3RT20161AB01 [SIEMENS]
CONTACTOR, AC-3, 4KW/400V, 1NO, AC 24V, 50/60 HZ, 3-POLE, SZ S00 SCREW TERMINAL; 接触器, AC- 3 , 4KW / 400V , 1NO , AC 24V , 50/60赫兹, 3极, SZ S00螺丝端子型号: | 3RT20161AB01 |
厂家: | Siemens Semiconductor Group |
描述: | CONTACTOR, AC-3, 4KW/400V, 1NO, AC 24V, 50/60 HZ, 3-POLE, SZ S00 SCREW TERMINAL |
文件: | 总7页 (文件大小:408K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product data sheet
3RT2016-1AB01
CONTACTOR, AC-3, 4KW/400V, 1NO, AC 24V,
50/60 HZ, 3-POLE, SZ S00 SCREW TERMINAL
General technical data:
product brand name
SIRIUS
S00
Size of the contactor
Product extension / auxiliary switch
Protection class IP / on the front
Protection against electrical shock
Degree of pollution
Yes
IP20
finger-safe
3
Installation altitude / at a height over sea level / maximum
Ambient temperature
m
2,000
• during storage
°C
°C
-55 … +80
-25 … +60
• during operating
Shock resistance
• at rectangular impulse
• at AC
6,7g / 5 ms, 4,2g / 10 ms
• at sine pulse
• at AC
10,5g / 5 ms, 6,6g / 10 ms
Impulse voltage resistance / rated value
Insulation voltage / rated value
Mechanical operating cycles as operating time
• of the contactor / typical
kV
V
6
690
30,000,000
3RT2016-1AB01
Page 1/7
subject to modifications
© Copyright Siemens AG 2012
07/27/2012
• of the contactor with added auxiliary switch block / typical
10,000,000
5,000,000
• of the contactor with added electronics-compatible auxiliary
switch block / typical
Main circuit:
Number of NC contacts / for main contacts
Number of NO contacts / for main contacts
Operating current
0
3
• at AC-1 / at 400 V
• at 40 °C ambient temperature / rated value
• at 60 °C ambient temperature / rated value
• at AC-2 / at 400 V / rated value
• at AC-3 / at 400 V / rated value
• at AC-4 / at 400 V / rated value
Operating current
A
A
A
A
A
22
20
9
9
8.5
• with 1 current path / at DC-1
• at 24 V / rated value
A
A
20
• at 110 V / rated value
2.1
• with 2 current paths in series / at DC-1
• at 24 V / rated value
A
A
20
12
• at 110 V / rated value
• with 3 current paths in series / at DC-1
• at 24 V / rated value
A
A
20
20
• at 110 V / rated value
• with 1 current path / at DC-3 / at DC-5
• at 24 V / rated value
A
A
20
• at 110 V / rated value
0.1
• with 2 current paths in series / at DC-3 / at DC-5
• at 24 V / rated value
A
A
20
• at 110 V / rated value
0.35
• with 3 current paths in series / at DC-3 / at DC-5
• at 24 V / rated value
A
A
20
20
• at 110 V / rated value
Service power
• at AC-2 / at 400 V / rated value
• at AC-3 / at 400 V / rated value
• at AC-4 / at 400 V / rated value
Active power loss / per conductor / typical
Off-load operating frequency
• at AC
kW
kW
kW
W
4
4
4
0.7
1/h
10,000
3RT2016-1AB01
Page 2/7
subject to modifications
© Copyright Siemens AG 2012
07/27/2012
• at DC
1/h
1/h
1/h
1/h
1/h
10,000
1,000
750
Frequency of operation / at AC-1 / according to IEC 60947-6-2
Frequency of operation / at AC-2 / according to IEC 60947-6-2
Frequency of operation / at AC-3 / according to IEC 60947-6-2
Frequency of operation / at AC-4 / according to IEC 60947-6-2
750
250
Control circuit:
Type of voltage / of the controlled supply voltage
Control supply voltage / 1
AC
• at 50 Hz / for AC / rated value
• at 60 Hz / for AC / rated value
V
V
24
24
Operating range factor control supply voltage rated value / of
the magnet coil
• at 50 Hz / for AC
0.8 … 1.1
0.85 … 1.1
27
• at 60 Hz / for AC
Apparent pull-in power / of the solenoid / for AC
Apparent holding power / of the solenoid / for AC
Inductive power factor
• with the pull-in power of the coil
• with the pull-in power of the coil
Closing delay
V·A
V·A
4.2
0.8
0.25
• at AC
ms
9 … 35
Opening delay
• at AC
ms
ms
3.5 … 14
10 … 15
Arcing time
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
0
Number of NC contacts / for auxiliary contacts / instantaneous
