Characteristics
Multi 9 - C60SP - MCB - 3P - 40 A - B Curve -
480Y/277 V - 5 kA - UL 1077
Product availability : Stock - Normally stocked in distribution facility
Price** : 324.00 USD
Main
Range
Multi 9
Product name
Multi 9 C60
Product or component type
Device short name
Device application
Poles description
Number of protected poles
Line Rated Current
Network type
Miniature circuit-breaker
C60SP
Distribution
3P
3
40 A 77 °F (25 °C) EN/IEC 60947-2
AC
Trip unit technology
Curve code
Thermal-magnetic
B
Breaking capacity
10 kA AIR 240 V AC UL 1077
10 kA AIR 240 V AC CSA C22.2 No 235
6 kA Icu 440 V AC EN/IEC 60947-2
10 kA Icu 415 V AC EN/IEC 60947-2
20 kA Icu 240 V AC EN/IEC 60947-2
6 kA Icu 440 V AC GB 14048.2
10 kA Icu 415 V AC GB 14048.2
20 kA Icu 240 V AC GB 14048.2
5 kA AIR 480Y/277 V AC UL 1077
5 kA AIR 480Y/277 V AC CSA C22.2 No 235
Suitability for isolation
Standards
Yes EN/IEC 60947-2
EN/IEC 60947-2
GB 14048.2
UL 1077
CSA C22.2 No 235
Product certifications
IEC
CCC
UR
CSA
Feb 27, 2020
1
Complementary
[Ue] rated operational voltage
240 V AC 50/60 Hz
415 V AC 50/60 Hz
440 V AC 50/60 Hz
Magnetic tripping limit
4 x In +/- 20 % AC
[Ics] rated service breaking capacity
4.5 kA 75 % EN/IEC 60947-2 - 440 V AC
7.5 kA 75 % EN/IEC 60947-2 - 415 V AC
15 kA 75 % EN/IEC 60947-2 - 240 V AC
4.5 kA 75 % GB 14048.2 - 440 V AC
7.5 kA 75 % GB 14048.2 - 415 V AC
15 kA 75 % GB 14048.2 - 240 V AC
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
500 V AC EN/IEC 60947-2
6 kVEN/IEC 60947-2
Yes
Toggle
Local signalling
ON/OFF indication
Clip-on
Mounting mode
Mounting support
9 mm pitches
DIN rail
6
Height
3.19 in (81 mm)
2.13 in (54 mm)
2.83 in (72 mm)
Grey
Width
Depth
Color
Mechanical durability
Electrical durability
Provision for padlocking
Connections - terminals
20000 cycles
10000 cycles
Padlockable
Tunnel type terminal top or bottom) 0.00…0.05 in² (1…35 mm²) AWG 18...AWG 2) - rigid
Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 3) - flexible with
ferrule
Tunnel type terminal top or bottom) 0.00…0.04 in² (1…25 mm²) AWG 18...AWG 3) - flexible
Wire stripping length
Tightening torque
0.55 in (14 mm) top or bottom
30.98 lbf.in (3.5 N.m) top or bottom
Without
Earth-leakage protection
Environment
IP degree of protection
IP20IEC 60529
IP40 modular enclosure)IEC 60529
Pollution degree
3 EN/IEC 60947-2
Tropicalisation
2 IEC 60068-1
Relative humidity
95 % 131 °F (55 °C)
0...6561.68 ft (0...2000 m)
-22…158 °F (-30…70 °C)
-40…176 °F (-40…80 °C)
Operating altitude
Ambient air temperature for operation
Ambient air temperature for storage
Ordering and shipping details
Category
00948 - M9 GEN 2 CB UL1077 / IEC
Discount Schedule
GTIN
DE2
00785901738190
Returnability
Yes
FR
Country of origin
Offer Sustainability
Sustainable offer status
REACh Regulation
Green Premium product
REACh Declaration
2
EU RoHS Directive
Compliant
EU RoHS Declaration
Mercury free
Yes
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information.
Environmental Disclosure
Circularity Profile
WEEE
Product Environmental Profile
No need of specific recycling operations
The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins.
3
相关型号:
©2020 ICPDF网 联系我们和版权申明