2924689 [PHOENIX]

MACX MCR-EX-T-UI-UP;
2924689
型号: 2924689
厂家: PHOENIX CONTACT    PHOENIX CONTACT
描述:

MACX MCR-EX-T-UI-UP

文件: 总40页 (文件大小:785K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MACX MCR-EX-T-UI-UP...  
Temperature transducers with intrinsically safe  
input for temperature sensors, voltage signals,  
resistance-type sensors and potentiometers  
Data sheet  
104601_en_04  
© PHOENIX CONTACT 2012-05-21  
1
Description  
The configurable and programmable MACX  
Features such as sensor type, connection method, measur-  
ing range, measuring unit, filter, alarm signal and output  
range can be configured using the IFS-CONF software and  
a device-specific DTM (Device Type Manager).  
MCR-EX-T-UI-UP... temperature transducer is used for the  
intrinsically safe (Ex i) operation of all standard temperature  
sensors (RTDs and thermocouples), voltage signals, re-  
mote resistance-type sensors and potentiometers. The tem-  
perature input signals are output in a linearized format at the  
output. In addition to an analog current and voltage output,  
the module also has a switching output. The power supply  
has been designed as a wide range power supply.  
Features  
Input for all standard temperature sensors (RTDs and  
thermocouples), voltage signals, remote resistance-  
type sensors and potentiometers.  
With intrinsically safe inputs [Ex ia] IIC  
Current and voltage output  
Switching output (1 PDT relay)  
Configuration via software (FDT/DTM) or operator inter-  
face (IFS-OP-UNIT)  
The devices can be installed in zone 2 in the protection type  
“n” (EN 60079-15).  
The temperature transducer can be configured with the  
standard configuration (see example: “Order key” on  
page 6) or order-specific according to the order key and is  
delivered calibrated and ready for operation. Possible set-  
tings for the modules configured according to the order  
(MACX MCR...-C) can be found in the order key on page  
page 6.  
Up to SIL 2 according to EN 61508 on output 4 ... 20 mA  
3-way electrical isolation  
Installation in zone 2 permitted  
Wide range power supply 19.2 ... 253 V AC/DC  
With screw or spring-cage connection  
The set configuration is shown on the label on the side of the  
housing.  
WARNING: Explosion hazard  
The device is an item of associated electrical equipment for intrinsically safe circuits. It is designed for  
use in zone 2, if specific conditions are observed.  
When installing and operating the device, the applicable safety directives (including national safety directives), ac-  
cident prevention regulations, as well as general technical regulations must be observed.  
WARNING: Explosion hazard  
Please observe the safety regulations and installation notes on page 11.  
Make sure you always use the latest documentation.  
It can be downloaded at www.phoenixcontact.net/catalog.  
This data sheet is valid for the products listed in Section 3 “Ordering data” .  
MACX MCR-EX-T-UI-UP...  
2
1
2
3
4
5
6
Table of contents  
Description.................................................................................................................................. 1  
Table of contents ........................................................................................................................ 2  
Ordering data.............................................................................................................................. 5  
Order key ................................................................................................................................... 6  
Technical data ............................................................................................................................ 7  
Minimum span and measuring accuracies.................................................................................. 9  
6.1  
Pt and Ni-RTD inputs........................................................................................................................................ 9  
6.2  
Cu-RTD inputs................................................................................................................................................... 9  
6.3 NI1000 input (Landis & Gyr), KTY 81-110, KTY 84-130 (Philips) .............................................................. 9  
6.4 Thermocouple input.......................................................................................................................................... 9  
6.5 Cold junction error...............................................................................................................................9  
6.6  
6.7  
6.8  
6.9  
Voltage signal input .......................................................................................................................................... 9  
R transducers and resistors ............................................................................................................................ 9  
Potentiometer.................................................................................................................................................. 10  
Output signals ................................................................................................................................................. 10  
7
8
Safety regulations and installation notes....................................................................................11  
7.1  
Installation and operation...............................................................................................................................11  
7.2 Safety regulations for installation in potentially explosive areas .............................................................. 11  
7.3  
Use in safety-related applications (SIL 2).................................................................................................... 12  
Installation .................................................................................................................................13  
8.1  
Basic circuit diagrams ................................................................................................................................... 13  
Structure........................................................................................................................................................... 13  
Dimensions...................................................................................................................................................... 14  
Mounting .......................................................................................................................................................... 14  
8.2  
8.3  
8.4  
8.5 Connecting the cables ......................................................................................................................14  
8.6 Power supply................................................................................................................................................... 14  
8.7 Sensor types.....................................................................................................................................15  
8.7.1 Thermocouple (TC) with internal cold junction compensation ...................................................................... 15  
8.7.2 Thermocouple (TC) with external or without cold junction compensation.....................................................15  
8.7.3 Voltage input ................................................................................................................................................ 15  
8.7.4 Potentiometer............................................................................................................................................... 15  
8.7.5 Resistance thermometer (RTD).................................................................................................................... 15  
8.7.6 Measuring resistances ................................................................................................................................. 15  
8.8  
8.9  
Current output ................................................................................................................................................. 15  
Voltage output ................................................................................................................................................. 15  
8.10 Switching output................................................................................................................................16  
104601_en_04  
PHOENIX CONTACT  
2
MACX MCR-EX-T-UI-UP...  
8.11 Switching output behavior with manual acknowledgement (latching) .................................................... 17  
8.11.1 Switching behavior (2): Undertemperature limit (SPH) .............................................................................. 17  
8.11.2 (Switching behavior (3): Overtemperature limit (SPH)............................................................................... 17  
8.11.3 Switching behavior (4): Undertemperature limit with hysteresis (SPL) ...................................................... 18  
8.11.4 Switching behavior (5): Overtemperature limit with hysteresis (SPH)........................................................ 18  
8.11.5 Switching behavior (6): Temperature range limit (SPL and SPH) ........................................................... 19  
8.11.6 Switching behavior (7): Temperature range limit (SPL and SPH) ........................................................... 19  
8.12 Monitoring function ......................................................................................................................................... 20  
8.13 Operating modes ............................................................................................................................................ 20  
8.13.1 SIL ON/SIL OFF ........................................................................................................................................... 20  
8.13.2 Service mode ............................................................................................................................................... 20  
9
Configuration .............................................................................................................................20  
9.1  
Delivered state/standard configuration........................................................................................................ 21  
9.2 Zero adjust, adjustment via buttons S2 and S3 (only possible with SIL OFF) ....................................... 21  
9.3 Span adjust, adjustment via buttons 2 and 4 (only possible with SIL OFF)............................................ 21  
9.4 Force output......................................................................................................................................21  
9.5  
Cable compensation, 2-wire RTD or RTD 1 with 2 x RTD ........................................................................ 21  
9.6 Cable compensation RTD 2 with 2 x RTD or TC with external cold junction compensation (TC + CJ  
external) ........................................................................................................................................................... 22  
9.7  
Automatic potentiometer adjustment (teach-in) ......................................................................................... 22  
9.8 Manual acknowledgement of switching outputs (latch function).............................................................. 22  
9.9 LED status indicators ........................................................................................................................22  
10 Password...................................................................................................................................23  
11 Flow chart, operator interface ....................................................................................................23  
11.1 Menu structure ................................................................................................................................................ 24  
11.2 Key for start screen......................................................................................................................................... 25  
11.3 Key for SETTINGS - MENU .......................................................................................................................... 25  
11.4 Key for SETTINGS - Configure..................................................................................................................... 25  
11.5 Key for SETTINGS - Service......................................................................................................................... 26  
11.6 Key for SETTINGS - Save ............................................................................................................................. 26  
11.7 Key for input..................................................................................................................................................... 27  
11.7.1 Key for input configuration (analog input) ..................................................................................................... 27  
11.8 Key for output .................................................................................................................................................. 29  
11.8.1 Key for output configuration (analog output)................................................................................................. 29  
11.9 Key for error handling..................................................................................................................................... 30  
11.10 Key for switch .................................................................................................................................................. 30  
104601_en_04  
PHOENIX CONTACT  
3
MACX MCR-EX-T-UI-UP...  
