25-000 [TE]
WILMAR™ Protective Relays - 25-000 Series; 丰益?保护继电器 - 25-000系列![25-000](http://pdffile.icpdf.com/pdf1/p00124/img/icpdf/25-000_684812_icpdf.jpg)
型号: | 25-000 |
厂家: | ![]() |
描述: | WILMAR™ Protective Relays - 25-000 Series |
文件: | 总1页 (文件大小:62K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Frequency Sensitive Relays
WILMAR™ Protective Relays – 25-000 Series
Function:
81 O/U
• ANSI/IEEE C37.90-1978
The output contacts of frequency relays are ener-
gized when the frequency exceeds the adjustable set
point. Overfrequency and underfrequency relays are
available in 50, 60 and 400Hz. Combination over/
underfrequency “band pass” relays are also avail-
able. These are energized at rated frequency and de-
energized during overfrequency or underfrequency
conditions. Frequency Differential relays are ener-
gized above the preset frequency. The pick-up and
drop-out frequency settings are independently ad-
justable.
#6 - 32 STUDS
6 PLACES
4 1/
2
Operation:
The normally open contacts close, and the normally
closed contacts open, at nominal frequency. The
contacts are de-energize at underfrequency,
overfrequency or no input voltage.
3 13
/
16
PART NUMBER SELECTION
11
/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
PART NUMBER SELECTION
Part Number
25-000 Series
120 VAC
Sample Part No.
Type:
25-050X
Input Voltage (±10%) ......................
Frequency Range (adjustable) ........
Trip Points ........................................
Temperature Range .........................
Temperature Drift.............................
Voltage Drift .....................................
Contact Ratings ................................
Output Contacts ...............................
25 - Over/Underfrequency
See Part Number Selection
Screwdriver adjustable
-20oC to +85oC
Frequency Range
050 =
Under
Over
40-50 Hz
50- 60 Hz
50-60 Hz
60-70Hz
400-450Hz
060 =
400 =
350- 400 Hz
Mounting Options
X = Flange
blank = Stud
± 1% frequency error over temperature range
± 1% frequency error input voltage variation of ± 10%
5 Amp resistive at 120 VAC or 28VDC
One set N.O., One set N.C.
Consult factory for additional models.
Notes:
1.
2.
3.
The contacts are shown in the de-energized position.
Remove screws for access to the underfrequency and overfrequency trip adjustments.
Clockwise rotation of the adjustment potentiometer will raise the frequency trip points.
4 2
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
相关型号:
©2020 ICPDF网 联系我们和版权申明