ED-DPI [SYSTEMSENSOR]

Intelligent Duct Smoke Detectors; 智能管道烟雾探测器
ED-DPI
型号: ED-DPI
厂家: SYSTEMSENSOR ADVANCED IDEAS.    SYSTEMSENSOR ADVANCED IDEAS.
描述:

Intelligent Duct Smoke Detectors
智能管道烟雾探测器

文件: 总4页 (文件大小:256K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
H V A C  
S Y S T E M S  
M O N I T O R I N G  
Series  
Intelligent  
Duct Smoke Detectors  
Intelligent Model Available  
ED-DPR: Duct Housing  
ED-DP(I): Duct Sensor Head  
*I denotes isolator version  
Product Overview  
The System Sensor EclipseSeries photoelectric air duct smoke detectors are capable of  
sensing smoke in air velocities from 500 to 4,000 feet per minute (2.54 to 20.32 m/sec).  
Air velocity rating from 500 to 4000 feet  
per minute (2.54 to 20.32 m/sec.)  
Operates from the control panel  
communication line  
The Eclipse Series ED-DPR duct housing can accommodate either the ED-DP or ED-DPI  
Intelligent Photoelectric Sensor. The twist-in, twist-out heads allow for quick and easy  
cleaning or application changes without removing the duct housing.  
Continuous sensitivity monitoring from  
the panel  
Intelligent photo isolator or non-isolator  
heads with twist-in/twist-out removal  
The Eclipse Series Detector samples air currents passing through a duct and gives  
dependable performance for shutdown of fans, blowers, and air conditioning systems,  
preventing the spread of toxic smoke and fire gases through the protected area.  
Easy to clean  
UL recognized field-replaceable  
power boards  
These intelligent sensors communicate and are continuously monitored through the com-  
munication line. Detector sensitivity changes caused by dirt, temperature, or humidity  
are reported to the panel, allowing compensation algorithms to maintain the sensor’s set  
sensitivity. An advance indication at the panel specifies the sensor address, allowing for  
selected maintenance to be performed as needed.  
Transparent cover for convenient  
visual inspection  
UL 268A listed  
3-year warranty  
Has outputs for remote LED display,  
remote test  
Remote alarm annunciation can be accomplished by using the RA400Z Remote  
Annunciator or the RTS451 or RTS451KEY Remote Test Station. Both these devices  
allow testing of the detector from a remote location.  
Requires com line power only  
Powered outputs for remote LED, and  
remote test and sounder  
The Eclipse Series is designed for simplified installation and easy maintenance.  
Remote test station and remote  
annunciator accessories  
WARNING: Duct smoke detectors have specific limitations.  
DUCT SMOKE DETECTORS ARE:  
NOT a substitute for an open area smoke detector,  
NOT a substitute for early warning detection, and  
NOT a replacement for a building’s regular fire detection system.  
Refer to NFPA 72 and 90A for additional duct smoke detector application information.  
APPROVED  
S911  
Architect/Engineer Specifications  
The duct smoke detector shall be a System  
Sensor Model ED-DPR Intelligent Duct  
Smoke Detector to be used with com-  
patible control panels. The duct smoke  
detector shall be UL listed per UL 268A,  
Standard for Smoke Detectors for Duct  
Applications, specifically for use in air  
handling systems. The detector shall oper-  
ate in air velocities from 500 to 4000 feet  
per minute. The detector housing shall be  
equipped with an integral mounting base  
capable of accommodating either the ED-  
DP or ED-DPI photoelectric detector head. due effects, thereby reducing maintenance  
It shall be capable of remote testing from  
the RTS451 or RTS451KEY Remote Test  
Station. The duct smoke detector housing  
shall incorporate an airtight smoke cham-  
ber in compliance with UL 268A. The  
housing shall be capable of mounting to  
either rectangular or round ducts without  
adapter brackets. An integral filter system  
shall be included to reduce dust and resi-  
and servicing. Sampling tubes shall be eas-  
ily installed after the housing is mounted  
to the duct by passing through the duct  
housing. Terminal connections shall be of  
the strip and clamp method suitable for  
14-18 AWG wiring.  
Wiring diagram for ED-DPR Duct Smoke Detector using a UL listed control panel  
(+) COM LINE  
TO REST OF SYSTEM  
SLC  
+
1
