Fig. V
Fig. II
Fig. II
201
Current Monitoring
SMSI DC R
SMSI AC R
• For AC/DC
• Adjustable switching threshold
• Relay output
With adjustable switching threshold
With adjustable switching threshold
up to 250 mA
up to 250 mA
Ordering data
Type
Cat. No.
Type
Cat. No.
SMSI 0.25 AC R 1159960000
SMSI 0.25 DC R 1156660000
Technical data
Measurement circuit voltage
Max. permissible current in measurement circuit
Rated consumption ~ (VA)
Voltage drop at input
10 V…250 Vac
300 mA
10 V…250 Vdc
350 mA
1075 mVA (l = 250 mA)
≤ 3 V (I = 250 mA)
40 mA…250 mA~
≤ 5%
750 mVA (l = 250 mA)
≤ 3 V (I = 250 mA)
Adjustable switching threshold
Hysteresis between turn-on and turn-off point
Activation time tA
40 mA…250 mA–
2% (250 mA)<lHY<10% (40 mA)
≤ 25 ms
-
Reaction time tR
≤ 15 ms
≤ 12 ms
Recovery
-
-
Output voltage
250 V
250 V
Max. continuous output current
Auxiliary voltage
3 A
3 A
24 V~ 10%
250 mW/450 mVA
8 A
24 V~ 10%
250 mW/450 mVA
8 A
Rated consumption auxiliary voltage
Max. switching current
Contact
1 NO1)
1 NO1)
Contact material
AgNi, gold-flashed
AgNi, gold-flashed
Storage temperature
–25 °C…+60 °C
–25 °C…+60 °C
Ambient temperature
–, assembled without spacing on TS
–, assembled with ≥ 20 mm spacing on TS
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
Coordination of insulation to DIN VDE 0160,Draft 11/94
Overvoltage category, input, output
Overvoltage category, input1-input2,
Output1-output 2, input-output
II
II
III
2
III
2
Contamination class
Dimensions and connection data
see page 307
Fig. V
Fig. V
1) NC on request
202
Current Monitoring
SMSI AC R
With adjustable switching threshold
SMSI AC R
Current monitoring with relay output up to 5 A
up to 2.5 A
without switching threshold
Ordering data
Type
Cat. No.
Type
Cat. No.
SMSI 2.5 AC R 1156960000
SMSI 5 AC R
1112260000
Technical data
Measurement circuit voltage
Max. permissible current in measurement circuit
Rated consumption ~ (VA)
Voltage drop at input
10 V…250 Vac
3 A
10 V…250 Vac
1 A…5 A
250 mVA (I = 2.5 A)
< 0.1 V (I = 2.5 A)
0.2…2.2 A
≤ approx. 5%
≤ 45 ms
1 VA (I = 5 A)
< 1 VA (I = 5 A)
Adjustable switching threshold
Hysteresis between turn-on and turn-off point
Activation time tA
-
-
-
Reaction time tR
≤ 30 ms
-
Recovery
< 75 ms
-
Output voltage
250 V
250 V
Max. continuous output current
Auxiliary voltage
3 A
3 A
24 Vuc 10%
1000 mW
5 A
24 Vdc 10%
Rated consumption auxiliary voltage
Max. switching current
Contact
-
8 A
1 NO1)
1 NO1)
Contact material
AgNi, gold-plated 3 µm
AgNi, gold-plated 3 µm
–40 °C…+60 °C
Storage temperature
–40 °C…+60 °C
Ambient temperature
–, assembled without spacing on TS
–, assembled with ≥ 20 mm spacing on TS
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
Coordination of insulation to DIN VDE 0160,Draft 11/94
Overvoltage category, input, output
Overvoltage category, input1-input2,
Output1-output 2, input-output
II
II
III
2
III
2
Contamination class
Dimensions and connection data
see page 307
Fig. V
Fig. V
203
Voltage Monitoring
SMSU 24 R
SMSU 48 R
• Voltage monitoring from 18 to 299 V
• One and three phase version
• Adjustable switching threshold
Block diagram/ timing diagram
Ordering data
Type
Cat. No.
Type
Cat. No.