switching
Number of NO contacts / for auxiliary contacts / instantaneous
switching
1
Operating current / of the auxiliary contacts
• at AC-12 / maximum
• at AC-15
• at 230 V
A
10
A
A
10
3
• at 400 V
• at DC-12
• at 48 V
A
A
A
6
6
3
• at 60 V
• at 110 V
3RT2016-1AB01
Page 3/7
subject to modifications
© Copyright Siemens AG 2012
07/27/2012
• at 220 V
• at DC-13
• at 24 V
A
1
A
A
A
A
A
10
2
• at 48 V
• at 60 V
2
• at 110 V
• at 220 V
1
0.3
Short-circuit:
Design of the fuse link
• for short-circuit protection of the auxiliary switch / required
• for short-circuit protection of the main circuit
• with type of assignment 1 / required
fuse gL/gG: 10 A
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35
A
• at type of coordination 2 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
20A
Installation/mounting/dimensions:
mounting position
+/-180° rotation possible on vertical mounting surface;
can be tilted forward and backward by +/- 22.5° on
vertical mounting surface
Type of mounting
screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
Type of fixing/fixation / series installation
Yes
45
57.5
73
0
Width
mm
mm
mm
mm
mm
Height
Depth
Distance, to be maintained, to the ranks assembly / sidewards
Distance, to be maintained, to earthed part / sidewards
6
Connections:
Design of the electrical connection
• for main current circuit
• for auxiliary and control current circuit
Type of the connectable conductor cross-section
• for main contacts
screw-type terminals
screw-type terminals
• solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
• finely stranded
• with conductor end processing
• for AWG conductors / for main contacts
• for auxiliary contacts
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
2x (20 ... 16), 2x (18 ... 14), 2x 12
• solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
• finely stranded
3RT2016-1AB01
subject to modifications
Page 4/7
07/27/2012
© Copyright Siemens AG 2012
• with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
2x (20 ... 16), 2x (18 ... 14), 2x 12
• for AWG conductors / for auxiliary contacts
Certificates/approvals:
General Product Approval
Declaration of
Conformity
Test Certificates
Special Test
Certificate
Shipping Approval
Shipping Approval
other
Confirmation
UL/CSA ratings:
yielded mechanical performance (hp)
• for single-phase squirrel cage motors
• at 110/120 V / rated value
hp
hp
0.33
1
• at 230 V / rated value
• for three-phase squirrel cage motors
• at 200/208 V / rated value
hp
hp
hp
hp
2
• at 220/230 V / rated value
3
• at 460/480 V / rated value
5
• at 575/600 V / rated value
7.5
Operating current (FLA) / for three-phase squirrel cage motors
• at 480 V / rated value
A
A
7.6
9
• at 600 V / rated value
Contact rating designation / for auxiliary contacts / according to
UL
A600 / Q600
Sicherheitsrelevante Kenngrößen:
B10 value / with high demand rate
• according to SN 31920
1,000,000
20
T1 value / for proof test interval or service life
• according to IEC 61508
a
Proportion of dangerous failures
• with low demand rate / according to SN 31920
• with high demand rate / according to SN 31920
%
%
40
73
3RT2016-1AB01
subject to modifications
Page 5/7
07/27/2012
© Copyright Siemens AG 2012
Failure rate (FIT value) / with low demand rate
• according to SN 31920
FIT
100
Product function
• mirror contact to IEC 60947-4-1
• comment
Yes
with 3RH29
No
• positively driven operation to IEC 60947-5-1
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator:
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RT2016-1AB01/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT2016-1AB01
3RT2016-1AB01
subject to modifications
Page 6/7
07/27/2012
© Copyright Siemens AG 2012
last change:
Jul 26, 2012
3RT2016-1AB01
Page 7/7
subject to modifications
© Copyright Siemens AG 2012
07/27/2012
相关型号: