AQ300IU3TUAIND
更新时间:2024-09-19 00:18:53
品牌:SYNQOR
描述:AC-DC Regulated Power Supply Module, ROHS COMPLIANT
AQ300IU3TUAIND 概述
AC-DC Regulated Power Supply Module, ROHS COMPLIANT
AQ300IU3TUAIND 数据手册
通过下载AQ300IU3TUAIND数据手册来全面了解它。这个PDF文档包含了所有必要的细节,如产品概述、功能特性、引脚定义、引脚排列图等信息。
PDF下载Technical
Specification
500 W Triple Vout Series
Industrial Grade AC/DC Power Supply With PFC
85-264 Vrms
12/24/36/48 V
500 W
700 W
Up to 90 %
Input Voltage
Semi-Regulated Output
Output Continuous Output Transient Full Load Efficiency
Includes 5 V (10 W) and 12 V (50 W) “Always On” Standby Power Outputs
1500 W Encased
1000 W Encased
Package Configurations Available
p to three units can be factory mounted into a chassis.
The 500 W Triple Vout Series can be configured as follows:
500 W Encased
•ꢀ500ꢀWꢀ(1ꢀunit)ꢀ
•ꢀ1000ꢀWꢀ(2ꢀunits)ꢀ
•ꢀ1500ꢀWꢀ(3ꢀunits)
500 W Triple Vout Series Features
• High efficiency (90% for 48 Vout Model at 500 W) • Over–current, over–voltage, and over–temp
protection
• Universal input voltage range
• DC Power Good / AC Power Good signals
• Remote enable input
• Semi-regulated output for bus stability
• Parallel operation supported
• Fan status output / Fan enable input
• Small size: 3.59" x 5.25" x 1.63"
• RoHS 6/6 compliant
• Integral fan cooling with speed control
• Active PFC; EN61000-3-2 compliant
• Low noise; EN55011 / EN55022 Class B compliant
• 5 V (10 W) and 12 V (50 W) standby outputs
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 1
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
ACuQor 500W Triple Vout Series ELECTRICAL CHARACTERISTICS
All specifications typical with T = 25 °C, unless otherwise specified.
A
MAIN OUTPUT SPECIFICATIONS
GENERAL SPECIFICATIONS
Output power (continuous) 85-132/170-264 Vrms
500 W (Note 1)
700 W (Note 1)
See Figures 11, 12
Fundamental ripple freq.
Input
Output
500 kHz
250 kHz
(5 s transient)
85-132/170-264 Vrms
132-170 Vrms
Audible noise
Weight
Fan speed varies with temp.
39 dBA @ 1 m max.
Nominal DC output
voltage (at 250W)
(Semi-regulated)
12 Vout (model 1T)
24 Vout (model 2T)
36 Vout (model 3T)
48 Vout (model 4T)
12.4 V
25 V
37.5 V
50 V
(EQ)
(RQ)
(TQ)
540 g (19.1 oz)
1068 g (37.7 oz)
1582 g (55.8 oz)
MTBF
MIL-217
Demonstrated
343.6 kHours
TBD kHours
Efficiency
(see figs. 1, 3, 5, 7)
(see Note 1)
12 Vout, 115 Vrms, 500 W
48 Vout, 115 Vrms, 500 W
12 Vout, 230 Vrms, 500 W
48 Vout, 230 Vrms, 500 W
86% typ.
89% typ.
88% typ.
90% typ.