1157660000
SMSU 24 R
1156760000 SMSU 48 R
Technical data
Voltage monitoring range
(also Supply voltage)
18 Vdc…27 Vdc or
18 Vac…27 Vac/50 Hz
< 0.8 W
36 Vdc…53 Vdc or
36 Vac…53 Vac/50 Hz
< 1 W
Rated consumption – (W)
Rated consumption ~ (VA)
Adjustable switch-off threshold
Hysteresis/factory setting
Switching points
< 0.9 VA
< 1.5 VA
18 Vuc…24 Vuc
1%…10%/5%
–
36 Vuc…48 Vuc
1%…10%/5%
–
Activation time tA
< 4 s
< 2.5 s
Reaction time tR
< 300 ms
< 300 ms
Derating curve
a = assembled without spacing on mounting rail
b = assembled with ≥ 20 mm spacing on mounting rail
Adjustable
threshold
switching
on
Continuous
current
Ambient temperature
switching
off
Hysteresis
Max. output voltage
Max. switching current
Max. continuous output current
Contact
250 V~
250 V~
8 A
8 A
3 A
3 A
1 changeover contact
1 changeover contact
Contact material
AgNi 0.15 gold-flashed
2000 VA
AgNi 0.15 gold-flashed
2000 VA
Switching capacity (resistive load)
Fuse
Relay
Storage temperature
–40 °C…+60 °C
–40 °C…+60 °C
Ambient temperature
–, assembled without spacing on TS
–, assembled with ≥ 20 mm spacing on TS
Coordination of insulation to DIN VDE 0160,Draft 11/94
Overvoltage category, input, input 1-input 2, output
Overvoltage category, input-output, output 1-output 2
Contamination class
–25 °C…+50 °C
–25 °C…+60 °C
–25 °C…+50 °C
–25 °C…+60 °C
Dimensions and connection data see page 306
204
SMSU 110 R
SMSU 220 R
SMSU 260 R
SMSU 3x220 R
Three-phase with
SMSU 1–24 DC
Single-phase without
switching threshold
SMSU 1–230
AC/DC
adjustable switching threshold
Single-phase without
adjustable switching threshold
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
SMSU 24 DC
0555060000 SMSU 230 AC/DC 0555160000
SMSU 110 R
1157760000 SMSU 220 R
1157860000 SMSU 260 R
1160160000 SMSU
3x220 R, 2 NO
1156560000
3x220 R,1 NC./1 NO 1178760000
24 Vdc 10%
230 Vdc 10%
83 Vdc…121 Vdc or
83 Vac…121 Vac/50 Hz
< 1.6 W
165 Vac…253 Vac/50 Hz
200 V…299 Vac/50 Hz
165 V~…230 Vac 50 Hz
0.5 W
0.9 W
–
–
–
–
1.1 W
–
–
–
–
–
< 1.5 W
< 10 VA
< 10 VA
200 V…260 V
1%…15%/5%
–
9 VA (L3); 60 mVA (L 1/L 2)
83 Vuc…110 Vuc
1%…10%/5%
–
165 Vac…220 Vac
150 V~…205 V~
1%…15%/5%
–/7%
–
On: 18.5 V, off: 5 V
15 ms
On: 140 V–/130 V~, off: 70 V–/80 V~
–
–
–
< 4 s
< 3 s
< 2 s
< 3 s
< 4 s
< 80 ms
10 ms
< 300 ms
< 2 s
24 V– 10%
24 V– 10%
250 V~
250 V~
250 V~
250 V~
8 A
8 A
8 A
8 A
1 A
1 A
3 A
3 A
3 A
3 A
1 changeover contact
1 changeover contact
1 changeover contact
1 changeover contact
1 changeover contact
2 NO (115656)
1 NO/1 NC (117876)
AgCdO, gold-flashed
5x107 switching operations
2x105 switching operations
105 switching operations
–40 °C…+60 °C
AgNi, gold-flashed
106 switching operations
100 mA
AgNi, gold-flashed
106 switching operations
100 mA
AgNi 0.15 gold-flashed
2000 VA
AgNi 0.15 gold-flashed
2000 VA
AgNi 0.15 gold-flashed
2000 VA
–40 °C…+60 °C
–40 °C…+60 °C
–40 °C…+60 °C
–40 °C…+60 °C
–40 °C…+60 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+40 °C
–25 °C…+50 °C
–25 °C…+30 °C
–25 °C…+55 °C
–25 °C…+45 °C
–25 °C…+60 °C
–25 °C…+45 °C
–25 °C…+60 °C
–5 °C…+40 °C
–5 °C…+55 °C
II
III
2
205
Movement and Rotational Speed Monitoring
SMS
SIZA
Rotational speed monitoring
Block diagram
Ordering data
Description
Type
Cat. No.