12 IFS-OP-UNIT operator interface error codes .............................................................................30  
13 Configuration with the service PC ..............................................................................................31  
13.1 System requirements ..................................................................................................................................... 31  
13.2 Configuring the user characteristic curve ..........................................................................................31  
14 Comparison of safety data.........................................................................................................31  
15 Application examples.................................................................................................................32  
15.1 Current output ................................................................................................................................................. 32  
15.2 Voltage output ................................................................................................................................................. 32  
15.3 Switching output.............................................................................................................................................. 33  
Appendix  
Safety-related applications (SIL 2) ............................................................................................................................. A-1  
104601_en_04  
PHOENIX CONTACT  
4
MACX MCR-EX-T-UI-UP...  
3
Ordering data  
Temperature transducer, Ex i  
Description  
Type  
Order No.  
2865654  
2924689  
2811763  
2924692  
Pcs. / Pkt.  
Standard configuration/in-stock article, with screw connection  
Standard configuration/in-stock article, with spring-cage connection  
Order configuration/KMAT, with screw connection  
Order configuration/KMAT, with spring-cage connection  
MACX MCR-EX-T-UI-UP  
MACX MCR-EX-T-UI-UP-SP  
MACX MCR-EX-T-UI-UP-C  
MACX MCR-EX-T-UI-UP-SP-C  
1
1
1
1
Accessories  
Description  
Type  
Order No.  
2811899  
2811886  
Pcs. / Pkt.  
1
1
1
Operator interface for the configuration of compatible MACX modules.  
Cradle unit, for snapping the operating and display unit onto the DIN rail  
IFS-OP-UNIT  
IFS-OP-CRADLE  
Programming adapter for MACX MCR... devices. With USB interface for pro- IFS-USB-PROG-ADAPTER  
gramming with the IFS-CONF software  
2811271  
Cold junction compensation connector for thermocouples  
MACX MCR-EX-CJC  
2925002  
1
For additional accessories, please refer to the INTERFACE catalog from Phoenix Contact.  
104601_en_04  
PHOENIX CONTACT  
5
MACX MCR-EX-T-UI-UP...  
4
Order key  
Order key for temperature transducer MACX-MCR-EX-T-UI-UP(-SP)-C (standard configuration entered as an example)  
Order No.  
Safety Integrity  
Level (SIL)  
Sensor type  
Connection  
method  
Cold junction  
compensation  
Measuring range:  
Start End  
Measuring  
unit  
Output range  
OUT02  
Factory calibration certificate  
= FCC  
2811763  
/
ON  
/
PT100  
/
4
/
0
/
-50  
/
150  
/
C
/
/
NONE  
2811763 ꢀ  
ON active  
See below  
2
3
4
2-wire  
3-wire  
4-wire  
0
1
off, e.g. with  
RTD, R,  
See  
See  
C
F
°C  
°F  
OUT15  
OUT16  
OUT01  
OUT15  
OUT25  
OUT26  
OUT02  
OUT05  
OUT03  
OUT06  
OUT04  
OUT13  
OUT14  
0...5 mA  
0...10 mA  
0...20 mA  
0...5 mA  
1...5 mA  
2...10 mA  
4...20 mA  
0...5 V  
NONE without FCC  
MACX MCR-EX-  
T-UI-UP-C  
below  
below  
potentiometer,  
mV  
NONE not active  
O
P
V
%
YES  
with FCC (a fee is  
charged)  
2924692 ꢀ  
mV  
MACX MCR-EX-  
T-UI-UP-SP-C  
ON only with output  
range = OUT02  
on, e.g. with TC  
YESPLUS Factory calibration  
certificate with  
0...10 V  
5 measuring points  
(a fee is charged)  
1...5 V  
2...10 V  
-5...+5 V  
-10...+10 V  
others freely  
configurable in the  
software  
Other setting options can be configured  
with the IFS-CONF software.  
Smallest measuring  
range  
-
Freely configurable user characteristic with  
30 interpolation points  
Resistance thermometers RTD  
Others can be selected or are freely  
configured in the software.  
PT100  
Pt 100 acc. to IEC/EN 60751  
-200  
-200  
-200  
-200  
-200  
-200  
-200  
-200  
-200  
-200  
-60  
850  
850  
850  
850  
850  
850  
850  
850  
850  
850  
250  
250  
180  
180  
160  
500  
200  
180  
150  
300  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
20 K  
100 K  
100 K  
100 K  
20 K  
20 K  
PT200  
Pt 200 acc. to IEC/EN 60751  
PT500  
Pt 500 acc. to IEC/EN 60751  
-
Output behavior in the event of a short circuit,  
sensor break, or overrange/underrange is  
freely configurable or can be set according to  
NE43 (standard configuration: NE43 upscale)  
PT1000  
PT100S  
PT1000S  
PT100G  
PT1000G  
PT100J  
PT1000J  
NI100  
Pt 1000 acc. to IEC/EN 60751  
Pt 100 acc. to Sama RC21-4-1966  
Pt 1000 acc. to Sama RC21-4-1966  
Pt 100 acc. to GOST 6651  
Pt 1000 acc. to GOST 6651  
-
-
Filter setting (standard configuration: 1)  
Pt 100 acc. to JIS C1604/1997  
Pt 1000 acc. to JIS C1604/1997  
Ni 100 acc. to DIN 43760/DIN IEC 60751  
Ni 1000 acc, to DIN 43760/DIN IEC 60751  
Ni 100 acc. to Sama RC21-4-1966  
Ni 1000 acc. to Sama RC21-4-1966  
Ni 1000 (Landis & Gyr)  
Restart after failsafe  
(standard configuration: ON)  
NI1000  
NI100S  
NI1000S  
NI1000L  
CU10  
-60  
-
Switching behavior: Switching output ?  
(limit values, times, etc.) (standard  
configuration: OFF)  
-60  
-60  
-50  
Cu 10 acc. to Sama RC21-4-1966  
-70  
CU50  
Cu 50/Cu 100 acc. to GOST 6651 (  
= 1.428)  
-50  
CU53  
Cu 53 acc. to GOST 6651 (= 1.426)  
-50  
KTY81  
KTY84  
KTY81-110 (Philips)  
-55  
KTY84-130 (Philips)  
-40  
Thermocouples TC  
B
E
acc. to IEC/EN 60584 (Pt30Rh-Pt6Rh)  
acc. to IEC/EN 60584 (NiCr-CuNi)  
acc. to IEC/EN 60584 (Fe-CuNi)  
acc. to IEC/EN 60584 (NiCr-Ni)  
acc. to IEC/EN 60584 (NiCrSi-NiSi)  
acc. to IEC/EN 60584 (Pt13Rh-Pt)  
acc. to IEC/EN 60584 (Pt10Rh-Pt)  
acc. to IEC/EN 60584 (Cu-CuNi )  
acc. to DIN 43760 (Fe-CuNi)  
acc. to DIN 43760 (Cu-CuNi)  
C ASTM JE988 (2002)  
500  
-230  
-210  
-250  
-250  
-50  
-50  
-200  
-200  
-200  
0
1820  
1000  
1200  
1372  
1300  
1768  
1768  
400  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
Others can be selected in the software.  
