400SERIES [SYSTEMSENSOR]
Direct-Wire Photoelectronic Smoke Detector; 直丝光电感烟探测器![400SERIES](http://pdffile.icpdf.com/pdf1/p00130/img/icpdf/400SE_718633_icpdf.jpg)
型号: | 400SERIES |
厂家: | ![]() |
描述: | Direct-Wire Photoelectronic Smoke Detector |
文件: | 总4页 (文件大小:280K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
400 Series™
Direct-Wire Photoelectronic
Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, IL 60174
1-800-SENSOR2 (736-7672), Fax 630-377-6495
http://www.systemsensor.com
Models Available
2400/2400A Photoelectronic
2400TH Photoelectronic with Thermal
2412B/2412BA Photoelectronic
2412THB Photoelectronic with Thermal
2424 Photoelectronic
2424TH Photoelectronic with Thermal
Features
• 12 or 24 volt operation
• Field sensitivity metering of detector to meet NFPA 72
requirements
• Twist-on mounting bracket with tamper option
• SEMS screws for easy wiring
• Unique optical sensing chamber
• Removable cover and insect screen for easy
cleaning
• Visible LED blinks in standby, latches on in
alarm
• 3-year warranty
• Optional built-in 135°F (57°C) heat sensor
• Sealed against dirt, insects, and back pressure
Specifications
Size:
3.2″ (8.1 cm) h, 5.5″ (13.9 cm)
Sensitivity:
3.0% ± .7 ft. nominal
dia. with mounting bracket;
add .5″ (1.27 cm) to height for
thermal
Test Features:
1. Test port – Insert 0.1 inch maximum diameter allen
wrench or screwdriver into test port on detector
housing.
Shipping Weight:
0.5 lb. (227 g)
Operating Temperature Range:
2. Test card – After removing detector cover, insert
calibrated test card into test slot on screen.
3. Test module – Using a standard voltmeter interface,
insert MOD400R plug into detector’s module port.
Fulfills calibrated sensitivity test per NFPA 72.
Thermal Sensor Rating
Thermal Models:
All Other Models:
32°F to 100°F (0°C to 38°C)
32°F to 120°F (0°C to 49°C)
Operating
Humidity Range:
Air Velocity Rating:
Wiring Gauge:
10 – 93% RH noncondensing
3000 fpm
12 – 18 AWG, twisted pair
recommended
(thermal models only): 135°F fixed temperature
restorable
Mounting:
31/
″ or 4″ octagon box,
2
4″ square box with plaster ring,
50, 60, 75 mm boxes
Smoke Detector Spacing:
On smooth ceilings (as defined in NFPA 72), spacing
of 30 feet (900 sq. ft.) may be used as a guide. Other
spacing may be used depending on ceiling height,
high air movements, and other conditions or response
requirements.
APPROVED
© System Sensor 2/97
This document is not intended to be used for installation purposes.
A05-194-03
General Description
System Sensor 400 Series photoelectronic detectors are The 400 Series offer 6 different photoelectronic detectors
specifically designed to meet the stringent performance
requirements of industrial and commercial fire detection/
alarm systems. The design of these detectors emphasizes
ease of installation and field maintenance.
with a variety of voltages, wiring configurations, and
thermal options.
Electrical Specifications
Control Operating
Auxiliary Remote LED
Current Consumption
Model
2400
2400TH
2412B
Product
Photo Detector
Photo Detector w/Fixed Heat Sensor
Photo Detector
Panel
2-wire
2-wire
4-wire
4-wire
4-wire
4-wire
Voltage
12/24 VDC
12/24VDC
12 VDC
12 VDC
24 VDC
Contacts
No
No
Yes
Yes
Yes
Yes
Option
Yes
Yes
No
No
Standby (max.)
Alarm (max.)
120 µA
120 µA
120 µA
120 µA
120 µA
120 µA
*
*
77mA
77mA
41mA
41mA
2412THB Photo Detector w/Fixed Heat Sensor
2424
2424TH
Photo Detector
Photo Detector w/Fixed Heat Sensor
No
No
24 VDC
* Must be limited by control panel
Relay Contact Ratings:
Resistive or inductive
(60% power factor) load
Alarm Contacts
Form A:
2.0A @ 30 VAC/DC
2.0A @ 30 VAC/DC
Form C:
0.6A @ 110 VDC, 1.0A @ 125 VAC
.3 sec. (max.)