SMS/SIZA
1110560000
Power supply with delayed turn-off relay output for three-condu-
cutor DC initiators (NPN or PNP).
The transformer supplies the initiator with 24 V DC. The initiator
signal activates the relay, at which time the adjustable turn-off
delay becomes effective. This module is particularly suitable for
monitoring cyclic movements, e.g, down-times monitoring of
conveyor drives, ventilators and pumps or stroke monitoring of
valves, die cutters and drilling heads.
A contact element actuates the initiator at regular intervals. If
these pulses cease, i.e. the proximity switch is continuously
actuated (t4-t6) or deactivated (t1-t3), the relay transmits a signal
after the set time has elapsed. During normal operation, the
time function bridges the gaps between regular pulses (t0-t2)
Technical data
Operating voltage
Initiator type/initiator voltage
Output voltage
230 Vdc +5 –15%
P or N switched/24 Vdc
250 V
Continuous current
Max. switching capacity (resistive load)
Contact
4 A
2000 VA
1 changeover contact
AgNi 0.15 gold-flashed
> 107 switching operations
0.5…5 s
Contact material
Mechanical service life
Time range
Coordination of insulation to VDE DIN 0160, draft11/94
Rated voltage
300 V
Rated surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
EMC
4 kV
III
2
≥ 3 mm
EN 50 081-1/50 082-2
Accessories and dimensions see page 307
Fig. VI
206
Namur Switch Amplifiers
EGV-Namur
EGV-Inverter
Block diagram
Ordering data
Description
Type
Cat. No.
Type
Cat. No.
EGV Namur
1120360000
EGV Inverter
1122460000
Switching amplifier for 2-wire Namur initiators with relay output.
This module inverts the switching function of electronic outputs.
Enables the use of economic Namur initiators with short design
lengths. This is particularly valid for areas where initiators are
subjected to heavy mechanical stresses, and often need to be
replaced. A potential-free NO contact is available on the output
side for switching larger ratings (2000 VA). The Namur initiator
can be directly connected to the module.
A PNP output is changed into an NPN output with the load con-
nected unilaterally against the positive potential (the negative
potential is switched through). An NPN output is changed into a
PNP output with the load connected unilaterally to the frame
potential (the positive potential is switched through).
The module reduces the inventory of sensors and electronic
switches with PNP/NPN outputs to a single type.
LED function indicators indicate switching statuses.
Technical data
Input voltage
24 Vdc 10%
approx. 8 Vdc
250 Vac/dc
24 Vdc 10% (closed circuit current < 10 mA)
24 Vdc 10% (switching threshold approx. 15 V)
Initiator type/initiator voltage
Output voltage, -current
Continuous current
Max. switching capacity (resistive load)
Contact
3 A
200 mA
2000 VA
1 NO
Contact material
AgNi 0.15 gold-flashed
> 107 switching operations
40 °C mounted
Mechanical service life
Ambient temperature
Coordination of insulation to VDE DIN 0160, draft11/94
Rated voltage
300 V
Rated surge voltage
Overvoltage category
Contamination class
Clearance and creepage distance
EMC
4 kV
III
2
≥ 3 mm
EN 50 081, EN 50 082, EN50 011
EN 50 081, EN 50 082, EN50 011
Accessories and dimensions see page 307
Fig. VI
Fig. V
207
Set Point Generator
EMA/SW 24
• Set point generator
• switchable –10.5 V/+10.5 V
Set point 1 or set point 2 can be switched to
the module’s output as required.
The changeover is performed safely separated
via the control input E1. The output voltage val-
ues (0…10.5 V) can be set using the spindle
operated potentiometers SW1 and SW2. The
control input E“ determines the polarity safely
separated
(–10.5 V … 0 V … +10 V).
Control input E1: 0 V = set point 1,
24 V = set point 2,
Control input E2: 0 V = positive set point,
24 V = negative set point
electronic changeover switch
Ordering data
Type
Cat. No.