J
K
N
R
S
T
L
900  
U
600  
CA  
DA  
A1G  
A2G  
A3G  
MG  
LG  
2315  
2315  
2500  
1800  
1800  
100  
D ASTM JE988 (2002)  
0
A-1 GOST 8.585-2001  
0
A-2 GOST 8.585-2001  
0
A-3 GOST 8.585-2001  
0
M GOST 8.585-2001  
-200  
-200  
L
GOST 8.585-2001  
800  
Remote resistance-type sensors R  
(2-, 3-, 4-wire)  
RES03  
RES05  
RES06  
RES09  
RES10  
RES12  
Resistance 0...150 ꢀ  
Resistance 0...600 ꢀ  
Resistance 0...1200 ꢀ  
Resistance 0...6250 ꢀ  
Resistance 0...12,500 ꢀ  
Resistance 0...50,000 ꢀ  
0
0
0
0
0
0
150  
600  
Others can be selected in the software.  
10% of the selected  
measuring range  
1200  
6250  
12500  
50000  
Potentiometers  
POT03  
POT05  
POT06  
POT09  
POT10  
POT12  
Potentiometer 0...150 ꢀ  
Potentiometer 0...600 ꢀ  
Potentiometer 0...1200 ꢀ  
Potentiometer 0...6250 ꢀ  
Potentiometer 0...12,500 ꢀ  
Potentiometer 0...50,000 ꢀ  
0
0
0
0
0
0
100  
100  
100  
100  
100  
100  
%
%
%
%
%
%
3-wire  
Others can be selected in the software.  
10% of the selected  
measuring range  
Voltage signals mV  
V04  
Voltage (mV)  
-1000  
+1000  
mV  
10% of nominal  
span  
Others can be selected in the software.  
9
Temperature conversion guide for °C to °F:  
T [°F] = – T [°C] + 32  
5
104601_en_04  
PHOENIX CONTACT  
6
MACX MCR-EX-T-UI-UP...  
5
Technical data  
Input  
Resistance thermometer  
Thermocouple sensor  
Pt, Ni, Cu sensors: 2-, 3-, 4-wire  
B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG  
(see example, “Order key” on page 6)  
Resistor  
0 ... 50 kΩ  
Potentiometer  
Voltage  
0 ... 50 kΩ  
-1000 mV ... 1000 mV  
Output  
Output signal  
4 mA ... 20 mA with SIL ON  
(further output signals can be configured with SIL OFF)  
Maximum output signal  
Voltage output  
Current output  
±11 V  
22 mA  
Load  
Voltage output  
10 kΩ  
Current output  
600 (at 20 mA)  
Behavior in the event of a sensor error  
According to NE 43 (or freely definable)  
Switching output  
Contact type  
1 PDT contact  
Contact material  
AgSnO2, hard gold-plated  
30 V AC (30 V DC)  
0.5 A (30 V AC) / 1 A (30 V DC)  
Maximum switching voltage  
Maximum switching current  
Cycles  
5
With ohmic load  
1 x 10  
General data  
Supply voltage range  
Current consumption  
Power consumption  
Temperature coefficient  
Step response (0 ... 99 %)  
With SIL  
24 V ... 230 V AC/DC (-20%/+10%, 50/60 Hz)  
< 50 mA (24 V DC)  
< 1.5 W  
0.01 %/K, maximum  
Typ. 1000 ms  
Typ. 700 ms  
Without SIL  
Transmission error, total  
Electrical isolation  
Input/output  
< 0.1% (e.g., for PT100, 300 K span, 4 ... 20 mA)  
4-way, between input/output/power supply/switching output  
375 V P (according to EN 60079-11)  
Input/power supply  
Input/switching output  
Output/power supply  
Power supply/switching output  
Ambient temperature  
Operation  
375 V P (according to EN 60079-11)  
375 V P (according to EN 60079-11)  
300 V rms reinforced insulation (according to EN 61010/50178)  
300 V rms reinforced insulation (according to EN 61010/50178)  
-20 °C ... +65°C  
Storage/transport  
Permissible humidity (operation)  
Shock  
-40 °C ... +85°C  
5% ... 95% (no condensation)  
15g, IEC 60068-2-27  
Vibration  
5g, IEC 60068-2-6  
Status indicators  
Green LED (supply voltage, PWR)  
Red LED, flashing (cable error, sensor error, ERR)  
Red LED (module error, ERR)  
Yellow LED (switching output)  
104601_en_04  
PHOENIX CONTACT  
7
MACX MCR-EX-T-UI-UP...  
General data [...]  
Housing material  
PA 66-FR  
Color  
Green  
Degree of protection  
Pollution degree  
IP20  
2
Dimensions (width x height x depth)  
Inflammability class according to UL 94  
Design  
17.5 x 99 x 114.5 mm  
V0  
Terminal housing for mounting on DIN rails  
Conformance  
EMC directive 2004/108/EC  
Ex directive (ATEX)  
1
EN 61326-1; EN 61000-6-2 ; EN 61000-6-4  
EN 60079-0, EN 60079-11, EN 60079-15, EN 61241-0, EN 61241-11  
1
During the interference, there can possibly be small deviations.  
Safety data according to ATEX for intrinsically safe circuits  
Maximum voltage (Uo)  
6 V  
Maximum current (Io)  
Maximum power (Po)  
Gas group  
Maximum external inductance (Lo)  
Maximum external capacity (Co)  
Maximum internal inductance (Ci)  
Maximum internal inductance (Li)  
7.4 mA  
11 mW  
Ex ia IIC  
100 mH  
1.3 µF  
44 nF  
Ex ia IIB  
100 mH  
6.8 µF  
10 mH  
1.7 µF  
44 nF  
1 mH  
2.6 µF  
44 nF  
10 mH  
9.2 µF  
44 nF  
1 mH  
15 µF  
44 nF  
44 nF  
Negligible  
Maximum voltage U  
253 V AC (125 V DC)  
m
Approvals  
ATEX  
X II (1)G [Ex ia] IIC; X II (1)D [Ex iaD]  
X II 3 G Ex nAC ic IIC / IIB / IIA T4 X  
[Ex ia] IIC; [Ex iaD]; Ex nAC ic IIC T4  
Applied for  
IBExU 10 ATEX 1044  
IBExU 10 ATEX 1044  
IECEx IBE 10.0004X  
IECEx approval  
UL, USA/Canada  
Functional safety (SIL)  
Can be used up to SIL 2  
Connection data MACX MCR-EX-T-UI-UP  
Conductor cross section  
Solid (minimum/maximum)  
Stranded (minimum/maximum)  
AWG/kcmil (minimum/maximum)  
Stripping length  
2
2
2
0.2 mm /2.5 mm  
2
0.2 mm /2.5 mm  
24/14  
7 mm  
Connection method  
Plug-in screw connection  
Tightening torque  
Minimum 0.5 Nm/maximum 0.6 Nm  
Connection data MACX MCR-EX-T-UI-UP-SP  
Conductor cross section  
Solid (minimum/maximum)  
Stranded (minimum/maximum)  
AWG/kcmil (minimum/maximum)  
Stripping length  
2
2
2
0.2 mm /1.5 mm  
2
0.2 mm /1.5 mm  
24/16  
8 mm  
Connection method  
Spring-cage connection  
104601_en_04  
PHOENIX CONTACT  
8
MACX MCR-EX-T-UI-UP...  
