CG45.6199.151 [SCHURTER]

Mains Power Connector, 6A, 250VAC, Male, Quick Connect Terminal, Socket;
CG45.6199.151
型号: CG45.6199.151
厂家: SCHURTER INC.    SCHURTER INC.
描述:

Mains Power Connector, 6A, 250VAC, Male, Quick Connect Terminal, Socket

连接器 电源连接器
文件: 总4页 (文件大小:285K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
POWER ENTRY MODULES  
CG  
Power entry modules  
Types CG, CG-Bowdencable  
Panel mount: screw-on version, front-side  
– 5 functions: appliance inlet, line switch or line switch for  
Bowdencable actuation, fuseholder with interchangeable  
fuse drawer for 5 x 20 or 6,3 x 32 mm fuses, with series-  
parallel voltage selector, line filter  
Fuse drawer  
Standard or  
Medical filter  
Pushbutton for front panel  
actuation  
Voltage selector  
insert  
50  
75  
100  
Bowden cable eliminates wiring  
between pushbutton and power  
entry module  
Remote mechanical line switch  
Characteristics  
All single elements are allready partial wired  
The “Extra-Safe” fuse drawers satisfy international standards for  
medical equipment. The drawer can only be removed with the aid  
of a tool  
The fuseholder is accessible from the equipment front  
Qualified for use in equipment according to IEC/EN 60950  
Technical data  
Rated voltage  
125/250 VAC; 50/60 Hz  
a
Rated currents Type CG  
Type CG-  
1–10 A; @T 40 °C  
a
1–6 A; @T 40 °C; SEV, VDE, Semko  
a
Bowdencable 1–6 A / 250 VAC; @T 40 °C; UL, CSA  
a
1–8 A / 125 VAC; @T 40 °C; UL, CSA  
Leackage current, Standard  
Medical  
Test voltage (2 sec)  
< 0,5 mA (250 V/60 Hz)  
< 5 µA (250 V/60 Hz)  
1,7 kVDC between L-N  
2,7 kVDC between L/N-PE  
Allowable ambient air  
a
temperatures T  
–25 °C to +85 °C  
Climatic category  
25/085/21 acc. to IEC/EN 60068-1  
Degree of protection (front-side) IP40 acc. to IEC 60529  
Protection class  
suitable for equipment with prot. cl. I,  
acc. to IEC 61140  
Terminals  
Panel thickness s  
Materials: Housing  
quick-connect 4,8 x 0,8 mm  
max. 8 mm  
Thermoplastic, black, UL94 V0  
120  
www.schurter.com  
POWER ENTRY MODULES  
CG  
Technical data  
Appliance-inlet  
acc. to. IEC/EN 60320-1/C14,  
Protection class I, pin-temperature 70 °C  
(cold condition)  
Fuseholder  
1- or 2-pole, shocksafe category PC2  
acc. to IEC/EN 60127-6  
for fuse-links 5 x 20 or 6,3 x 32 mm  
Rated power acceptance at  
5 x 20: 2,5 W (1-pole)/2 W (2-pole) per pole  
6,3 x 32: 3,15 W (1-pole)/2,5 W (2-pole)  
per pole  
a
ambient air temp. T 23 °C  
Admissible power acceptance  
see derating curves. Take note of the  
information on page 197  
a
at higher T  
Line switch  
2-pole, non illuminated  
(Rocker switch)  
acc. to IEC/EN 61058-1  
Line switch for Bowdencable  
2-pole, non illuminated  
Technical details see page 201  
series-parallel, 4, 3 or 2 switch positions  
or usable as a 2-pole change-over  
switch.  
Voltage selector  
Line filter, standard and medical acc. to. IEC 60939, EN 133 200,  
UL 1283, CSA C 22.2 no. 8  
Technical details see page 202  
Dimensions type CG  
Mounting screw torque 0,5 Nm  
Panel cut-out  
Dimensions type CG Bowdencable  
Panel cut-out see type CG  
Details and description for Bowdencable see  
page 59  
R 0,5  
Panel cut-out for the actuating part B1  
Mounting screw torque 0,5 Nm  