EMA/SW
1172660000
Technical data
Input signal/measurement range
0=0 V, 1=+24 V
Control voltage
24 V 20 %
Max. input current
≤ 7 mA at 24 V
Display
Setting
each control input: red LED
via trimming potentiometer
25 rotations nom.
Output signal
Output
adjustable from –10.5 V…+10.5 V
Voltage output selection by E1/E2
max. 25 mA at Urated=24 V–
min. 400 Ω at Urated=24 V
Output current
Load resistance
Slew-Rate
0.168 V/µs
Supply voltage UB
Residual ripple
Reaction time
24 V– 20 %, 30 mA (RL= ∞)
30 mV/106 kHz (at Umax
rising 50 µs
)
decreasing 80 µs
Isolation voltage, voltage strength
Input/output/supply
1 kV-
Input-Output/TS
4 kVeff
Storage temperature
–20 °C…+70 °C
0 °C…+50 °C
Operating temperature
Insulation coordination according to EN 50 178
Overvoltage category
III
2
Contamination class
Accessories, dimensions and connection data see page 307
Fig. V
208
209
8-Bit Analogue/Digital Converters
RS/U-D8
RS/I-D 8
Hold function (H):
Enable function (E):
The converter can, for
The Enable circuit (E)
example, by means of the allows several converters,
hold function (H) be e.g. on an input card of a
matched to the cycle time PLC, to be switched on.
of a PLC. Holding and The Enable input (E) is
release of the conversion. connected internally to 0
The Hold input (H) is
internally connected to
0 V via a resistor.
In order to store the last
signal, the Hold input (H)
must be supplied with
24 V.
V via a resistor. In order to
make the connection to
the PLC, one converter
must be disconnected.
The other converters are
supplied with 24 V
(at least 12 V).
This causes the convert-
ers at the output to be
highly resistive.
Functions table (example)
Block diagram
Block diagram
Terminal
Digital volue/
PIN
Analog
voltage
digital
value
LSB
MSB
Analogue
voltage
E8 E7 E6 E5 E4 E3 E2 E1
0 V
0
0
0
0
-
0
0
0
0
-
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
-
0
1
0
1
-
-
-
-
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
1
0
1
+10 V
Type
Cat. No.
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
RS/U-D 8
1122361001
RS/U-D 8
1160361001 RS/I-D 8
1160561001 RS/I-D 8
1168561001
Technical data
Input signal
–10 V…+10 V
0…10 V
0…20 mA
4…20 mA
Max. input voltage
Max. input current
Input resistance
Max. limit frequency
Resolution
3.5 V
3.5 V
≤ 55 µA
≤ 25 µA
25 mA
25 mA
≥ 200 kΩ
5 kHz at Full-Scale (Sinus)1)
≥ 400 kΩ
≥ 51 Ω
5 kHz at Full-Scale (Sinus)1)
≥ 51 Ω
5 kHz at Full-Scale (Sinus)1)
5 kHz at Full-Scale (Sinus)1)
62.5 µA c 1 LSB
78 mV c 1 LSB
39 mV c1 LSB
78 µA c1 LSB
8 Bit (1 Bit prefix)
≤ 25 mA (as source)
approx. 17 V cH, 0 V cL
MSB: H c positive, L c negative
1 LSB
Output signal
Output current
Output level
Prefix
8 Bit
8 Bit
8 Bit
≤ 25 mA (as source)
approx. 17 V cH, 0 V cL
≤ 25 mA (as source)
approx. 17 V cH, 0 V cL
≤ 25 mA (as source)
approx. 17 V cH, 0 V cL
Transmission error
Conversion time
Supply
1 LSB
1 LSB
1 LSB
≤ 4 µs
≤ 4 µs
≤ 4 µs
≤ 4 µs
24 V–, 20 %, 35 mA
(plus output current)
24 V–, 20 %, 35 mA
(plus output current)
24 V–, 20 %, 35 mA
(plus output current)
24 V–, 20 %, 35 mA