6.5  
Cold junction error  
6
Minimum span and measuring  
accuracies  
Cold junction error: ± 1 K, maximum  
(with internal cold junction compensation).  
With external compensation it depends on the quality of the  
cold junction and the sensor used.  
6.1  
Pt and Ni-RTD inputs  
Minimum measuring span:  
With 10 Ω ≤ R < 100 : 100 K  
0
0
6.6  
Voltage signal input  
With 100 Ω ≤ R 10 k: 20 K  
Minimum measuring span:  
10% of the nominal span of the respective range.  
Measuring accuracy:  
-1000 ... 1000 mV : 0.01% (of measuring range)  
-500 ... 500 mV : 0.01% (of measuring range)  
-250 ... 250 mV : 0.01% (of measuring range)  
-125 ... 125 mV : 0.01% (of measuring range)  
Measuring accuracy:  
For 10 Ω ≤ R < 100 : 0.2 K x 100 / R  
0
0
= 0.1% x (100 /R ) x (200 K/measuring span)  
0
For 100 Ω ≤ R 1 k: 0.2 K  
0
= 0.1% x (200 K/measuring span)  
For 1 k< R 10 k: 0.4 K  
0
= 0.1% x (400 K/measuring span)  
-60 ...  
-30 ...  
-15 ...  
60 mV : 0.01% (of measuring range)  
30 mV : 0.01% (of measuring range)  
15 mV : 0.01% (of measuring range)  
6.2  
Cu-RTD inputs  
Minimum measuring span:  
6.7  
R transducers and resistors  
For 10 Ω ≤ R < 100 : 100 K  
0
For 100 Ω ≤ R 10 k: 20 K  
0
50% of measuring range (nominal value of R transducer +  
lead resistance) measuring range  
Minimum measuring span: 10% of the selected measuring  
range  
Measuring accuracy:  
For 10 Ω ≤ R < 100 : 0.5 K x 100 /R  
0
0
= 0.1% x (100 /R ) x (500 K/measuring span)  
0
For 100 Ω ≤ R 1 k: 0.5 K  
0
Measuring accuracy:  
= 0.1% x (500 K/measuring span)  
0 ...  
0 ...  
0 ...  
0 ...  
75 : 0.10% (of measuring range)  
150 : 0.05% (of measuring range)  
300 : 0.02% (of measuring range)  
600 : 0.01% (of measuring range)  
For 1 k< R 10 k: 1.0 K  
0
= 0.1% x (1000 K/measuring span)  
6.3  
NI1000 input (Landis & Gyr), KTY 81-110,  
KTY 84-130 (Philips)  
0 ... 1200 : 0.01% (of measuring range)  
0 ... 2400 : 0.01% (of measuring range)  
0 ... 4800 : 0.01% (of measuring range)  
0 ... 6250 : 0.02% (of measuring range)  
0 ... 12500 : 0.02% (of measuring range)  
0 ... 25000 : 0.02% (of measuring range)  
0 ... 50000 : 0.02% (of measuring range)  
Minimum measuring span: 20 K  
Measuring accuracy: 0.2 K  
6.4  
Thermocouple input  
Minimum measuring span with TC: 50 K  
Measuring accuracy of the input with TC signals:  
TC type E, J, K, N, T, L, U, M, Lr  
Without cold junction error: 0.30 K  
TC types B, R, S, C, D, A1, A2, A3  
Without cold junction error: 0.50 K  
Example:  
R transducer with nominal value: 1000 Ω  
Measuring range to be selected: 0 ... 1200 Ω  
Minimum measuring span: 10% of the selected measuring  
range = 120 Ω  
Measuring accuracy: 0.01% of the selected measuring  
range = 120 mΩ  
104601_en_04  
PHOENIX CONTACT  
9
MACX MCR-EX-T-UI-UP...  
6.8  
Potentiometer  
50% of measuring range (nominal value of potentiometer  
+ lead resistance) measuring range  
Minimum measuring span: 10% of the selected measuring  
range  
Measuring accuracy:  
0 ...  
0 ...  
0 ...  
0 ...  
75 : 0.10% (of measuring range)  
150 : 0.05% (of measuring range)  
300 : 0.02% (of measuring range)  
600 : 0.02% (of measuring range)  
0 ... 1200 : 0.02% (of measuring range)  
0 ... 2400 : 0.02% (of measuring range)  
0 ... 4800 : 0.02% (of measuring range)  
0 ... 6250 : 0.10% (of measuring range)  
0 ... 12500 : 0.10% (of measuring range)  
0 ... 25000 : 0.10% (of measuring range)  
0 ... 50000 : 0.10% (of measuring range)  
Example:  
Potentiometer with nominal value: 1000 Ω  
Measuring range to be selected: 0 ... 1200 Ω  
Minimum measuring span: 10% of the selected measuring  
range = 120 Ω  
Measuring accuracy: 0.02% of the selected measuring  
range = 240 mΩ  
6.9  
Output signals  
Analog output error  
2 mV  
2 mV  
4 µA  
0.01% at -10 ... 10 V  
0.02% at 0 ... 10 V  
0.02% at 0 ... 20 mA  
104601_en_04  
PHOENIX CONTACT 10  
MACX MCR-EX-T-UI-UP...  
7
Safety regulations and installation notes  
7.1  
Installation and operation  
7.2  
Safety regulations for installation in poten-  
tially explosive areas  
WARNING: Sensor does not conform to the  
specification  
Regulations for intrinsically safe circuits  
Make sure that the connected sensors are only  
used in the specified area (see “Order key” on  
page 6).  
WARNING: Explosion hazard  
The devices are approved for intrinsically safe (Ex  
i) circuits up to zone 0 (gas) and Ex zone 20  
(dust). The technical safety values of the intrinsi-  
cally safe field devices have to match the specifi-  
cations of this package slip or otherwise the EC-  
type examination certificate.  
WARNING: Sensor wiring  
Check the structure for functionally correct wiring  
(see “Basic circuit diagrams” on page 13).  
Follow the installation instructions.  
WARNING: Explosion hazard  
NOTE: Installation, operation, and maintenance  
may only be carried out by qualified specialist per-  
sonnel.  
If the device has been used in non-intrinsically  
safe circuits, it must not be used again in intrinsi-  
cally safe circuits. Label the device clearly as be-  
ing not intrinsically safe.  
When installing and operating the device, the applicable  
safety directives (including national safety directives), acci-  
dent prevention regulations, as well as general technical  
regulations must be observed.  
WARNING: Explosion hazard  
If the device has been used in non-intrinsically  
safe circuits, it must not be used again in intrinsi-  
cally safe circuits. Label the device clearly as be-  
ing not intrinsically safe.  