ISOLATION SPECIFICATIONS
Isolation voltage
Input to output
Input to ground
Output to ground
3000 Vrms
1500 Vrms
500 Vrms
Hold-up time (to -20%)
(see Note 1)
12 Vout
24 / 36 / 48 Vout
12 ms @ 500 W
16 ms @ 500 W
Insulation resistance
Leakage currents
Output to ground
10 MΩ min.
See Note 2
Maximum load capacitance 12 Vout
16,000 µF
8,000 µF
4,000 µF
2,000 µF
24 Vout
36 Vout
48 Vout
ENVIRONMENTAL CHARACTERISTICS
Thermal performance
Operating ambient
Non-operating ambient
0 ºC to +70 ºC
-40 ºC to +85 ºC
Output ripple voltage
Switching frequency (20 MHz BW)
Twice line frequency (at 300W)
0.5% p-p
5.0% p-p
Relative humidity
Altitude
Non-condensing
5-95% RH
Turn-on delay
2 s max.
Operating
Non-operating
10,000 ft max.
30,000 ft max.
Transient response
Iout steps from 50-75%
At 0.2 A/µs
3% typ / 6% max.
dev.
100 ms recovery
Random vibration
Shock
5-500 Hz
0.03 g2/Hz
20 g peak
Half-sine, 10 ms, 3 axes
Overvoltage protection
Short circuit protection
Total regulation
Cyclic restart
110-120%
115% rated Iout
±6.0%
EMC CHARACTERISTICS
Conducted emissions
Cyclic operation
Over line, load and temperature
ΔVout caused by 50 W step
ΔVout caused by 10 W step
Automatic recovery
EN55011 and EN55022, FCC
part15
Level B
12V_STANDBY cross-reg.
5V_STANDBY cross-reg.
Thermal protection
0.5%
Line frequency harmonics EN61000-3-2
Class A
Clause 5b
Level 3
Level 3
Level 3
Level 3
Level 3
Level 3
3 A/m
0.1%
Voltage fluctuations
ESD air
EN61000-3-3
EN61000-4-2
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-4-5
EN61000-4-6
EN61000-4-8
EN61000-4-11
+125 ºC (PCB Temp)
REMOTE_ENABLE
Input Low Voltage
Input High Voltage
0.45 V (max)
4.15 V (min)
ESD contact
12V_STANDBY OUTPUT SPECIFICATIONS
Output power 85-264 Vrms
Nominal DC output voltage Semi-regulated
Radiated immunity
Fast transients
50 W
12.4 V
Line surge immunity
Conducted immunity
Power freq. mag. field
Voltage dip immunity
Total regulation
Over line, load and temperature
±6.0%
400 mV
Main output cross-reg.
Δ12V_STANDBY caused by Δ350W
on main output
Perf Criteria A, A, B
<5% UT 10 ms,
70% UT 500 ms,
40% UT 100 ms
Output ripple
Switching frequency (20 MHz BW)
Twice line frequency
10 mV
0.45 Vrms
Output current
Continuous
4.2 A
5.0 A
Short circuit protection
Maximum load capacitance
Cyclic operation
SAFETY AGENCY CERTIFICATIONS (pending)
All certification marks appear on individual unit labels.
UL60950
2,000 uF
5V_STANDBY OUTPUT SPECIFICATIONS
Output power 85-264 Vrms
Nominal DC output voltage Fully regulated
10 W
5.0 V
IEC/EN 60950
CE Marked
Total regulation
Over line, load and temperature
±5.0%
2.0 A
Output current
Continuous
cUL CSA Standards
Short circuit protection
Maximum load capacitance
Cyclic operation
2.5 A
1,000 uF
NOTES:
INPUT SPECIFICATIONS
AC input voltage
1. Main output power rating always includes 5 V and 12 V standby outputs.
2. Leakage currents:
Universal range
85-264 Vrms
47-63 Hz
Input frequency
Input current
(see Note 1)