(plus output current)
Connection arrangement
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 8
Terminal 9
MSB
Enable2)
Terminal 8
Terminal 9
MSB
Enable2)
Terminal 8
Terminal 9
MSB
Enable2)
Terminal 8
Terminal 9
MSB
Enable2)
Terminal 10 Hold
Terminal 10 Hold
Terminal 10 Hold
Terminal 10 Hold
Hold function:
Hold function:
Hold function:
Hold function:
High c+24 V cstorage of last
converted value
High c+24 V cstorage of last
converted value
High c+24 V cstorage of last
converted value
High c+24 V cstorage of last
converted value
Low c0 V cfree conversion
Low c0 V cfree conversion
Low c0 V cfree conversion
Low c0 V cfree conversion
–40 °C…+85 °C
0 °C…+50 °C
Storage temperature
Operating temperature
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
EMC EN 50 081-1/50 082-2
1) 1 LSB-Accuracy
2) Enable:24 V = tristate
0 V = free conversion
210
8-Bit Digital/Analogue Converters
RS/D 8-U
RS/D 8-I
Block diagram
Block diagram
Pin assignment
Pin assignment
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
RS/D 8-U
1160761001
RS/D 8-U
1123361001
RS/D 8-I
1165861001 RS/D 8-I
1169261001
Technical data
Input signal
8 Bit
8 Bit (1 Bit prefix)
8 Bit
8 Bit
Max. input voltage
Max. input current
Input resistance
Prefix
5…24 V (typ. 24 V)
2.5 mA
5…24 V (typ. 24 V)
2.5 mA
5…24 V (typ., max. 30 V) cH
50 kΩ per input
5…24 V (type., max. 30 V) cH
50 kΩ per input
50 kΩ per input
50 kΩ per input
MSB: H cpositive, L cnegative
78 mV c 1 LSB
Resolution
39 mV c1 LSB
78 µA c1 LSB
62.5 µA c1 LSB
Output signal
Output current
Offset
0…10 V
–10 V…+10 V
≤ 10 mA max. current
≤ 20 mV
0…20 mA
4…20 mA
≤ 10 mA
0…20 mA (as source)
max. 0.08 mA
≤ 500 Ω
4…20 mA (as source)
4 mA
≤ 20 mV
Load resistance
Transmission error
Conversion time
Supply
≥ 1 kΩ
≥ 1 kΩ
≤ 500 Ω
1 LSB
1 LSB
1 LSB
1 LSB
≤ 30 µs
≤ 30 µs
≤ 30 µs
≤ 30 µs
24 V–, 20 %, 25 mA
(plus output current)
24 V–, 20 %, 25 mA
(plus output current)
24 V–, 20 %, 25 mA
(plus output current)
24 V–, 20 %, 25 mA
(plus output current)
Connection arrangement
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 8
Terminal 9
MSB
Hold
Terminal 8
Terminal 9
MSB
Hold
Terminal 8
MSB
Hold
0 V
Terminal 8
Terminal 9
MSB
Hold
Terminal 9
Terminal 10 0 V
Terminal 10 0 V
Terminal 10
Hold function:
Terminal 10 0 V
Hold function:
Hold function:
Hold function:
High c+24 V cstorage of
last converted value
Low c0 V cfree conversion
High c+24 V cstorage of
last converted value
Low c0 V cfree conversion
High c+24 V cstorage of
last converted value
High c+24 V cstorage of
last converted value
Low c0 V cfree conversion
Low c0 V cfree conversion
Storage temperature
Operating temperature
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
EMC EN 50 081-1/50 082-2
211
12-Bit Analogue/Digital Converters
Hold function (H):
The converter can, for
example, by means of the
hold function (H) be
matched to the cycle time
of a PLC. Holding and
release of the conversion.
The Hold input (H) is
internally connected to
0 V via a resistor.
In order to store the last
signal, the hold input (H)
