3200W 3-Phase Input Industrial Power Supplies
The TPS3000 series industrial AC-DC power supplies offer output power up to 3,200W in a 2U high package with 3 phase supply input. Features include voltage
and current programming, remote on/off, remote sense, a standby supply, PMBusTM communication, built in ORing FET and wide operating temperature range of
-40°C to +70°C. The TPS3000 is also designed to meet MIL-STD-810F vibration and shock.
Features
Benefits
• 400/440/480Vac (Nominal) 3 Phase Delta or Wye
• Fully Regulated, Wide Range Voltage Adjustment
• Voltage and Current Programming
• -40°C (start up) to +70°C Operation
• 92% Typical Efficiency
• Global Use
• Versatile Application
• Flexible Control and Adjustment
• Suitable for Rugged Environments
• Less Energy Used
• PMBusTM Communication
• Remote Output Programming and Monitoring
• Suitable for N + 1 Redundancy
• Built in ORing FET for Parallel Operation
Model Selector
Nominal Output
Voltage (V)
Adjustment
Maximum
Current (A)
125
Maximum
Power (W)
3000
Max
Current (A) (2)
133.3
Maximum
Power (W) (2)
3200
Model
TPS3000-24
TPS3000-48
Range (V) (1)
19.2 - 28.5
38.4 - 56.5
24
48
66.7
3200
66.7
3200
*Wider range adjustment as stated on the UL safety files are possible, although some parameters might not meet some of the listed specifications.
Related Products
Type
Part Number
RTMN-5020
Description
EMC filter
High attenuation 20A 500Vac 3-phase input two stage filter
Specifications
Model
TPF3000
Input
Input Voltage range
Input Frequency
Vac
Hz
A
350 - 528, Delta or Wye 3 phase (Note: Safety certified for 400-480Vac only)
47 - 63 (Note: Safety certified for 50 to 60Hz only)
6 per phase (steady state)
Input Current (At nominal Vin)
Inrush Current at 400-480Vac (Cold Start)
Dropped Phase Power
Leakage Current
A
<15 per phase (excluding initial filter capacitor charging <2ms)
Output Power 1290; output power increases with input voltage
<3
W
mA
-
Power Factor (400-480Vac)
Harmonics
0.92 typical at rated load, nominal Vin
Not applicable
-
Hold Up Time (typ)
ms
%
-
>10 at 80% of rated current, nominal input/output voltage
92
Efficiency (Typical)
Conducted & Radiated EMI
Safety Certifications and Markings
Voltage Dips
EN55022 Class A, FCC part 15 Class-A
IEC/UL/CSA/EN62368-1, 60950-1, CE Mark and UKCA
SEMI F47-0706
-
-
1
TPS3000 Series
Immunity
Test
Standard
Test Level
Criteria
B
Notes
±8 kV air discharge,
±4 kV contact discharge
3 V/m from 80-1000 MHz
(80% AM at 1kHz)
ESD
EN61000-4-2
Radiated Susceptibility
Electrical Fast Transient Burst
EN61000-4-3
EN61000-4-4
A
B
B
A
Power line pulses of ± 1 kV;
I/O line pulses of ± 0.5 kV
±2kV common mode,
±1kV differential mode
3 Vrms, 150 kHz - 80 MHz
(80% AM at 1kHz)
Surge
EN61000-4-5
EN61000-4-6
See Immunity Data
Conducted Susceptibility
Inductive loop at 50 Hz
to 1 amp (rms) per meter
Magnetic fields
EN61000-4-8
A
Voltage Dips and
Input Interruptions
Voltage Dips of 30% and
EN61000-4-11
B & C
>95%; Interruptions of >95%.
2
TPS3000 Series
Specifications
Model
TPS3000
Output
Line Regulation
%
<0.25
<0.5
Load Regulation
%
Total Regulation
%
<1.75
Warm Up Drift
%
<0.15
Temperature Stability
Temperature Coefficient
Ripple & Noise (pk-pk) (Max)
Minimum Load
-
0.05% of rated Vout for 8hrs after 30min warmup. Constant line, load, & temp.
200
ppm/°C
mV
A
%
%
-
24V model: 130, 48V model: 260
0.5 minimum
Overcurrent Protection
Overvoltage Protection
Overtemperature Protection
Fan Fail
Adjustable (70-105 of maximum rated current). Constant current style.
115 of output voltage set point (tracking). Cycle AC or use the remote on/off to reset
Internal thermostat. Automatic reset
-
Blocked or fan failure detection. Cycle AC input or use PMBus to reset
Compensates for a total of 1V cable drop
Remote Sense
-
Remote On/Off
-
Enable or Inhibit (switch selectable)
Voltage Programming
Overcurrent Programming
DC Good
-
0 - 5V external voltage adjusts the output from Vout max to Vout min
0 - 5V external voltage adjusts the current limit from Iout max to Iout min
Open Collector, max sink current 5mA, ON when output is above 85 to 95% of output set point (tracking)
Open Collector, max. sink current 5mA; ON when AC input is above 340Vac and unit is enabled
Open collector, max. sink current 5mA; OFF (open) normal operation; strobing when input phase missing.
