6024923 [SICK]
SAFETY RELAYS;UE10-4XT3D2
UE10-4XT
SAFETY RELAYS
UE10-4XT3D2 | UE10-4XT
SAFETY RELAYS
Ordering information
A
B
C
D
E
F
Type
UE10-4XT3D2
Part no.
6024920
Other models and accessories www.sick.com/UE10-4XT
Illustration may differ
Detailed technical data
Safety-related parameters
Safety integrity level
H
I
SIL3 (IEC 61508) 1)
SILCL3 (EN 62061) 1)
Category 4 (EN ISO 13849) 1)
PL e (EN ISO 13849) 1)
Category
Performance level
B10d parameter
J
2.5 x 106 witching cycles (AC-15, 230 V, I = 1.5 A)
6 x 106 switching cycles (AC-15, 230 V, I = 0.75 A)
2 x 106 switching cycles (DC-13, 24 V, I = 2.5 A)
10 x 106 switching cycles (DC-13, 24 V, I = 0.6 A)
K
L
2.47 x 10-8 (EN ISO 13849)
PFHD (mean probability of a dangerous fail-
ure per hour)
20 years (EN ISO 13849)
TM (mission time)
1)
M
N
O
P
Q
R
S
T
If the feedback current path Y1 - Y2 (external device monitoring) is monitored using an appropriate main unit.
Interfaces
Connection type
Plug-in screw-type terminals
4, relevant for safety
Number of enable current (N/O) contacts
Electrical data
Operating data
A1, A2
Voltage supply
Output circuit > 25 V AC / 60 V DC PELV
Output circuit ≤ 25 V AC / 60 V DC PELV or SELV
A1, A2
Supply voltage VS
24 V AC/DC (20.4 V AC/DC ... 26.4 V AC/DC)
1)
Residual ripple
(≤ 2.4 Vpp
)
1)
In DC operation, within the limits of V .
S
2
SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK
Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE10-4XT3D2 | UE10-4XT
SAFETY RELAYS
2.7 VA (AC)
1.5 W
Power consumption
III (see operating instructions)
300 V AC
Overvoltage category
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Test voltage
4 kV
2 kV (50 Hz) (EN 60439-1)
1)
In DC operation, within the limits of V .
S
Electrical output circuits: 13/14, 23/24, 33/34, 43/44, 51/52, 61/62, Y1/Y2
(≤ 40 ms) 1)
Response time
4, relevant for safety
Contactor monitoring contact 10 V DC ... 24 V DC
Number of enable current (N/O) contacts
2, not safety-relevant
Number of signalling current (N/C) contacts
1, external device monitoring (EDM)
Number of contactor monitoring (N/C) con-
tacts
Positively driven
Contact type
Silver alloy, gold flashed
Contact material
Switching voltage
Enable current contact 10 V AC ... 230 V AC
10 V DC ... 300 V DC
Signalling current contact 10 V DC, 10 V DC ... 230 V AC, 300 V DC
Current-carrying capacity per OSSD
Enable current contact 10 mA ... 6 A
Signalling current contact 10 mA ... 2 A
Contactor monitoring contact 10 mA ... 100 mA
Total current ≤ 12 A
AC-15/DC-13 (EN 60947-5-1)
Usage category
3 A (230 V AC) 3600 switching cycles/h
4 A (24 V DC) 360 switching cycles/h
2.5 A (24 V DC) 3600 switching cycles/h
Rated operating current (voltage)
≤ 3600/h
Switching frequency
1 x 107 switching cycles
2 x 106 switching cycles
Mechanical life (relay contacts)
Electrical life (relay contacts)
1)
K1/K2.
Mechanical data
22.5 mm x 114 mm x 96.5 mm
0.2 kg
Dimensions (W x H x D)
Weight
Classifications
27371990
27371990
27371819
27371819
27371819
ECl@ss 5.0
ECl@ss 5.1.4
ECl@ss 6.0
ECl@ss 6.2
ECl@ss 7.0
2018-09-11 15:13:28 | Online data sheet
Subject to change without notice
SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK
3
UE10-4XT3D2 | UE10-4XT
SAFETY RELAYS
27371819
27371819
27371819
EC001449
EC001449
41113704
ECl@ss 8.0
ECl@ss 8.1
ECl@ss 9.0
ETIM 5.0
A
B
C
D
E
F
ETIM 6.0
UNSPSC 16.0901
Dimensional drawing (Dimensions in mm (inch))
78
(3.07)
58
(2.28)
H
I
J
K
L
93.3
(3.67)
96.5
(3.8)
M
N
O
P
Q
R
S
T
67
(2.64)
85
(3.35)
4
SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK
Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE10-4XT3D2 | UE10-4XT
SAFETY RELAYS
Connection diagram
A1 A2
Y1
13 23 33 43 51 61
K1
K2
Y2
14 24 34 44 52 62
2018-09-11 15:13:28 | Online data sheet