must be supplied with
24 V.
Functions table (example)
Block diagram
Block diagram
Digital volue/
digital
Terminal
PIN
Analog
current
Analog
current
value
MSB
LSB
12 11 10
9
0
0
0
0
8
0
0
0
0
7
0
0
0
0
6
0
0
0
0
5
0
0
0
0
4
0
0
0
0
3
0
0
0
0
2
0
0
1
1
-
1
4 mA
0
0
0
0
-
0
0
0
0
-
0
0
0
0
0
1
0
1
-
-
-
-
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
1
1
0
1
20 mA
Ordering data
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
RS/U-D 12
1168261001
RS/U-D 12
1168361001 RS/I-D 12
1168461001 RS/I-D 12
1169161001
Technical data
Input signal/measurement range
–10…+10 V
15 V
0…10 V
0…20 mA
4…20 mA
Max. input voltage
Max. input current
Input resistance
Prefix
15 V
30 mA
30 mA
100 kΩ
100 kΩ
500 Ω
500 Ω
MSB: H cpositive, L cnegative
4.88 mV c1 LSB
Resolution
2.44 mV c1 LSB
4.9 µA c1 LSB
12 Bit
4 µA c1 LSB
Output signal
Output current
12 Bit (1 Bit prefix)
≤ 25 mA (as source)
24 V cH, 0 V cL
12 Bit
12 Bit
≤ 25 mA (as source)
24 V cH, 0 V cL
≤ 25 mA (as source)
24 V cH, 0 V cL
≤ 25 mA (as source)
Output level
24 V cH, 0 V cL
Load resistance
Transmission error
Conversion time
Temperature coefficient
Supply
1 LSB
≤ 50 µs
1 LSB *
24 V–, 20 %
4 W
1 LSB
≤ 50 µs
1 LSB *
24 V–, 20 %
4 W
1 LSB
≤ 50 µs
1 LSB *
24 V–, 20 %
4 W
1 LSB
≤ 50 µs
1 LSB *
24 V–, 20 %
4 W
Max. power loss
Connection arrangement
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
High c+24 V cstorage of
digital signal
High c+24 V cstorage of
digital signal
High c+24 V cstorage of
digital signal
High c+24 V cstorage of
digital signal
Low c0 V cenabling the
conversion cycle
Low c0 V cenabling the con- Low c0 V cenabling the con- Low c0 V cenabling the con-
version cycle
version cycle
version cycle
Storage temperature
Operating temperature
–40 °C…+80 °C
0 °C…+50 °C
–40 °C…+80 °C
0 °C…+50 °C
–40 °C…+80 °C
0 °C…+50 °C
–40 °C…+80 °C
0 °C…+50 °C
EMC EN 50 081-1/50 082-2
212
12-Bit Digital/Analogue Converters
Block diagram
Block diagram
Ordering data
Type
RS/D 12-U
Cat. No.
Type
Cat. No.
Type
Cat. No.
Type
Cat. No.
1160861001
RS/D 12-U
1166161001
RS/D 12-I
1166061001
RS/D 12-I
1165961001
Technical data
Input signal/measurement range
12 Bit (1 Bit as prefix)
12 Bit
12 Bit
12 Bit
Max. input voltage
Input current, Inom
Input resistance
Prefix
24 V–, 20 %
4.2 mA
24 V–, 20 %
4.2 mA
24 V–, 20 %
4.2 mA
24 V–, 20 %
4.2 mA
5.7 kΩ
5.7 kΩ
5.7 kΩ
5.7 kΩ
MSB: H cpositive, L cnegative
4.88 mV c1 LSB
Resolution
2.44 mV c1 LSB
4.9 µA c1 LSB
4 µA c1 LSB
Output signal
Output current
–10 V…+10 V
0 V…10 V
0…20 mA
4…20 mA
≤ 10 mA
≤ 10 mA
0…20 mA (as source)
4…20 mA (as source)
Output level
Load resistance
Transmission error
Conversion time
Temperature coefficient
Supply
≥ 1 kΩ
≥ 1 kΩ
1 LSB
≤ 4 µs
≤ 500 Ω
≤ 500 Ω
1 LSB
1 LSB
1 LSB
≤ 4 µs
≤ 4 µs
≤ 4 µs
100 ppm from FSR/°C
24 V–, 20 %, 40 mA
100 ppm from FSR/°C
24 V–, 20 %, 40 mA
100 ppm from FSR/°C
24 V–, 20 %, 60 mA
100 ppm from FSR/°C
24 V–, 20 %, 60 mA
Max. power loss
Connection arrangement
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 1
LSB
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
Terminal 12 MSB
Hold function:
High c+24 V cstorage of
analogue signal
High c+24 V cstorage of
analogue signal
High c+24 V cstorage of
analogue signal
High c+24 V cstorage of
analogue signal
Low c0 V cenabling the
conversion cycle
Low c0 V cenabling the
conversion cycle
Low c0 V cenabling the
conversion cycle
Low c0 V cenabling the
conversion cycle
Storage temperature
Operating temperature
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
–40 °C…+85 °C
0 °C…+50 °C
EMC EN 50 081-1/50 082-2