115 Vrms @ 400 W
230 Vrms @ 400 W
4 Arms
2 Arms
AC Leakage Current
from Input to Earth
Normal Open Neutral
AC Line Connection
240 V L-N, 1 phase
Condition
Fault
Power factor
>0.98
400 µA
200 µA
200 µA
800 µA
400 µA
400 µA
ACuQor Typical at
110% nominal input 208 V L-L, 120 V L-N, 1 of 3 phases
Input surge current
Internal input fuses
264 Vrms (cold start)
Both AC lines
40 A max.
10.0 A
voltage 60 Hz
240 V L-N-L, 120 V L-N, split phase
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 2
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
EFFICIENCY, DERATING, AND VOUT DROOP CURVES
100
95
90
85
80
75
13.5
13.0
12.5
12.0
11.5
11.0
10.5
Continuous
115 Vrms
70
230 Vrms
65
44
50
0
100
100
100
200
300
400
500
500
500
600
700
700
700
0
6
12
18
24
30
36
42
48
54
60
Output Load (A)
Output Power (W)
Figure 2: 12 V
droop characteristic.
Figure 1: 12 V
efficiency curves.
OUT
OUT
100
95
90
85
80
75
70
65
27
26
25
24
23
22
21
Continuous
115 Vrms
230 Vrms
22
25
0
200
300
400
600
0
6
12
18
24
30
Output Power (W)
Output Load (A)
Figure 3: 24 V
efficiency curves.
Figure 4: 24 V
droop characteristic.
OUT
OUT
100
95
90
85
80
75
70
65
40.5
39.0
37.5
36.0
34.5
33.0
31.5
Continuous
115 Vrms
230 Vrms
16.5
18.75
18
0
200
300
400
600
0
3
6
9
12
15
21
Output Load (A)
Output Power (W)
Figure 6: 36 VOUT droop characteristic.
Figure 5: 36 V
efficiency curves.
OUT
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 3
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
EFFICIENCY, DERATING, AND VOUT DROOP CURVES
100
95
90
85
80
75
54
52
50
48
46
44
42
Continuous
115 Vrms
70
230 Vrms
65
11
12.5
12
0
100
200
300
400
500
600
700
0
3
6
9
15
Output Power (W)
Output Load (A)
Figure 8: 48 V
droop characteristics.
Figure 7: 48 V
efficiency curves.
OUT
OUT
600
500
400
300
200
100
0
600
500
400
300
200
100
0
24 / 36 / 48 V, VIN ≥ 105 Vrms
12 V, VIN ≥ 105 Vrms
24 / 36 / 48 V with Fan Enabled
12 V with Fan Enabled
24 / 36 / 48 V, VIN = 85 Vrms
12 V, VIN = 85 Vrms
0
10
20
30
40
50
60
70
80
0
10
20
30
40
50
60
70
80
Ambient / Case Temperature (ºC)
Case Temperature (ºC)
Figure 9: Continuous power derating curve in natural convection. For Fan
Figure 10: Fan Disabled continuous power derating curve in natural
Disabled, see Figure 10.
convection.
800
700
600
500
400
300
800
700
600
500
400
300
200
200
Transient (24/36/48 V Out)
Transient (12 V Out)
100
100
0
Continuous
Continuous
0
132 150
Input AC Voltage (VRM S
264
85
132
264
85
105
170
210
170
)
Input AC Voltage (VRM S)
Figure 11: Rated output power vs Input AC Voltage.
Figure 12: Rated output power vs Input AC Voltage.
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 4
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
MECHANICAL DRAWINGS (1 Module Encased Version — E Package Type)
Top
Right
Bottom
Front
Back
NOTES (applies to all mechanicals)
1)ꢀRecommendedꢀscrewꢀtighteningꢀtorqueꢀofꢀ6ꢀin.lbs
2)ꢀUndimensionedꢀcomponentsꢀareꢀshownꢀforꢀvisualꢀreferenceꢀonly
3)ꢀAllꢀdimensionsꢀinꢀinchesꢀ[mm]
ꢀ ꢀ Tolerances:ꢀ x.xxꢀinꢀ±ꢀ0.02
ꢀ ꢀ
ꢀ
ꢀ
x.xxxꢀinꢀ±ꢀ0.010
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 5
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
MECHANICAL DRAWINGS (2 Modules Flat Version — R Package Type)
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 6
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
MECHANICAL DRAWINGS (3 Modules Flat Version — T Package Type)
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 7
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
CONNECTOR DETAILS
OUTPUT CONNECTOR PINOUT (top side)
Pin 1 FAN_GOOD
Open collector with internal 5V pullup. See Figure A.
