4420.0308 [SCHURTER]
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 3 poles;型号: | 4420.0308 |
厂家: | SCHURTER INC. |
描述: | Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 3 poles |
文件: | 总8页 (文件大小:528K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Manual Motor Controller / Circuit Breaker for Equipment thermal-magnetic, 3 poles
Description
Applications
- Thermal-magnetic circuit breaker
- High short circuit performance
- Availability of AC and DC in the same frame size
- DIN-Rail Mounting
- Industrial appliances
Weblinks
pdf-datasheet, html-datasheet, General Product Information, Approvals,
CE declaration of conformity, RoHS, CHINA-RoHS, REACH, Distributor-
Stock-Check, Detailed request for product, Product News
Standards
- Approval Reference Type: AS168X
- IEC 60934
- UL508, UL1077
- CSA C22.2
Technical Data
General data
Tripping Type
Positively trip free
Rated Voltage AC
IEC : 420 V Y / 240 V; 50/60 Hz
Actuation type
Manual ON/OFF
UL/CSA : 480 V Y / 277 V; 50/60 Hz
65 V
Permissible wire cross section 1.5 - 25 mm² / 16 - 4 AWG
Rated Voltage DC
Rated current
Switched neutral
0.5 - 52 A , see approbations
Rated Voltage
Rated current
Function
AC 277 V
AC/DC 65 A
The switched neutral closes with ma-
nual closure of the poles and opens
automatically with thermal magnetic
tripping of the poles.
Conditional short circuit capa- Icn: AC 420 V Y/240 V / DC 65 V: 5 kA
city IEC 60934 (no fuse)
Conditional short circuit capa- Inc: AC 480 V Y/277 V: 10 kA (with fuse
city UL 1077
class H/J, 4x rated current (min. 15 A))
Icn: AC 480 V Y/277 V: 5 kA (no fuse)
Icn: DC 65 V: 2 kA (no fuse)
Conditional short circuit capa- Icn: AC 480 V Y/277 V: 5 kA (no fuse)
city UL 508
Add-on modules
Add-on modules
Technical data for the additional module
see separate data sheet
Degree of Protection
Lifetime
Dielectric Strength
from front side IP 40 acc. to IEC 60529
1 x Ir 6000switching cycles
50Hz: > 2kV
Impulse 1.2/50 μs
Vibration Resistance
0.75 mm ꢀ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
10 G ꢀ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
250/440VAC > 5 MΩ
30 G / 18ms
Insulation Resistance
Shock Resistance
acc. to IEC 60068-2-27, test Ea
Ambient temperature
Weight
-10°C to 55°C
100 - 130g
1
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Dimension
AS168X 3 pole
45
A)
52.5
35
90
1.9
B)
A) 35 mm DIN rail EN 50022
B) Max. torque
Wire crosssection
Max. torque
2.5 Nm
3.1 Nm
20 ... 22 lb–in
26 ... 28 lb–in
1.5 ... 10 mm2
16 ... 25 mm2
AWG #16 ... 8
AWG #6 ... 4
AS168X 3 pole and switched neutral pole
45
A)
70
35
90
1.9
B)
A) 35 mm DIN rail EN 50022
B) Max. torque
Wire crosssection
1.5 ... 10 mm2
16 ... 25 mm2
AWG #16 ... 8
AWG #6 ... 4
Max. torque
2.5 Nm
3.1 Nm
20 ... 22 lb–in
26 ... 28 lb–in
2
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Diagrams
AS168X-CB1...