NOTE:  
Do not open the device or making changes to it.  
Do not repair the device yourself; replace it with  
an equivalent device. Repairs may only be per-  
formed by the manufacturer. The manufacturer is  
not liable for damage resulting from violation.  
Installation in zone 2  
WARNING: Explosion hazard  
The device is associated equipment of the Ex-i  
protection type and is suitable for installation in  
zone 2.  
NOTE: The IP20 degree of protection (IEC  
60529/EN 60529) of the device is intended for  
use in a clean and dry environment. Do not sub-  
ject the device to mechanical and/or thermal  
loads that exceed the specified limits.  
Observe the specified conditions for use in potentially ex-  
plosive areas.  
WARNING: Explosion hazard  
NOTE: Only specified devices from Phoenix  
Contact may be connected to the 12-pos. S-  
PORT interface.  
Install the device in a suitable, approved housing  
with a minimum of IP54 degree of protection.  
At the same time, observe IEC 60079-14/EN  
60079-14 requirements.  
For safety data, please refer to this data sheet and the cer-  
tificates (EC-type examination certificate, and other approv-  
als, if necessary).  
WARNING: Explosion hazard  
Disconnect the block power supply before:  
Connecting or disconnecting cables of non-  
intrinsically safe circuits.  
WARNING: Explosion hazard  
Use only category 3G modules (ATEX 94/9/EC).  
104601_en_04  
PHOENIX CONTACT 11  
MACX MCR-EX-T-UI-UP...  
WARNING: Explosion hazard  
The device must be stopped and immediately re-  
moved from the Ex area if it is damaged, was sub-  
jected to an impermissible load, stored incorrectly  
or if it malfunctions.  
Installation in areas with a danger of dust explosions  
WARNING: Explosion hazard  
The device is not designed for installation in ar-  
eas with a danger of dust explosions.  
Connection to the intrinsically safe circuit in areas with  
a danger of dust explosions (zones 20, 21 and 22) is only  
permitted if the equipment connected to this circuit is ap-  
proved for this zone (e.g., category 1D, 2D or 3D).  
WARNING: Explosion hazard  
If, however, you wish to use the device in zone 22,  
it must be installed in a housing that complies with  
IEC/EN 61241-1. In doing so, observe the maxi-  
mum surface temperatures. Observe the require-  
ments of IEC/EN 61241-14.  
NOTE: Install the device in a suitable housing  
with IP54 protection.  
7.3  
Use in safety-related applications (SIL 2)  
When using the MACX MCR-EX-T-UI-UP... in safety-relat-  
ed applications, observe the instructions in the appendix, as  
the requirements differ for safety-related functions. .  
The switching output is not intended for safety-re-  
lated applications.  
104601_en_04  
PHOENIX CONTACT 12  
MACX MCR-EX-T-UI-UP...  
8.2  
MACX MCR-...  
Structure  
8
Installation  
NOTE: Electrostatic discharge!  
7 mm  
0,5-0,6 Nm  
5-7 lb In  
The device contains components that can be  
damaged or destroyed by electrostatic discharge.  
When handling the device, observe the neces-  
sary safety precautions against electrostatic dis-  
charge (ESD) according to EN 61340-5-1 and EN  
61340-5-2.  
1.3  
1.2  
1.1  
1
32825  
2.3  
ExBTloemmberg,  
2.2  
2.1  
MA  
Germany  
CX  
S
upp  
Ord.  
M
perature  
CR  
24V ly  
3.3  
No.: –EX–T–UI–UP  
2865654  
Transducer/Ex  
(–20%...+10V%,  
...  
230Volta  
3.2  
AC/gDeC  
U
3.1  
:
m
=
=
253V  
1,5W  
P
50Hz/60Hz)  
N
Inpu  
RTD, t  
–Temperaturmessumform  
TC,  
A
0
na  
mV,  
/
lo  
20mA  
g
Poti,  
–O  
U
ut  
1.1  
R
m
=
=
N
253V  
30V  
igita (Zone  
U
10V  
m
C
D
0,5A  
1.2  
2.3  
1
2
Take precautions against electrostatic discharge  
before opening the front cover.  
er  
1.3  
1
2.2 3.3  
2
3.2  
1
l
–O  
2)  
1
1
2.1  
4
(30V  
u
6
C
T
t
2.2  
U
o
u
amb –20°...+A  
5)°C/  
t
2.3  
I
M
U
o
/
u
OUT  
G
N
D
ax.  
t
1
A
3.1  
(30V  
V
O
3.2  
a
lues –4°...+149°F  
DC)  
V
DC  
=
=
=
6,0  
7,4  
11  
I
3.3  
O
P
O
mA  
see  
μc  
mW  
manual  
WARNING  
S
-
P
O
R
3
4
DO  
NOT  
AND  
T
5.1  
SEPARATE  
INSTALLED  
5.2  
www.phoenixcontact.com  
WHEN  
R
5.3  
PW  
I
N
4.1  
4.2  
ZONE  
8.1  
Basic circuit diagrams  
ENERGIZED  
DAT  
ERR  
2
4.3  
O
D
IN  
MCR-EX-T-UI-UP  
Sensor / Field  
PLC / DCS  
OUT  
IN  
+
5
MACX  
passive  
4.3  
4.2 5.3  
5.2  
-
Poti  
-
4.3 4.3  
3.3  
GND 3.3 3.3  
OUT 3.2  
+
I
4.2 4.2  
4.1 4.1  
3.2  
+
UOUT 3.1 3.1  
RTD1  
RTD  
2.3 2.3 14  
2.2 2.2 11  
2.1 2.1 12  
4.3  
4.2  
4.1  
ϑ
ϑ
ϑ
Figure 3 Structure MACX MCR-EX-T-UI-UP  
MACX MCR-...-SP  
DI  
ϑ
5.3 5.3  
5.2 5.2  
5.1 5.1  
NC 1.3  
8 mm  
RTD2  
ϑ
1.2  
1.1  
Power  
24V ...230V AC/DC  
1.3  
1.2  
1.1  
2.3  
1
32825  
2.2  
Zone 0,1,2  
Zone 20,21,22  
ExBTloemmberg,  
Supply  
2.1  
M
Zone 2  
AC  
G
ermany  
perature  
X
N
Ord.  
M
C
R
.
:
3.3  
24V  
(–20%...+10V%o, ltage:  
–EX–T–UI–UP–SP  
2924689  
3.2  
o
...  