Pulsed low on fan failure, 100ms, 50% duty.
Short to VOUT(-) to disable fan.
Pin 2 AC_POWER_GOOD
Pin 3 DC_POWER_GOOD
Open collector with internal 5V pullup. See Figure B.
Pulled low on AC power dropout.
Figure A: Fan status output / Fan enable input interface circuitry.
Open collector with internal 5V pullup. See Figure B.
Pulled low during startup ramp and within 5 ºC of
temperature shutdown threshold.
Pin 4 5V_STANDBY
Pin 5 VOUT(+)
Pin 6 VOUT(+)
Pin 7 VOUT(+)
Pin 8 VOUT(+)
Pin 9 Reserved
Pin 10 Reserved
Pin 11 REMOTE_ENABLE
5 V @ 10 W available whenever AC power is applied.
Positive Output Voltage.
Positive Output Voltage.
5V_STANDBY
Positive Output Voltage.
1N4148
Positive Output Voltage.
Reserved for future use.
5 k
Reserved for future use.
10 Ohms
AC_POWER_GOOD or
DC_POWER_GOOD
2N3904
Logic input. See Figure C.
Pull high to enable main output.
From AC/DC
Monitor
Circuitry
0.1 µF
VOUT(-)
Pin 12 12V_STANDBY
Pin 13 VOUT(–)
Pin 14 VOUT(–)
Pin 15 VOUT(–)
Pin 16 VOUT(–)
12 V @ 50 W available whenever AC power is applied.
Negative Output Voltage.
Negative Output Voltage.
Figure B: Power good interface circuitry.
Negative Output Voltage.
Negative Output Voltage.
5V_STANDBY
5V_STANDBY
12 V OUTPUT CONNECTOR PINOUT (bottom side)
Pin 1 VOUT(+)
Pin 2 VOUT(+)
Pin 3 VOUT(+)
Positive Output Voltage.
Positive Output Voltage.
Positive Output Voltage.
Positive Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage.
Negative Output Voltage
10 Ohms
5 k
To Enable
Circuitry
REMOTE_ENABLE
0.1 µF
10k
VOUT(-)
VOUT(+)
Pin 4
Pin 5 VOUT(–)
Pin 6 VOUT(–)
Pin 7 VOUT(–)
Pin 8 VOUT(–)
Figure C: Remote enable interface circuitry.
MATING CONNECTORS
Connector
Type
Contact
OUTPUT (16 pins)
12V_OUTPUT (8 pins)
INPUT
Molex 430251600
Molex 436450800
JST VHR-5N
Molex 430300008*
Molex 430300008*
JST SVH-41T-P1.1
INDIVIDUAL INPUT CONNECTOR PINOUT
Pin 1
Pin 3
Pin 5
Ground
AC Neutral
AC Line
* Each contact rated for a maximum of 5.5 A.
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 8
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
PARALLEL OPERATION - MULTIPLE UNITS
Chassis configurations for Parallel Units
Specifications of Parallel Units
ACuQor units are available either open-frame or pre-mounted As a rule, units wired in parallel behave the same as single units.
at the factory. Up to 3 units can be mounted into a chassis, in Any specification will remain unchanged that is expressed in units
either side-by-side or stacked configurations. For a complete list of of voltage, time, frequency, or efficiency. Specifications expressed
options, see the “Part Numbering System” table on the last page, in terms of power, current, or capacitance, should be scaled by the
under “Package Type”, along with the Mechanical Drawings pages. number of units wired in parallel.
Only side-by-side configurations can be populated with 500W units,
since each includes a thermal pad underneath.