AS168X-CB1...N
AS168X-CB1... / AS168X-ACBH1
AS168X-CB1... / AS168X-ACBS1
AS168X-CB1... / AS168X-ACBA
AS168X-CB1... / AS168X-ACBH2
AS168X-CB1... / AS168X-ACBS2
3
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Symbol
Standard
Rated current
0.5 - 52 A
Rated voltage AC
480Y/277 V
Conditional short circuit Rated voltage DC
capacity Icn
Conditional short circuit
capacity Icn
UL 508
CSA C22.2 no. 14
5 kA
-
-
-
UL 1077
0.5 - 40 A
480 V
10 kA
-
CSA C22.2 no. 235
EN 60934
0.5 - 50 A
0.5 - 30 A
480 V
5 kA
65 V
65 V
2 kA
240/420 V
4.5 kA
4.5 kA
GB 17701
-
-
-
-
-
Effect of ambient temperature
AC-breaker are calibrated for an ambient temperature of +40°C, DC-breakers for +23°C. To determine the rated current for a lower or
higher ambient temperature, use a correction factor from the table below:
Ambient temperature [°C]
Correction factor AC version
Correction factor DC version
-20
-5
0.78
0.82
0.83
0.87
0.91
0.95
1.00
1.05
1.11
0.80
0.87
0.90
0.95
1.00
1.05
1.10
1.20
1.30
0
+10
+23
+30
+40
+50
+60
Example DC version: Rated current = 10 A; Environmental temperature = 50 °C; --> Correction factor = 1.2; Resulting current = 12 A
4
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
AS168X-CB
Motor Nameplate
Nominal Circuit Voltage, VAC
220-
110-
120
380-
415
440-
480
200
208
265
277
240
Rated Current
FLA
Starting/
LRC Rating
3°
1 pole
2 pole
(See Note #1)
0.5A
1A
Rating
0.5A
1A
1.5A
2A
3A
4A
5A
6A
6°
9°
12A
18A
24A
30A
36A
42A
48A
54A
60A
72A
78A
90A
96A
1/10
1/6
1/4
1/3
1/2
3/4
1
1 1/2
2
2
2
3
3
3
3
5
5
5
1.5A
2A
3A
4A
5A
6A
7A
8A
9A
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
1/10
1/8
1/4
1/3
1/2
1/2
3/4
1
1/10
1/6
1/4
1/3
1/2
3/4
1
1/10
1/6
1/3
1/3
1/2
3/4
1
1/10
1/8
1/6
1/4
1/4
1/3
1/3
1/2
1/2
1/2
3/4
1
1/6
1/4
1/3
1/2
1/2
3/4
3/4
1
1 1/2
1 1/2
2
2
2
1/6
1/3
1/3
1/2
1/2
3/4
1
1/2
1
1 1/2
2
2
2
3
3
3
3
5
5
5
7A
8A
9A
1
1
1
1
1 1/2
2
2
2
3
3
3
3
3
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
1
1 1/2
2
2
2
2
3
3
3
3
1 1/2
2
2
3
3
3
3
3
5
1 1/2
1 1/2
2
2
2
3
3
3
3
108A
120A
138A
150A
162A
180A
1
1 1/2
1 1/2
2
2
2
3
3
3
3
5
7 1/2
7 1/2
10
10
5
5
5
5
3
5
5
5
7 1/2
7 1/2
3
3
Horsepower
(FLA & LRC Ratings Apply where no HP Rating is given)
AS168X-CB
Motor Nameplate
Nominal Circuit Voltage, VAC
110-120
200
208
220-240
380-415
440-480
3 pole
Rated Current
FLA
Rating
0.5A
1A
Starting/
LRC Rating
(See Note #1)
0.5A
1A
1.5A
2A
3A
4A
5A
6A
7A
8A
9A
1.5A
2A
3A
4A
5A
6A
7A
8A
9A
10A
12.5A
20A
25A
32A
32A
32A
46A
46A
1/2
3/4
1
1 1/2
2
2
3
3
3
1/2
3/4
1 1/2
2
3
3
3
5
5
1/2
3/4
1
1
1/2
2
2
1/2
3/4
1
1
1/2
2
2
1/2
3/4
1
1/2
2
1/2
1/2
3/4
3/4
1
2
2
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
10A
12A
13A
15A
16A
18A
20A
23A
25A
27A
30A
46A
1
2
3
3
3
3
5
5
5
5
2
3
3
3
3
5
5
5
3
3
3
3
5
5
5
5
5
5
5
63.5A
63.5A
81A
81A
81A
1 1/2
1 1/2
2
2
2
3
3
3
3
7 1/2
7 1/2
10
10
10
10
15
15
20
20
7 1/2
7 1/2
10
10
10
10
15
15
81A
116A
116A
145A
145A
7 1/2
7 1/2
7 1/2
10
7 1/2
7 1/2
7 1/2
7 1/2
7 1/2
3
Note #1: For AC motor circuit nameplate FLA loads, AC general-use loades, AC resistance loads
5
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Time-Current-Curves
Version F / Magnetic 3-5 xln
Version G / Magnetic 6-10 xln
1hr
1hr
1000s
1000s
100s
10s
1s
100s
10s
1s
0,1s
10ms
1ms
0,1s
10ms
1ms
0,1ms
1
0,1ms
1
10
100
1000 x I
10
100
1000 x I
n
n
Multiple of Rated Current In
Multiple of Rated Current In
Reference Temperature +23°
Reference Temperature +23°
Version H / Magnetic 12-20 xln
1hr
1000s
100s
10s
1s
0,1s
10ms
1ms
0,1ms
1
10
100
1000 x I
n
Multiple of Rated Current In
Reference Temperature +23°
Config. Code
AS168X-CB|1|DG|200|N|
The characters are placeholders for the correspondingly keys of selections from the key tables.