230V  
3.1  
Transducer/Ex  
U
P
=
=
AC/DC  
m
253V  
1,5W  
50Hz/60Hz)  
N
Input  
RTD,  
–Temperaturm  
TC,  
Analog–Out  
mV,  
Figure 1  
Sensor connection - resistance thermometers  
and potentiometers  
0
Poti,  
2)  
20mA  
U
1.1  
R
essum  
m
=
=
N
253V  
/
U
10V  
m
C
form  
Digi3ta0Vl–Out  
1.2  
.3  
2
3
1
2
(Zone  
er  
.2  
.2  
.3  
1.3  
1
2
3
1
0,5A  
1
1
2.1  
4
(30V  
T
2.2  
U
amb  
AC)  
out  
20°...+65°C/  
2.3  
I
Max.  
out  
/
O
U
G
N
D
1
A
T
3.1  
U
=
(
Values –4°..3.+01V49D°CF)  
O
O
O
3.2  
6
7
8
9
6
I
=
,
3.3  
0
V
DC  
7
P
,
4
m
=
A
mW  
11  
see  
μ
c
m
anu  
WARNING  
al  
S
-
P
O
R
DO  
AND  
T
NOT  
5.1  
SEPARATE  
INSTALLED  
5.2  
www.phoenixcontact.com  
R
PW  
5.3  
WHEN  
IN  
4.1  
ZONE  
ENERGIZED  
4.2  
AT  
D
2
4.3  
Sensor / Field  
PLC / DCS  
OUT  
IN  
ERR  
DO  
IN  
passive  
MCR-EX-T-UI-UP-SP  
MACX MCR-EX-CJC  
4.3 4.3  
4.2 4.2  
-
+
-
MACX  
3.3  
GND 3.3 3.3  
OUT 3.2  
.3  
.3  
TC  
4
5
.2  
.2  
+
4
5
I
3.2  
-
+
+
UOUT 3.1 3.1  
4.1 4.1  
2.3 2.3 14  
2.2 2.2 11  
2.1 2.1 12  
4.3  
4.2  
4.1  
DI  
Figure 4  
Structure MACX MCR-EX-T-UI-UP-SP  
5.3 5.3  
5.2 5.2  
5.1 5.1  
NC 1.3  
mV  
TC  
1.2  
1.1  
1
2
3
4
5
6
7
8
Plug-in COMBICON connectors  
Power  
-
24V ...230V AC/DC  
+
S-PORT (12-pos. programming interface)  
Button S3 (UP), adjustment and reset functions  
Button S2 (DOWN), adjustment and reset functions  
DIP switch S1 for service mode  
PWR LED, green, power supply  
DAT LED, green, no function at present  
Zone 0,1,2  
Zone 20,21,22  
Zone 2  
Figure 2  
Sensor connection - thermocouples and mV  
sources  
LED ERR, red, module, cable and sensor error, under-  
range or overrange, service mode  
9
DO LED, yellow, status of switching output  
104601_en_04  
PHOENIX CONTACT 13  
MACX MCR-EX-T-UI-UP...  
8.3  
Dimensions  
8.5  
Connecting the cables  
Screw terminal blocks (for MACX MCR-EX-T-UI-UP);  
litz wires provided with ferrules.  
17,5  
99  
Permissible cable cross section: 0.2 mm2 to 2.5 mm2  
Spring-cage terminal blocks (for  
MACX MCR-EX-T-UI-UP-SP); litz wires provided with  
ferrules.  
Permissible cable cross section: 0.2 mm2 to 1.5 mm2  
Install intrinsically safe and non-intrinsically safe cables  
separately.  
Screw connection:  
Insert the conductor into the corresponding con-  
nection terminal block.  
Use a screwdriver to tighten the screw in the open-  
ing above the connection terminal block.  
Spring-cage connection:  
Figure 5  
Dimensions (in mm)  
Insert a screwdriver into the opening above the  
connection terminal block.  
8.4  
Mounting  
Insert the conductor into the corresponding con-  
nection terminal block.  
WARNING: Explosion hazard  
If the module has been used in non-intrinsi-  
cally safe circuits, it must not be used again in  
intrinsically safe circuits.  
The module must be clearly labeled as non-intrin-  
sically safe.  
8.6  
Power supply  
The power supply has been designed as a wide range  
power supply (19.2 ... 253 V AC/DC). The module is sup-  
plied with voltage via connection terminal blocks 1.1 and  
1.2.  
Figure 6  
Mounting and removal  
Mount the module on a 35 mm DIN rail according to EN  
60715.  
Install the module in a suitable housing to meet the re-  
quirements for the protection class.  
Before startup, check for correct function and wiring of  
the MACX MCR-EX-T-UI-UP..., in particular the wiring  
and marking of the intrinsically safe circuits.  
104601_en_04  
PHOENIX CONTACT 14  
MACX MCR-EX-T-UI-UP...  
8.7.6 Measuring resistances  
Up to 75 : RL 2.5 for each lead.  
8.7  
Sensor types  
The sensor types that can be used and their specific proper-  
ties can be found in Section “Order key” on page 6  
Depending on the connection method, the following termi-  
nal points are to be connected for temperature measure-  
ment (see Figure 1 on page 13).  
Up to 150 : RL 5 for each lead.  
Up to 300 : RL 10 for each lead.  
The terminal points 4.2 and 4.3 are used for measuring dif-  
fering resistances.  
8.7.1 Thermocouple (TC) with internal cold junction  
compensation  
8.8  
Current output  
Thermocouple connection: Terminals 4.1 “+“, 4.2 “-“  
The current output can be freely configured between 0 and  
20 mA. The minimum span is 4 mA. In safety-related appli-  
cations (SIL = ON), the output is fixed at 4 ...20 mA.  
Use the MACX MCR-EX-CJC cold junction com-  
pensation connector provided (Order No.  
2925002).  
Connection: Terminals 3.2 “+“, 3.3 “-“  
8.9  
Voltage output  
TC+CJ: Use the cold junction compensation con-  
nector provided at connection terminal blocks  
4.1, 4.2 and 4.3.  
The voltage output cannot be used for safety-re-  
lated applications (SIL = ON).  
8.7.2 Thermocouple (TC) with external or without  
cold junction compensation  
The voltage output can be freely configured between -10  
and +10 V. The minimum span is 2 V.  
Connection: Terminals 3.1 “+“, 3.3 “-“  
Thermocouple connection: Terminals 5.1 “+“, 5.2 “-“  
TC+CJ external: Use the external cold junction  
compensation sensor (e.g., PT100) at connection  
terminal blocks 4.2 and 4.3.  
8.7.3 Voltage input  
Connection: Terminals 5.1 “+“, 5.2 “-“  
8.7.4 Potentiometer  
Connection: Terminals 4.1, 4.2, 4.3  
8.7.5 Resistance thermometer (RTD)  
RL 25 for each lead.  
2-wire connection method: Terminals 4.2, 4.3  
The cable resistance can be compensated with the help  
of the IFS-CONF PC program, the IFS-OP-UNIT opera-  
tor interface or in service mode (DIP switch).  
3-wire connection method: Terminals 4.1, 4.2, 4.3  
In the case of the 3-wire connection method, ensure  
that all three cable resistances are the same.  
4-wire connection method: Terminals 4.2, 4.3, 5.1, 5.2  
2 x 2-wire connection method  
Terminals RTD 1: 4.2, 4.3  
Terminals RTD 2: 5.1, 5.2  
104601_en_04  
PHOENIX CONTACT 15  
MACX MCR-EX-T-UI-UP...  
8.10 Switching output  
Switching behavior 6  
Switching output picks up between  
Switching output 1 has one PDT. The behavior of the switch-  
ing output can be selected. The switching points SPL1 and  
SPH2 can be configured across the entire sensor range:  
SPL1 and SPH2.  
1
0
SPL  
SPH  
Switching behavior of the switching output  
Switching behavior 0  
Switching behavior 7  
Switching output is permanently  
dropped.  
Switching output drops out between  
1
SPL1 and SPH2.  
1
0
0
SPL  
SPH  
1
2
SPL = Set Point Low (lower switching point)  
SPH = Set Point High (upper switching point)  
Switching behavior 1  
Switching output is permanently  
picked up.  