ACuQor units are individually calibrated at the factory, so that the
output voltage vs. output current characteristic is always consistent
(see Vout droop characteristic figures). As such, multiple units will
Interconnection of Parallel Units
ACuQor units mounted in 2 and 3 unit chassis are not connected share output current accurately. Full current is guaranteed from a
together. This allows the physical routing and connectivity of the bank of multiple units wired in parallel.
external wiring to be customized to each application. The following
table summarizes the recommended wiring to operate multiple
units in parallel:
Output Connector Signal
REMOTE_ENABLE
FAN_GOOD
Suggested Connection
Behavior with Multiple Units
Wire in parallel
Inputs activated simultaneously
“
“
“
“
“
Wired-OR outputs – can be pulled low by any unit during an abnormal condition.
AC_POWER_GOOD
DC_POWER_GOOD
VOUT(+), VOUT(-)
12V_STANDBY*
5V_STANDBY
“
“
Built-in droop characteristic ensures graceful current sharing.
“
Do not wire in parallel Fully regulated characteristic does not support current sharing. If placed in
parallel, only the output with the highest set-point will drive current.
*Note: Triple output models only.
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 9
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
INSTALLATION INSTRUCTIONS
General:ꢀꢀACuQorꢀAC/DCꢀpowerꢀsuppliesꢀareꢀintendedꢀforꢀuseꢀ
asꢀ componentsꢀ inꢀ industrialꢀ equipment.ꢀ ꢀ ACuQorꢀ unitsꢀ mustꢀ beꢀ
properlyꢀinstalledꢀwithinꢀendꢀuseꢀequipmentꢀbeforeꢀtheyꢀcanꢀbeꢀ
safelyꢀappliedꢀasꢀdescribedꢀinꢀthisꢀdocument.ꢀꢀTheꢀsuitabilityꢀofꢀ
theꢀACuQor/equipmentꢀcombinationꢀmustꢀbeꢀverifiedꢀthroughꢀendꢀ
productꢀinvestigation.
Output:ꢀꢀReferꢀtoꢀtheꢀConnectorꢀDetailsꢀsectionꢀforꢀoutputꢀcon-
nectorꢀ wiringꢀ andꢀ signalꢀ I/Oꢀ functionality.ꢀ ꢀ Referꢀ toꢀ nameplateꢀ
labelꢀ forꢀ outputꢀ currentꢀ ratings.ꢀ ꢀ Mainꢀ DCꢀ outputꢀ (Vout+,ꢀ Vout-)ꢀ
pinsꢀshouldꢀuseꢀ20ꢀAWGꢀ(0.5mm2)ꢀwireꢀsize.ꢀꢀIndividualꢀmainꢀ
outputꢀpinsꢀshouldꢀnotꢀbeꢀloadedꢀtoꢀmoreꢀthanꢀ5.5ꢀA.ꢀꢀForꢀcurrentsꢀ
greaterꢀthanꢀ5.5ꢀA,ꢀmultipleꢀmainꢀoutputꢀpins/wiresꢀmustꢀbeꢀusedꢀ
inꢀparallel.ꢀꢀAllꢀsignalꢀI/OꢀpinsꢀareꢀreferencedꢀtoꢀVout-.ꢀ
Mounting:ꢀꢀReferꢀtoꢀtheꢀMechanicalꢀDrawingsꢀsection.ꢀꢀACuQorꢀ
unitsꢀareꢀprovidedꢀwithꢀthreadedꢀstainless-steelꢀstand-offsꢀorꢀinsertsꢀ
forꢀmounting.ꢀꢀThisꢀmountingꢀhardwareꢀisꢀinternallyꢀconnectedꢀtoꢀ
theꢀ inputꢀ connectorꢀ protective-earthꢀ terminalꢀ forꢀ functional-earthꢀ
EMCꢀcontrol.ꢀꢀAnyꢀorientationꢀ(vertical,ꢀhorizontal,ꢀetc.)ꢀmayꢀbeꢀ
used.ꢀꢀAdequateꢀairꢀspaceꢀshouldꢀbeꢀprovidedꢀoverꢀtheꢀfanꢀintakeꢀ
(top)ꢀ andꢀ exhaustꢀ (sides)ꢀ toꢀ allowꢀ forꢀ exchangeꢀ ofꢀ coolingꢀ air.ꢀ
ACuQorꢀisꢀdesignedꢀforꢀaꢀpollutionꢀdegreeꢀ2ꢀenvironment.ꢀꢀTheꢀ
suitabilityꢀofꢀtheꢀenclosedꢀACuQorꢀmechanicalꢀassembliesꢀmustꢀbeꢀ
verifiedꢀthroughꢀendꢀproductꢀinvestigation.