121  
www.schurter.com  
POWER ENTRY MODULES  
CG  
Diagrams  
Standard version  
with fuseholder 1- or 2-pole  
Medical version  
with fuseholder 2-pole  
Load  
Line  
Line  
Load  
x) Connections to be made by customer  
Optional accessory cables (stranded conductor) for voltage selector  
wiring see on page 63  
Technical data of filter-components  
Rated current  
(A)  
Filter-Type  
Inductance  
L1/L2 (mH)  
Capacitance  
CX (nF)  
R
(M)  
CY (nF)  
2 x 2,2  
1
2
4
6
10  
1
2
4
6
10  
2 x 10  
2 x 4  
Standard  
2 x 1,5  
2 x 0,8  
2 x 0,3  
2 x 10  
2 x 4  
2 x 1,5  
2 x 0,8  
2 x 0,3  
1
68  
68  
Medical  
Derating curves for fuseholder  
Fuses  
1-pole  
5 x 20 mm  
2-pole  
(per pole)  
Fuses  
1-pole  
6,3 x 32 mm  
2-pole  
(per pole)  
a
Ambient air temperature T °C  
Attenuation loss  
Standard version  
Medical version  
differential mode  
common mode  
4 A  
4 A  
1 A  
1 A  
2 A  
6 A  
2 A  
6 A  
122  
www.schurter.com  
POWER ENTRY MODULES  
CG  
Attenuation loss  
Standard version  
Medical version  
differential mode  
common mode  
10 A  
10 A  
Order Numbers to type CG for socket  
Fuse drawer and voltage selector insert must be ordered separately.  
Order nos see pages 62, 63  
Type  
CG  
Order no  
Rated current Filter-Type  
Line switch  
Fuseholder  
1-pole  
CG16.5101.151  
CG26.5101.151  
CG36.5101.151  
CG46.5101.151  
CG66.5101.151  
CG10.6101.151  
CG20.6101.151  
CG30.6101.151  
CG40.6101.151  
CG60.6101.151  
CGG0.6101.151  
CGA0.6101.151  
CGC0.6101.151  
CGE0.6101.151  
CGL0.6101.151  
1 A  
2 A  
Standard  
4 A  
2-pole  
6 A  
10 A  
1 A  
2 A  
4 A  
Standard  
2-pole  
2-pole  
2-pole  
2-pole  
6 A  
10 A  
1 A  
2 A  
4 A  
Medical  
6 A  
10 A  
Order Numbers to type CG-Bowdencable: for socket  
Fuse drawer, voltage selector insert and Bowdencable must be  
ordered separately.  
Order nos see page 63 (fuse drawer), 62 (voltage selector insert)  
and 59 (Bowdencable)  
Type  
Order no  
Rated current Filter-Type  
Line switch  
Fuseholder  
for Bowdencable  
2-pole  
CG  
CG15.6199.151  
1 A  
Standard  
Standard  
Medical  
Bowden- CG25.6199.151  
cable  
2 A  
4 A  
6 A  
1 A  
2 A  
4 A  
6 A  
1 A  
2 A  
4 A  
6 A  
1-pole  
2-pole  
2-pole  
CG35.6199.151  
CG45.6199.151  
CG10.6199.151  
CG20.6199.151  
CG30.6199.151  
CG40.6199.151  
CGG0.6199.151  
CGA0.6199.151  
CGC0.6199.151  
CGE0.6199.151  
2-pole  
2-pole  
Accessories see page 171  
123  
www.schurter.com  

相关型号:

CG451T200R4C

Reliable Screw Terminal Aluminum Electrolytic Capacitor 85 ⅹC, Screw Terminal Capacitors
CDE

CG451T200R4C0ND

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NF

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NG

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NH

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NL

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NN

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0NV

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0PD

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0PF

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0PG

CAP,AL2O3,450UF,200VDC,10% -TOL,50% +TOL
CDE

CG451T200R4C0PL

Aluminum Electrolytic Capacitor, Polarized, Aluminum (wet), 200V, 50% +Tol, 10% -Tol, 450uF
CDE