.
1
0
The switching output is not intended for safety-re-  
lated applications.  
Switching behavior 2  
If only the switching output is to be used, the cur-  
rent output (connection terminal blocks 3.2 and  
3.3) must be short circuited or subjected to a load.  
Switching output picks up when SPH2  
1
is exceeded.  
0
SPH  
Switching behavior 3  
Switching output drops out when SPH2  
is underrange.  
1
0
SPH  
Switching behavior 4  
Switching output picks up when SPL2  
is exceeded and drops out when SPH1  
0
1
is underrange (hysteresis).  
SPL  
SPH  
Switching behavior 5  
Switching output drops out when SPL2  
is exceeded and picks up when SPH1  
is underrange (hysteresis).  
0
1
SPL  
SPH  
104601_en_04  
PHOENIX CONTACT 16  
MACX MCR-EX-T-UI-UP...  
8.11.2 (Switching behavior (3): Overtemperature limit  
8.11 Switching output behavior with manual ac-  
knowledgement (latching)  
(SPH)  
Latching: No automatic restart after exceeding  
limit value (SPH: SET Point High) or falling below  
limit value (SPL: Set Point Low).  
1
0
SPH  
Disable the option “Restart after fail safe” in the  
configuration software.  
Normal operating state < SPH  
Step  
1
Measure  
Measured  
value  
< SPH and module are acti-  
vated  
8.11.1 Switching behavior (2): Undertemperature limit  
(SPH)  
2
3
Relay  
Measured  
value  
ON  
SPH  
1
0
SPH  
4
5
6
Relay  
Measured value  
Relay  
OFF  
< SPH  
Normal operating state > SPH  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Step  
1
Measure  
Measured  
value  
> SPH and module are acti-  
vated  
2
3
Relay  
ON  
Measured  
value  
SPH  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
4
5
6
Relay  
OFF  
Measured value  
Relay  
> SPH  
Critical operating state SPH  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Step  
1
Measure  
Measured  
value  
SPH and module are acti-  
vated  
2
3
Relay  
Measured  
value  
OFF  
< SPH  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Critical operating state SPH  
Step  
1
Measure  
Measured  
value  
Relay  
Measured  
value  
SPH and module are acti-  
vated  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
2
3
OFF  
> SPH  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
104601_en_04  
PHOENIX CONTACT 17  
MACX MCR-EX-T-UI-UP...  
8.11.3 Switching behavior (4): Undertemperature limit  
8.11.4 Switching behavior (5): Overtemperature limit  
with hysteresis (SPL)  
with hysteresis (SPH)  
0
1
0
1
SPL  
SPH  
SPL  
SPH  
Normal operating state > SPL  
Normal operating state < SPH  
Step  
1
Measure  
Measured  
value  
Step  
1
Measure  
Measured  
value  
> SPL and module are acti-  
vated  
< SPH and module are acti-  
vated  
2
3
Relay  
Measured  
value  
ON  
SPL  
2
3
Relay  
Measured  
value  
ON  
SPH  
4
5
6
Relay  
Measured value  
Relay  
OFF  
> SPH  
4
5
6
Relay  
Measured value  
Relay  
OFF  
< SPL  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Critical operating state SPL  
Critical operating state SPH  
Step  
1
Measure  
Measured  
value  
Step  
1
Measure  
Measured  
value  
SPL and module are acti-  
vated  
SPH and module are acti-  
vated  
2
3
Relay  
Measured  
value  
OFF  
> SPH  
2
3
Relay  
Measured  
value  
OFF  
< SPL  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
104601_en_04  
PHOENIX CONTACT 18  
MACX MCR-EX-T-UI-UP...  
8.11.5 Switching behavior (6): Temperature range lim-  
8.11.6 Switching behavior (7): Temperature range lim-  
it (SPL and SPH)  
it (SPL and SPH)  
1
0
1
0
SPL  
SPH  
SPL  
SPH  
Normal operating state > SPL and < SPH  
Normal operating state < SPL and > SPH  
Step  
1
Measure  
Measured  
value  
Step  
1
Measure  
Measured  
value  
> SPL and < SPH module  
are activated  
a) < SPL and module are acti-  
vated  
2
3
Relay  
Measured  
value  
Relay  
Measured value  
Relay  
ON  
b) > SPH and module are acti-  
vated  
SPL or SPH  
2
3
Relay  
Measured  
value  
Relay  
Measured value  
Relay  
ON  
4
5
6
OFF  
> SPL or < SPH  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
a) SPL and SPH  
b) SPH and SPL  
OFF  
4
5
6
< SPL or > SPH  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Critical operating state SPL and SPH  
1
Measured  
value  
a) SPL and module are acti-  
vated  
Critical operating state SPL and SPH  
b) SPH and module are acti-  
Step  
1
Measure  
Measured  
value  
vated  
SPL and SPH and mod-  
ule are activated  
2
3
Relay  
Measured  
value  
OFF  
a) > SPL and < SPH  
b) < SPH and > SPL  
2
3
Relay  
Measured  
value  
OFF  
< SPL or > SPH  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
4
Relay  
Remains OFF (latches) until  
delay time has passed and  
then acknowledged manu-  
ally  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
Acknowledgement is only possible when  
there is no critical state anymore and the de-  
lay time has passed.  
104601_en_04  
PHOENIX CONTACT 19  
MACX MCR-EX-T-UI-UP...  
8.13.2 Service mode  
8.12 Monitoring function  
Service mode can be selected at any time via the  
IFS-OP-UNIT operator interface and the configuration soft-  
ware, e.g., IFS-CONF or via DIP switch S1.  
The temperature transducer is equipped with monitoring  
functions for the input and output range.  
Input monitoring function  
If settings are changed during service mode and service  
mode is then exited, the temperature transducer performs a  
warm start in order to apply the newly set values. If no  
changes are made, the transducer starts up in normal mea-  
suring mode without a warm start. The switching output  
switches according to its configuration.  
The input monitoring function for line break and short circuit  
refers to the sensor connected to the input. When an error is  
detected, the output signal is set to the configured error  
value. In the case of RTD sensors and resistance-type sen-  
sors, short-circuit failures are detected resistance values <  
1 .  
In service mode, it is also possible to simulate the output sig-  
nal independently of the input signal (force). In this case, in  
safety-related applications the safety function of the device  
is deactivated and the initial value for the analog output sig-  
nal is 2 mA, which allows subsequent devices to detect the  
deviation from normal operation as a result of the measured  
value being underrange.  
Short circuits of thermocouples and mV sources cannot be  
detected, since 0 V can be a valid signal.  
On RTD sensors, resistance-type sensors and potentiome-  
ters, a line break is detected when the current flow through  
the sensor is faulty.  
As soon as the fault has been eliminated, the temperature  
transducer continues to perform its normal functions. (see  
“LED status indicators” on page 22, Line faults)  
During service mode, the switching output is deactivated  
and remains in its idle position.  
Output monitoring function  
The current output can be monitored for line breaks and  
maximum load. This is activated via the configuration. In  
safety-related applications (SIL = ON), the output monitor-  
ing is always active. The voltage output is not monitored. As  
soon as the fault has been eliminated, the temperature  
transducer continues to perform its normal functions. (see  
“LED status indicators” on page 22, Line faults)  
9
Configuration  
WARNING: Explosion hazard  
When configuring in zone 2, the PC used must be  
approved for use in zone 2.  