EMC:ꢀꢀACuQorꢀproductsꢀhaveꢀbeenꢀtestedꢀtoꢀtheꢀEMCꢀspecifica-
tionsꢀlistedꢀinꢀtheꢀElectricalꢀCharacteristicsꢀsection.ꢀꢀHowever,ꢀendꢀ
useꢀequipmentꢀmustꢀbeꢀtestedꢀtoꢀverifyꢀEMCꢀcompliance.
Hipot Testing:ꢀ ꢀ ACuQorꢀ productsꢀ areꢀ ratedꢀ forꢀ Hipotꢀ testingꢀ
levelsꢀ ofꢀ1500ꢀVacꢀ inputꢀtoꢀprotective-earth,ꢀ500ꢀVacꢀoutputꢀtoꢀ
protective-earth,ꢀandꢀ3000ꢀVacꢀinputꢀtoꢀoutput.ꢀꢀWhenꢀperform-
ingꢀ theꢀ 3000ꢀ Vacꢀ inputꢀ toꢀ outputꢀ test,ꢀ theꢀ testꢀ voltageꢀ mustꢀ beꢀ
balancedꢀevenlyꢀ1500ꢀVacꢀinputꢀandꢀoutputꢀtoꢀprotective-earth.ꢀ
Twoꢀoppositelyꢀphasedꢀtestꢀvoltageꢀsourcesꢀorꢀaꢀsingleꢀtestꢀvolt-
ageꢀsourceꢀwithꢀexternalꢀbalancingꢀimpedancesꢀ(capacitors)ꢀmayꢀ
beꢀusedꢀtoꢀpreventꢀoverstressingꢀinputꢀorꢀoutputꢀtoꢀprotective-earthꢀ
insulationꢀperꢀIEC/ENCꢀ60950-1.
Encased models:ꢀ ꢀ Aꢀ minimumꢀ ofꢀ 5ꢀ mmꢀ electricalꢀ clearanceꢀ
shouldꢀbeꢀallowedꢀfromꢀtheꢀconnectorꢀendsꢀofꢀencasedꢀmodels.
Input:ꢀꢀReferꢀtoꢀtheꢀConnectorꢀDetailsꢀsectionꢀforꢀinputꢀconnec-
torꢀwiring.ꢀꢀACuQorꢀproductsꢀrequireꢀaꢀsingleꢀphaseꢀACꢀpowerꢀ
sourceꢀofꢀ100-240Vꢀ50/60Hzꢀnominal.ꢀꢀReferꢀtoꢀnameplateꢀlabelꢀ
forꢀ inputꢀ currentꢀ ratings.ꢀ ꢀ Aꢀ protective-earthꢀ connectionꢀ isꢀ alsoꢀ
required.ꢀ ꢀ Minimumꢀ wireꢀ sizeꢀ ofꢀ 18ꢀ AWGꢀ (0.8mm2)ꢀ isꢀ recom-
mended.ꢀꢀBothꢀsidesꢀofꢀtheꢀACꢀlineꢀareꢀinternallyꢀfusedꢀ(seeꢀtableꢀ
forꢀspecificꢀmodels).ꢀꢀTheseꢀfusesꢀareꢀnotꢀuserꢀreplaceable.