2
3
1
2
3
6
7
8
9
10 11 12 13 14  
1
2
3
4
5
(–) COM LINE  
TO REST OF SYSTEM  
3
1
2
SLC  
-
OPTIONAL RETURN LOOP  
Note: For terminals 9 through 14, normally closed  
and normally opened relay positions are  
defined with product in reset condition, not  
in alarm.  
Wiring diagram for ED-DPR Duct Smoke Detector with optional RA400Z  
6
4
(+)  
(–)  
(+)  
(–)  
RED  
DUCT DETECTOR  
RA400Z  
REMOTE  
ANNUNCIATOR  
Break Tab on RA400Z for use with ED-DPR.  
Wiring diagram for ED-DPR Duct Smoke Detector with RTS451/RTS451KEY  
1
5
RTS451/  
451KEY  
ALARM  
(LED)  
2
GROUND  
4
8
4
TEST (+)  
TEST (–)  
TEST (+)  
5
TEST (–)  
7
DUCT DETECTOR  
RTS451/RTS451KEY  
REMOTE TEST STATION  
ED-DPR Specifications  
Current Requirements (using no accessories)  
Power supply voltage  
Max. standby current  
Max. alarm current  
Alarm response time  
Power up time  
14–30VDC  
360 µA max.  
7 mA max. @ 24VDC (LEDs on)  
30 sec.  
2 sec.  
Self test initiation time 1 sec.  
Relay Contact Ratings (Each set of Form C Contacts)  
CURRENT RATINGS  
MAXIMUM VOLTAGE  
30VDC  
LOAD DESCRIPTION  
Resistive  
APPLICATION  
Non Coded  
Coded  
3A  
2A  
30VDC  
Resistive  
.9A  
.9A  
.5A  
1A  
110VDC  
125VAC  
30VDC  
Resistive  
Non Coded  
Non Coded  
Coded  
Resistive  
Inductive (L/R=5ms)  
Inductive (L/R=2ms)  
Inductive (PF=.35)  
Inductive (PF=.35)  
Inductive (PF=.35)  
30VDC  
Coded  
.3A  
.7A  
1.5A  
125VAC  
75VAC  
Non Coded  
Non Coded  
Non Coded  
25VAC  
Accessory Current Loads at 24VDC  
Device  
Standby  
0 mA  
Alarm  
RA400Z  
4.6 mA Max.  
4.6 mA Max.  
RTS451/RTS451KEY  
0 mA  
Specifications  
Operating Temperature Range  
32° to 120°F (0° to 49°C)  
Shipping Weight  
ED-DPR:4lbs. (1.8 kg)  
Operating Humidity Range  
10% to 93% relative humidity  
(non-condensing)  
Length  
14.5(36.7 cm)  
Width  
Duct Air velocity  
5(12.7 cm)  
500 – 4000 ft./min.  
(2.54 – 20.32 m/s)  
Depth  
4(10.2 cm)  
Ordering Information  
Part No.  
ED-DPR  
Description  
Accessories  
RTS451  
Description  
Eclipse Series intelligent duct smoke detector  
housing  
Remote test station (see below)  
Remote test station w/key (see below)  
Remote LED (see below)  
RTS451KEY  
RA400Z  
ED-DP  
ED-DPI  
ST-1.5  
ST-3  
Photoelectric duct sensor head  
Photoelectric isolator duct sensor head  
Metal sampling tube duct widths 1–2′  
Metal sampling tube duct widths 2–4′  
Metal sampling tube duct widths 4–8′  
Metal sampling tube duct widths 8–12′  
Replacement Eclipse Power Board  
F36-05-00  
P48-21-00  
T80-71-00  
Replacement filters  
End cap for metal sampling tube  
Replacement plastic sampling tube  
ST-5  
ST-10  
A2121  
ALARM  
ALARM  
ON  
RESET  
TEST  
RESET  
RTS451  
RTS451KEY  
RA400Z  
Remote Test Station  
(UL S2522)  
Remote Test Station with  
key (UL S2522)  
Remote  
Annunciator  
(UL S2522)  
System Sensor Sales and Service  
System Sensor Headquarters  
3825 Ohio Avenue  
St. Charles, IL 60174  
Ph: 800/SENSOR2  
Fx: 630/377-6495  
Documents-on-Demand  
800/736-7672 x3  
System Sensor Canada  
Ph: 905.812.0767  
Fx: 905.812.0771  
System Sensor in China  
Ph: 86.29.524.6253  
Fx: 86.29.524.6259  
System Sensor – Far East  
Ph: 85.22.191.9003  
Fx: 85.22.736.6580  
System Sensor – India  
Ph: 91.124.237.1770 x.2700  
Fx: 91.124.237.3118  
System Sensor Europe  
Ph: 44.1403.891920  
Fx: 44.1403.891921  
System Sensor in Singapore  
Ph: 65.6273.2230  
Fx: 65.6273.2610  
System Sensor – Australia  
Ph: 613.54.281.142  
Fx: 613.54.281.172  
System Sensor – Russia  
Ph: 70.95.937.7982  
Fx: 70.95.937.7983  
www.systemsensor.com  
© 2004 System Sensor. The company reserves the right to change product specifications without notice.  
A05-0373-000•4/04•#1261  

相关型号:

ED-DPR

Intelligent Duct Smoke Detectors
SYSTEMSENSOR

ED-P

Intelligent Photoelectric Smoke Detectors
SYSTEMSENSOR

ED-PT

Intelligent Photoelectric Smoke Detectors
SYSTEMSENSOR

ED-TI

Intelligent Heat Detector
SYSTEMSENSOR

ED0006-AL

Power Filter Inductor
COILCRAFT

ED0006_13

Power Filter Inductor
COILCRAFT

ED01-353

Peripheral IC
ETC

ED01-353-1

Peripheral IC
ETC

ED01-353-2

Peripheral IC
ETC

ED02-353-1

Peripheral IC
ETC

ED02-353-2

Peripheral IC
ETC

ED02315000J0G

Barrier Strip Terminal Block,
AMPHENOL