11.2 - 12.5V, 0.3A (200mVp-p ripple and noise)
-
-
AC Fail
-
Dropped Phase Warning
Standby Voltage
-
-
Indicators
-
Green LEDs indicates DC is OK and AC is ON. Blinking red/green during dropped phase (Load >20%)
Single wire current share, 10% accuracy up to 8 units. Power derated 10% of rated.
See installation manual
Parallel Operation
Series Operation
Environmental
Operating Temperature (-40°C start-up)
-
-
°C
-10 to +50, derate 2%/C from 50°C to 60°C, and 2.5%/C from 60 to 70
(At <-10C a 20 min warm-up is needed)
Storage Temperature
Humidity (non condensing)
Pollution Degree
Cooling
°C
-40 to +85
%RH
10 - 90
-
PD 2
Internal variable speed fan
-
m
-
Altitude
4,000
Withstand Voltage (For 1 minute)
Isolation Resistance
Vibration
Input to Ground 2,000Vac, Input to Output 3,000Vac, Output to Ground 500Vdc
>100 at 25°C, 70%RH
MΩ
-
MIL-STD-810F, Method 514.5, Proc I, Category 4, 10
MIL-STD-810F, Method 516.5, Procedure I, IV & VI
Shock
-
Other
Weight (Typ)
g
3,700
Size (WxHxD)
mm
107 x 85 x 324 (excluding output busbars)
4.21 x 3.35 x 12.76 (excluding output busbars)
180,000. Method 1, Ground Benign, 25C, nominal input
3
Size (WxHxD)
Inches
Hours
Years
MTBF - Telcordia SR-332 issue 3
Warranty
3
TPS3000 Series
PMBus Functions
Derating Curve
Output Voltage Monitoring
Output Current Monitoring
Internal Temperature Monitoring
Remote On/Off Programming
Remote Voltage Programming
Remote Overcurrent Programming
Fault Clearing
Reading Manufacturing Related Data
Notes:
See website for detailed specifications, test methods and installation manual
(1) A minimum load of 0.5A is required to maintain regulation and ripple spec throughout the output voltage adjustment range.
(2) Rating at nominal output voltage only
Outline Drawings & Pin Out
4
TPS3000 Series
TDK-Lambda France SAS
TDK-Lambda Americas
Tel: +33 1 60 12 71 65
Tel: +1 800-LAMBDA-4 or 1-800-526-2324
tla.powersolutions@tdk.com
www.us.lambda.tdk.com
tlf.fr.powersolutions@tdk.com
www.emea.lambda.tdk.com/fr
Italy Sales Office
Tel: +39 02 61 29 38 63
tlf.it.powersolutions@tdk.com
www.emea.lambda.tdk.com/it
TDK Electronics do Brasil Ltda
Tel: +55 11 3289-9599
sales.br@tdk-electronics.tdk.com
www.tdk-electronics.tdk.com/en
Netherlands
tlf.nl.powersolutions@tdk.com
www.emea.lambda.tdk.com/nl
TDK-Lambda Germany GmbH
Tel: +49 7841 666 0
tlg.powersolutions@tdk.com
TDK-Lambda Corporation
Tel: +81-3-6778-1113
www.jp.lambda.tdk.com
www.emea.lambda.tdk.com/de
TDK-Lambda (China) Electronics Co. Ltd.
Tel: +86 21 6485-0777
tlc.powersolutions@tdk.com
www.lambda.tdk.com.cn
Austria Sales Office
Tel: +43 2256 655 84
tlg.at.powersolutions@tdk.com
TDK-Lambda Singapore Pte Ltd.
Tel: +65 6251 7211
tls.marketing@tdk.com
www.sg.lambda.tdk.com
www.emea.lambda.tdk.com/at
Switzerland Sales Office
Tel: +41 44 850 53 53
tlg.ch.powersolutions@tdk.com
www.emea.lambda.tdk.com/ch
TDK India Private Limited, Power Supply Division
Tel: +91 80 4039-0660
mathew.philip@tdk.com
www.sg.lambda.tdk.com
Nordic Sales Office
Tel: +45 8853 8086
tlg.dk.powersolutions@tdk.com
www.emea.lambda.tdk.com/dk
TDK-Lambda UK Ltd.
Tel: +44 (0) 12 71 85 66 66
tlu.powersolutions@tdk.com
www.emea.lambda.tdk.com/uk
TDK-Lambda Ltd.
Tel: +9 723 902 4333
tli.powersolutions@tdk.com
www.emea.lambda.tdk.com/il-en
For Additional Information, please visit
https://product.tdk.com/en/power/
TPS3000_Datasheet_ 260827 April 7th, 2023 V3
5
TPS3000 Series
相关型号:
©2020 ICPDF网 联系我们和版权申明