MODEL
AQ0300
AQ0400
AQ0500
Input Fuses (in Both AC Lines)
Littelfuseꢀ6.3Aꢀ250Vꢀ21606.3XEP
Littelfuseꢀ6.3Aꢀ250Vꢀ21606.3XEP
Littelfuseꢀ10.0Aꢀ250Vꢀ216010XEP
Fuses Total
2
2
2
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 10
85-264 V
12/24/36/48V Semi-reg
500 W Series
Industrial
AC Input:
DC Output:
Power:
RMS
.
Grade:
Technical Specification
PART NUMBERING SYSTEM
Theꢀ partꢀ numberingꢀ systemꢀ forꢀ SynQor’sꢀ ACuQorꢀ AC/DCꢀ powerꢀ suppliesꢀ followsꢀ theꢀ formatꢀ shownꢀ inꢀ theꢀ tableꢀ below.
Notꢀallꢀcombinationsꢀmakeꢀvalidꢀpartꢀnumbers,ꢀpleaseꢀcontactꢀSynQorꢀforꢀavailability.
Thermal
Design
Output Voltage
(xx=Standard; xT=Triple)
Package Type
(Correlates to Output Power)
Family
Output Power
Grade
Range
Options
0300: 300 W
0400: 400 W
0500: 500 W
0600: 600 W (2 x 300 W)
0800: 800 W (2 x 400 W)
0900: 900 W (3 x 300 W)
1000: 1000 W (2 x 500 W)
1200: 1200 W (3 x 400 W)
1500: 1500 W (3 x 500 W)
12: 12 V
1T: 12 V / 5 & 12 V
24: 24 V
2T: 24 V / 5 & 12 V
36: 36 V
3T: 36 V / 5 & 12 V
48: 48 V
STBY
STBY
STBY
STBY
AQ
E: 1 unit (3" x 5")
R: 2 units; flat
S: 2 units; stacked
T: 3 units; flat
A: open frame
C: encased
Q: encased only
U: universal
Industrial Grade:
IND: Industrial
ACuQor series
of ac-dc semi-regulated
output power supplies
I: industrial
(85-264 V
)
RMS
U: 3 units; stacked
4T: 48 V / 5 & 12 V
Example: AQ1500IU1TTQIND
ACCESSORIES
SynQorꢀoffersꢀaꢀseriesꢀofꢀassembliesꢀthatꢀcanꢀbeꢀorderedꢀaccordingꢀtoꢀtheꢀtableꢀbelow.ꢀꢀMechanicalꢀdrawingsꢀforꢀtheseꢀaccessoriesꢀareꢀ
availableꢀforꢀdownloadꢀinꢀpdfꢀformatꢀfromꢀtheꢀSynQorꢀwebsite.
Part Number
AQ-CBL-INPUT1C
AQ-CBL-OUT1C
AQ-CBL-OUT1CD
AQ-CBL-OUT2C
AQ-CBL-OUT2CD
AQ-INSUL1M
Description
Input mating cable with pre-stripped wire ends (36" long).
Output mating cable with pre-stripped wire ends (18" long).
Same as AQ-CBL-OUT1C with an additional 8-pin connector.
Output mating cable with connectors on both ends (18" long).
Same as AQ-CBL-OUT2C with an additional 8-pin connector.
Single module bottom-side Mylar insulator for open frame mounting.
Evaluation board for up to three paralleled modules.
AQ-EVAL-PRL3
APPLICATION NOTES
AꢀvarietyꢀofꢀapplicationꢀnotesꢀandꢀtechnicalꢀwhiteꢀpapersꢀcanꢀbeꢀdownloadedꢀinꢀpdfꢀformatꢀfromꢀtheꢀSynQorꢀwebsite.
