4-1415419-0 [TE]
Rast 5 Power Relay 419 11 (EA/..); RAST 5功率继电器419 11 ( EA / ..)型号: | 4-1415419-0 |
厂家: | TE CONNECTIVITY |
描述: | Rast 5 Power Relay 419 11 (EA/..) |
文件: | 总3页 (文件大小:257K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
General Purpose Relays
SCHRACK
Rast 5 Power Relay 419 11 (EA/..)
n
n
n
n
n
n
n
2 pole 16 A
Safety mains insulation
Quick connect terminals 6.3 x 0.8 mm
Contact gap > 3 mm
4 kV / 8 mm coil-contact
Snap or screw mounting
Product in accordance to IEC60335-1
Applications
Industrial and domestic appliances, heating controls,
absolute safe power supply disconnection
F0255-CI
Approvals
V
REG.-Nr. 5064 ÜG,
Z
E214024
Technical data of approved types on request
Contact data
Contact configuration
2 NO
bifurcated contacts
full disconnection
250 / 400 VAC
16 A
Contact set
Type of interruption
Rated voltage / max. switching voltage AC
Rated current
Limiting making capacity, max 4 s, duty factor 10%
Contact material
Contact gap
Rated frequency of operation with / without load
25 A
AgCu3
> 3 mm
15 / 600 min-1
Contact ratings
Type
Contact Load
Ambient
temp. [°C]
Cycles
IEC 61810
0419 .. 03
0419 .. 04
0419 .. 03
0419 .. 12 & 13 2 NO
0419 .. 12 & 13 2 NO
0419 .. 12 & 13 2 NO
2 NO
2 NO
2 NO
16 A, 250 VAC, cosϕ=1
85°C
85°C
85°C
85°C
85°C
85°C
250x103
250x103
6x103
12 A, 250 VAC, cosϕ=1
20 A, 250 VAC, cosϕ=1
16 A, 250 VAC, cosϕ=1
12 A, 400 VAC, cosϕ=1
20 A, 250 VAC, cosϕ=1
250x103
250x103
6x103
Coil data
Rated coil voltage range DC coil
AC coil
6...60 VDC
24...400 VAC
1 / 2
Operative range to IEC 61810 DC coil / AC coil
Coil versions, DC-coil
Coil
Rated
voltage
VDC
6
Operate
voltage
VDC
3.5
Release
voltage
VDC
0.4
Coil
resistance
Ohm
50+10%
150+10%
200+10%
800+10%
Rated coil
power
mW
code
10
11
12
13
720
10
6.0
0.7
667
12
24
7.5
15.0
0.9
1.8
720
720
Coil versions, AC-coil
Coil
code
Rated
voltage
VAC
Operate
voltage
VAC
Release
voltage
VAC
Coil
resistance
Ohm
4050+10%
4500+10%
850+10%
Rated coil
power
VA
01
200.50 / 60 Hz
03 220..240.50 / 60 Hz 187.0
160.0
15.0
2.2
16.0
2.2
04 100..120.50 / 60 Hz
80.0
7.0
2.2
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request
1
Datasheet Rev. IJ1
Issued 2009/10
www.tycoelectronics.com
www.schrackrelays.com
Dimensions are in mm unless
otherwise specified and are
shown for reference purposes
only.
Product specification
processing information only
to be used together with the
'Definitions' section in the cat-
alogue or at schrackrelays.com
in the ‘Schrack’ section.
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
Specifications subject to
change.
General Purpose Relays
SCHRACK
Rast 5 Power Relay 419 11 (EA/..) (Continued)
Insulation
Dimensions
Dielectric strength coil-contact circuit
open contact circuit
4000 Vrms
2000 Vrms
4000 Vrms
W 6 / 8 mm
IIIa
adjacent contact circuits
Clearance / creepage coil-contact circuit
Material group of insulation parts
Tracking index of relay base
Insulation to IEC 61810-1
Type of insulation coil-contact circuit
open contact circuit
PTI 250
reinforced
full disconnection 3 mm
adjacent contact circuits
Rated insulation voltage
reinforced
250 V
3
230 / 400 V
III
Pollution degree
Rated voltage system
Overvoltage category
Other data
Mechanical endurance DC-coil
2x106 cycles
AC-coil
Material
0,5x106 cycles
RoHS - Directive 2002/95/EC
Environment
Ambient temperature range
compliant as per product date code 0349
-20...+85°C
Vibration resistance (function) NO (5...500Hz)
Shock resistance (destruction)
Category of protection
2 g
80 g
S0470-A
RTI - dust protected
Processing
Mounting
Relay weight
Packaging unit
snap or screw mounting
92 g
50 pcs
2
Datasheet Rev. IJ1
Dimensions are in mm unless
otherwise specified and are
shown for reference purposes
only.
Product specification
processing information only
to be used together with the
'Definitions' section in the cat-
alogue or at schrackrelays.com
in the ‘Schrack’ section.
Issued 2009/10
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
www.tycoelectronics.com
www.schrackrelays.com
Specifications subject to
change.
General Purpose Relays
SCHRACK
Rast 5 Power Relay 419 11 (EA/..) (Continued)
Product key
Typical product key
0419
1
1
03
0
1
00
Type
0419 Rast 5 Power Relay 419 11 (EA/..)
Mounting
1
2
3
Snap mounting, 1.0 mm panel
Snap mounting, 1.5 mm panel
Screw mounting
Version
1
2
2 coil connectors
3 coil connectors
Coil
Coil code: please refer to coil versions table
Contact material
AgCu 3
Contact connectors
Silver plated
0
1
Version
00 Standard
Other types on request
Product key
Version
Snap Mounting
1.0 mm plate
Cont-material Cont.configuration
Coil
AC-coil
DC-coil
Coil
Part number
3-1415419-5
4-1415419-0
4-1415419-2
4-1415419-9
5-1415419-5
0419 11 0301 00
0419 11 1201 00
0419 11 1301 00
0419 31 0301 00
0419 31 1301 00
AgCu3
2 NO
230 VAC
12 VDC
24 VDC
230 VAC
24 VDC
contacts
Screw Mounting
AC-coil
DC-coil
3
Datasheet Rev. IJ1
Issued 2009/10
www.tycoelectronics.com
www.schrackrelays.com
Dimensions are in mm unless
otherwise specified and are
shown for reference purposes
only.
Product specification
processing information only
to be used together with the
'Definitions' section in the cat-
alogue or at schrackrelays.com
in the ‘Schrack’ section.
according to IEC 61810-1.
Product data, technical para-
meters, test conditions and
Specifications subject to
change.
相关型号:
©2020 ICPDF网 联系我们和版权申明