Reset Time:
Startup Time:
34 sec. (max.)
Engineering Specifications
Smoke Detector shall be a photoelectronic type (model
2400, 2412, 2424) or a combination photoelectronic/
thermal (model 2400TH, 2412TH, 2424TH) with thermal
sensor rated at 135°F as manufactured by System Sensor.
Wiring connections shall be made by means of SEMS
screws. The detector will have a visible LED which will
blink in standby and latch on in alarm. The detector shall
have a nominal sensitivity of 3% per foot as measured in
the UL smoke box. The detector screen and cover should
be easily removable for cleaning. It shall be possible to
perform a sensitivity and functional test without the need
of generating smoke. Detector circuitry shall perform a self
test on the sensing chamber and internal electronics every
40 seconds. If circuitry fails, the detector LED shall stop
blinking. The detector shall have a mounting bracket that
allows for mounting to a 31/
square electrical box.
2″ or 4″ octagon box or 4″
Page 2
A05-194-03
400 Series Wiring Guide
(–)
EOL
RESISTOR
(+)
(+)
(+)
2
2
(–)
(–)
(+)
(+)
1
1
REMOTE
LED
(+)
REMOTE
3
LED
(+)
3
RA400Z
RA400Z
(–)
(–)
OPTIONAL
OPTIONAL
2400/2400TH
Wiring Diagram
OPTIONAL CLASS “A” LOOP
(–)
POWER FROM
CONTROL PANEL
(+)
(+)
2
(+)
COMMON
COMMON
(–)
2
1
BLACK
RED
(–)
1
N/O
N/C
4
N/O
N/C
N/O
N/O
8
4
8
7
7
5
5
A77-716B
12/24 VDC EOL
RELAY
6
6
ALARM CIRCUIT
FROM CONTROL PANEL
PURPLE
PURPLE
2412B/THB, 2424/TH
Wiring Diagram
EOL
RESISTOR
Page 3
A05-194-03
Ordering Information
Part No.
Description
Accessories
Two-Wire Models
A77-716B End of line relay for power supervision, 12/24 VDC
2400
2400A
2400TH
Photoelectronic detector, 2-wire, 12/24 VDC
Same as above, Canadian model
Photoelectronic detector, 2-wire, 12/24 VDC with
built-in 135°F fixed heat sensor
RA400Z
Remote annunciator for 2 or 4 wire systems, 3-32V –
Use with ion and photo detectors. Fits standard U.S.
single gang electrical box. (See below.)
MOD400R Detector sensitivity test module – Use with most
analog or digital multimeters. Satisfies requirement
of NFPA 72 for sensitivity testing. (See below.)
Four-Wire Models
2412B
Photoelectronic detector, 4-wire, 12 VDC, with
auxiliary contacts
Same as above, Canadian model
2412THB Photoelectronic detector, 4-wire, 12 VDC, with
auxiliary contacts and integral 135°F fixed heat
sensor
RS24
RS24T
Replacement insect screen for 2400, 2412B, 2424
Replacement insect screen for 2400TH, 2412THB and
2424TH
2412BA
DUST45
Replacement protective dust cover for 400 Series
2424
Photoelectronic detector, 4-wire, 24 VDC, with
auxiliary contacts
2424TH
Photoelectronic detector, 4-wire, 24 VDC, with
auxiliary contacts and integral 135°F fixed heat
sensor
The MOD400R Field Sensitivity Test Module can be used with
any standard DC voltmeter or multimeter to check the
sensitivity range of System Sensor’s detectors (satisfies NFPA
72 requirement for sensitivity testing).
RA400Z Remote
Annunciator, 3 – 32V
Use with ion and photo
detectors that have remote
annunciator output
System Sensor Worldwide Manufacturing & Distribution
In Canada:
In the Far East:
In Italy:
Telephone: 905-812-0767
Fax: 905-812-0771
Telephone: 852-2191-9003
Fax: 852-2736-6580
Telephone: 39-40-949011
Fax: 39-40-382137
In China:
Telephone: 86-29-524-6253
Fax: 86-29-524-6259
In India:
Telefax: 91-11-5676815
In the United Kingdom:
Telephone: 44-1403-276500
Fax: 44-1403-276501
Page 4
A05-194-03