Number of Poles
Configuration
key
AS168X-CB|1|DG|200|N|= Number of Poles
3-pole
3
6
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
Rated current
Configuration
key
AS168X-CB|1|DG|200|N|= Tripping characteristics
Tripping characteristics
Configuration
key
12.0 A
120
150
160
180
200
230
250
270
300
320
350
400
450
500
520
15.0 A
1.0-1.25xIn / 3-5xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 12-20xIn / 0.5-52 A
F
G
H
16.0 A
18.0 A
20.0 A
23.0 A
25.0 A
AS168X-CB|1|DG|200|N|= Rated current
27.0 A
Rated current
Configuration
key
30.0 A
32.0 A
0.05 A
005
010
015
020
030
040
050
060
070
080
090
100
35.0 A
1.0 A
40.0 A
1.5 A
45.0 A
2.0 A
50.0 A
3.0 A
52.0 A
4.0 A
Other rated currents on request
5.0 A
6.0 A
7.0 A
AS168X-CB|1|DG|200|N|= Switched neutral
8.0 A
Switched neutral
Configuration
key
9.0 A
10.0 A
Switched neutral pole
N
Other rated currents on request
Variants
Tripping characteristics
Rated current
Switched neutral
Config. Code
Order Number
1.0-1.25xIn / 3-5xIn / 0.5-52 A
1.0-1.25xIn / 3-5xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
30.0 A
35.0 A
2.0 A
AS168X-CB3F300
AS168X-CB3F350
AS168X-CB3G020
AS168X-CB3G030
AS168X-CB3G040
AS168X-CB3G050
AS168X-CB3G100
AS168X-CB3G150
4420.0742
4420.0994
4420.0402
4420.0400
4420.0388
4420.0301
4420.0241
4420.0204
3.0 A
4.0 A
5.0 A
10.0 A
15.0 A
█
█
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
20.0 A
25.0 A
AS168X-CB3G200
AS168X-CB3G250
4420.0198
4420.0242
█
█
1.0-1.25xIn / 6-10xIn / 0.5-52 A
1.0-1.25xIn / 6-10xIn / 0.5-52 A
30.0 A
32.0 A
AS168X-CB3G300
AS168X-CB3G320
4420.0210
4420.0323
1.0-1.25xIn / 6-10xIn / 0.5-52 A
40.0 A
AS168X-CB3G400
4420.0199
1.0-1.25xIn / 12-20xIn / 0.5-52 A
1.0-1.25xIn / 12-20xIn / 0.5-52 A
15.0 A
20.0 A
AS168X-CB3H150
AS168X-CB3H200
4420.0569
4420.0308
1.0-1.25xIn / 12-20xIn / 0.5-52 A
1.0-1.25xIn / 12-20xIn / 0.5-52 A
1.0-1.25xIn / 12-20xIn / 0.5-52 A
1.0-1.25xIn / 12-20xIn / 0.5-52 A
25.0 A
30.0 A
40.0 A
50.0 A
AS168X-CB3H250
AS168X-CB3H300
AS168X-CB3H400
AS168X-CB3H500
4420.0542
4420.0287
4420.0372
4420.0762
█ Most Popular.
Availability for all products can be searched real-time:http://www.schurter.com/Stock-Check/Stock-Check-SCHURTER
7
Circuit Breakers
Thermal-magnetic (TM and AS-line)
AS168XAC3
www.schurter.com /PG20
1 Pcs
Packaging Unit
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
8