CA3KN22BD [SCHNEIDER]
Power/Signal Relay, 4PST, Momentary, 0.005A (Coil), 24VDC (Coil), 120mW (Coil), 690VDC (Contact), DC Input, Panel Mount/Din-Rail Mount, GREEN AND REACH COMPLIANT;型号: | CA3KN22BD |
厂家: | SCHNEIDER ELECTRIC |
描述: | Power/Signal Relay, 4PST, Momentary, 0.005A (Coil), 24VDC (Coil), 120mW (Coil), 690VDC (Contact), DC Input, Panel Mount/Din-Rail Mount, GREEN AND REACH COMPLIANT 继电器 |
文件: | 总2页 (文件大小:73K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Product data sheet
Characteristics
CA3KN22BD
TeSys K control relay - 2 NO + 2 NC - <= 690
V - 24 V DC standard coil
Product availability: Stock - Normally stocked in distribution facility
Main
Commercial Status
Commercialised
TeSys K control relay
Control relay
Range of product
Product or component
type
Device short name
Contactor application
Utilisation category
CA3K
Control circuit
AC-15
DC-13
Pole contact
composition
2 NO + 2 NC
[Ue] rated operational
voltage
<= 690 V <= 400 Hz
Control circuit type
DC standard
24 V DC
Control circuit voltage
Complementary
[Ith] conventional free air thermal current
Irms rated making capacity
Associated fuse rating
10 A at <= 122 °F (50 °C)
110 A conforming to IEC 60947
10 A gG conforming to VDE 0660
10 A gG conforming to IEC 60947
[Ui] rated insulation voltage
600 V conforming to CSA C22.2 No 14
690 V conforming to BS 5424
750 V conforming to VDE 0110 group C
690 V conforming to IEC 60947
Mounting support
Plate
Rail
Connections - terminals
Screw clamp terminals 2 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness:
flexible - without cable end
Screw clamp terminals 1 cable(s) 0...0 in² (0.34...1.5 mm²) - cable stiffness:
flexible - with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness:
flexible - without cable end
Screw clamp terminals 1 cable(s) 0...0.01 in² (0.75...4 mm²) - cable stiffness:
flexible - with cable end
Screw clamp terminals 2 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Screw clamp terminals 1 cable(s) 0...0.01 in² (1.5...4 mm²) - cable stiffness: solid
Tightening torque
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver Philips No 2
0.24 in (6 mm)
11.5 lbf.in (1.3 N.m) - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit voltage limits
Operating time
0.1...0.75 Uc at 122 °F (50 °C) drop-out
0.8...1.15 Uc at 122 °F (50 °C) operational
25...35 ms coil energisation and NC opening
15 ms coil de-energisation and NC closing
30...40 ms coil energisation and NO closing
10 ms coil de-energisation and NO opening
Mechanical durability
Operating rate
20 Mcycles
10000 cyc/h
2 ms
Immunity to microbreaks
Inrush power in W
3 W at 68 °F (20 °C)
3 W at 68 °F (20 °C)
3 W
Hold-in power consumption in W
Heat dissipation
Minimum switching voltage
17 V
Mar 13, 2014
1
Minimum switching current
Non overlap distance
Insulation resistance
Height
5 mA
0.02 in (0.5 mm)
> 10 MOhm
2.28 in (58 mm)
1.77 in (45 mm)
2.24 in (57 mm)
0.5 lb(US) (0.225 kg)
Width
Depth
Product weight
Environment
Standards
BS 5424
IEC 60947
NF C 63-140
VDE 0660
Product certifications
CSA
UL
IP degree of protection
IP2x
Protective treatment
TC conforming to IEC 60068
-13...122 °F (-25...50 °C)
-58...176 °F (-50...80 °C)
6561.68 ft (2000 m) without derating in temperature
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
Flame retardance
Requirement 2 conforming to NF F 16-102
Requirement 2 conforming to NF F 16-101
V1 conforming to UL 94
Mechanical robustness
Shocks contactor closed 15 Gn for 11 ms IEC 60068-2-27
Shocks contactor open 10 Gn for 11 ms IEC 60068-2-27
Vibrations contactor closed 4 Gn, 5...300 Hz IEC 60068-2-6
Vibrations contactor open 2 Gn, 5...300 Hz IEC 60068-2-6
Ordering and shipping details
Category
22371 - RELAYS, CONTROL
Discount Schedule
GTIN
I12
00785901898771
Nbr. of units in pkg.
Package weight(Lbs)
Product availability
Returnability
1
0.49
Stock - Normally stocked in distribution facility
Y
Country of origin
FR
Offer Sustainability
Sustainable offer status
RoHS
Green Premium product
Compliant - since 0633 -
Schneider Electric declaration of conformity
REACh
Reference not containing SVHC above the threshold
Available Download Product Environmental
Need no specific recycling operations
Product environmental profile
Product end of life instructions
Contractual warranty
Period
18 months
2
相关型号:
©2020 ICPDF网 联系我们和版权申明