PATENTS
SynQorꢀholdsꢀtheꢀfollowingꢀpatents,ꢀoneꢀorꢀmoreꢀofꢀwhichꢀmightꢀapplyꢀtoꢀthisꢀproduct:
ꢀ
ꢀ
ꢀ
ꢀ
5,999,417ꢀ
6,594,159ꢀ
6,927,987ꢀ
7,119,524ꢀ
6,222,742ꢀ
6,731,520ꢀ
7,050,309ꢀ
7,269,034ꢀ
6,545,890ꢀ
6,894,468ꢀ
7,072,190ꢀ
7,272,021ꢀ
6,577,109
6,896,526
7,085,146
7,272,023
Warranty:ꢀSynQorꢀoffersꢀaꢀtwoꢀ(2)ꢀyearꢀlimitedꢀwarranty.ꢀCompleteꢀwarrantyꢀinforma-
tionꢀisꢀlistedꢀonꢀourꢀwebsiteꢀorꢀisꢀavailableꢀuponꢀrequestꢀfromꢀSynQor.
Contact SynQor for further information:
Phone:ꢀ 978-849-0600
TollꢀFree:ꢀ 888-567-9596
Limitationꢀ onꢀ use:ꢀ SynQor’sꢀ productsꢀ areꢀ notꢀ authorizedꢀforꢀuseꢀ andꢀ shouldꢀ notꢀ beꢀ
used,ꢀwithoutꢀtheꢀspecificꢀpriorꢀwrittenꢀapprovalꢀofꢀanꢀauthorizedꢀofficerꢀofꢀSynQorꢀ
makingꢀspecificꢀreferenceꢀhereto,ꢀinꢀanyꢀlifeꢀsupportꢀsystem,ꢀnuclearꢀfacilityꢀorꢀapplica-
tion,ꢀaircraftꢀcontrolꢀapplicationꢀorꢀanyꢀotherꢀapplicationꢀinꢀwhichꢀfailureꢀofꢀtheꢀproductꢀ
couldꢀreasonablyꢀresultꢀinꢀharmꢀtoꢀlife,ꢀpropertyꢀorꢀtheꢀenvironment.
Fax:ꢀ
978-849-0602
E-mail:ꢀ
Web:ꢀ
power@synqor.com
www.synqor.com
InformationꢀfurnishedꢀbyꢀSynQorꢀisꢀbelievedꢀtoꢀbeꢀaccurateꢀandꢀreliable.ꢀꢀHowever,ꢀ
noꢀresponsibilityꢀisꢀassumedꢀbyꢀSynQorꢀforꢀitsꢀuse,ꢀnorꢀforꢀanyꢀinfringementsꢀofꢀpatentsꢀ
orꢀotherꢀrightsꢀofꢀthirdꢀpartiesꢀwhichꢀmayꢀresultꢀfromꢀitsꢀuse.ꢀNoꢀlicenseꢀisꢀgrantedꢀbyꢀ
implicationꢀorꢀotherwiseꢀunderꢀanyꢀpatentꢀorꢀpatentꢀrightsꢀofꢀSynQor.
Address:ꢀ 155ꢀSwansonꢀRoad
ꢀ Boxborough,ꢀMAꢀ01719,ꢀUSA
ꢀ
Product # AQ0500IUxT Series
Phone 1-888-567-9596
www.synqor.com
Doc.# 005-005055 Rev. 1
09/04/08
Page 11
AQ300IU3TUAIND 相关器件
型号 | 制造商 | 描述 | 价格 | 文档 |
AQ300IU3TUCIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU3TUQIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48EAIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48ECIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48EQIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48RAIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48RCIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48RQIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48SAIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 | |
AQ300IU48SCIND | SYNQOR | AC-DC Regulated Power Supply Module, ROHS COMPLIANT | 获取价格 |
AQ300IU3TUAIND 相关文章
- 2024-09-20
- 5
- 2024-09-20
- 8
- 2024-09-20
- 8
- 2024-09-20
- 6