R
ess  
A
V
m
=
=
/
253  
30  
U
um  
10  
N
m
1
C
V
.
1
form  
3
3
.
.
D
V
1
2
3
12  
.
2
i
(
g
Z
2
2
er  
OU  
i
one  
1
.
.
ta  
11  
.
2
3
3
0,5  
l
8.13 Operating modes  
2)  
1
A
Out  
1
4
2
(30  
.
1
T
V
A
2
.
2
U
amb  
o
Ma 20°  
)
.
3
u
C
t
2
Io  
/
...+  
u
t
1
G
x.  
V
T
65°C  
A
N
3
D
U
.
1
(30  
V
DC)  
...+  
O
O
O
/
3
a
V
=
.
4
2
l
ues  
°
6,0  
I
3
.
3
1
=
=
4
D
9°  
7,  
P
C
F
4
m
A
If the configuration is modified using the  
IFS-OP-UNIT operator interface and PC-based  
software (e.g., IFS-CONF) or via DIP switch, the  
changes made must always be checked again  
and released before transfer to the temperature  
transducer.  
11  
see  
μc  
m
manua  
W
WA  
S3  
S
R
l
-P  
O
R
NIN  
DO  
AN  
T
G
S
N
D
O
5
T
.
1
IN  
E
5
P
S
.
2
www. TALLE  
A
R
R
ATE WHEN ENE  
5
.
3
W
P
D
phoenIN  
Z
4
.
1
O
4
NE  
conta  
T
A
.
2
UP  
ix  
D
2
ct RG  
4
I
.
3
IZE  
D
U
R
R
.
com  
E
-
S2  
S1  
X
-
O
IN  
D
MCR  
C
A
+
M
3
.
.
4
5
2
2
3
.
.
4
5
After the transfer, the new data in the temperature  
transducer is applied by means of activation and  
a warm start.  
Figure 7  
Position of the DIP switch and buttons  
8.13.1 SIL ON/SIL OFF  
When a DIP switch from S1-2 ... S1-8 (ON) is  
switched on, the device is switched to service  
mode. The red ERR LED flashes (1.2 Hz) and a  
diagnostic I/O fault is displayed in the start  
screen.  
The temperature transducer can either be operated in SIL  
ON or SIL OFF. The standard configuration is SIL ON with  
DIP switch S1 set to the OFF position. With the order config-  
uration, customer-specific configurations can be selected in  
the order key (see “Order key” on page 6).  
104601_en_04  
PHOENIX CONTACT 20  
MACX MCR-EX-T-UI-UP...  
9.1  
Delivered state/standard configuration  
9.4  
Force output  
Switch position DIP-S1  
When SIL is activated, the analog output starts at  
2 mA and the switching output is deactivated.  
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF OFF OFF  
Set the adjustment by setting DIP switch S1-4 to ON.  
Observe the analog output and set with the S2 (de-  
scending value) or S3 (ascending value) button.  
The specification/simulation is reset and ended by set-  
ting DIP switch S1-4 back to OFF.  
9.2  
Zero adjust, adjustment via buttons S2  
and S3 (only possible with SIL OFF)  
Set the adjustment by setting DIP switch S1-2 to ON.  
Observe the analog output and set it with button S2 (de-  
scending value) or S3 (ascending value)  
or  
Switch position DIP-S1  
1
2
3
4
5
6
7
8
OFF OFF OFF ON  
OFF OFF OFF OFF  
press the buttons S2 and S3 simultaneously time for >  
3 seconds to reset the cable compensation.  
9.5  
Cable compensation, 2-wire RTD or RTD 1  
with 2 x RTD  
Set the cable compensation RTD 1 via DIP switches  
S1-1 to OFF and  
S1-5 to ON.  
Short circuit the sensor.  
Apply the current measured value as the cable resis-  
tance by pressing the S2 button.  
Save the set value by setting DIP switch S1-2 back to  
OFF.  
Switch position DIP-S1  
1
2
3
4
5
6
7
8
OFF ON OFF OFF OFF OFF OFF OFF  
9.3  
Span adjust, adjustment via buttons 2 and  
4 (only possible with SIL OFF)  
Save the set value by setting DIP switch S1-5 back to  
OFF.  
Set the adjustment by setting DIP switch S1-3 to ON.  
Observe the analog output and set it with button S2 (de-  
scending value) or S3 (ascending value)  
or  
Pressing buttons S2 and S3 simultaneously for > 3 seconds  
resets the cable compensation.  
Switch position DIP-S1  
press the buttons S2 and S3 simultaneously time for >  
3 seconds to reset the cable compensation.  
1
2
3
4
5
6
7
8
Save the set value by setting DIP switch S1-3 back to  
OFF.  
Pressing buttons S2 and S3 simultaneously for > 3 sec-  
onds resets the adjustment.  
OFF OFF OFF OFF ON OFF OFF OFF  
Switch position DIP-S1  
1
2
3
4
5
6
7
8
OFF OFF ON OFF OFF OFF OFF OFF  
104601_en_04  
PHOENIX CONTACT 21  
MACX MCR-EX-T-UI-UP...  
9.6  
Cable compensation RTD 2 with 2 x RTD or  
TC with external cold junction compensa-  
tion (TC + CJ external)  
9.9  
LED status indicators  
3
.
1
2
.
1
1
.
1
3
.
2
32825  
2
.
2
B
1
.
l
2
omberg,  
Ex  
M
A
C
X
Set the cable compensation RTD 2 via DIP switches  
S1-1 to ON and  
S1-5 to ON.  
Short circuit the sensor.  
Apply the current measured value as the cable resis-  
tance by pressing the S2 button.  
T
Germany  
em  
Supp  
Ord  
.
N
3
M
o
.
perature  
3
C
.:  
2
l
... y  
R
4V  
2
V
.
3
EX  
(
o
1
20% 230  
l
.
Atage  
T
292  
3
T
V
10%,  
U
I
UP  
...+  
U
P
ransducer  
4
:
689  
m
=
C
/
253  
DC  
SP  
V
50  
N
=
Hz/  
1,5  
I
60  
nput  
W
/Ex  
Hz  
)
R
T
T
D,  
na  
em  
pe  
T
A
0
C,  
m
ra  
l
V
,
Pot  
og  
turm  
20m Out  
i
,
U
R
e
ssum  
A
/
m
=
253  
30  
U
10  
V
N
m
=
1
C
V
.
form  
1
3
.
D
0,5  
V
1
2
3
.
12  
2
2
1
.
3
i
(
Z
g
er  
OU  
.
.
2
.3  
i
one  
ta  
11  
2
3
l
2)  
1
2
A
Out  
1
4
(30  
.
1
T
V
A
2
U
o
u
am  
.
2
Ma 20°  
.
3
b
C)  
t
2
Io  
/
...+  
u
t
1
G
x.  
=
V
T
65°C  
A
N
3
D
U
.1  
3
(30  
V
DC)  
...+  
O
O
O
/
6
7
8
9
a
V
4
.2  
l
ues  
°
6,0  
I
3
.3  
1
=
=
4
DC  
9°  
7,  
P
F
4
m
A
11  
s
e
μc  
e
m
m
W
a
WA  
n
u
a
G
S
S
-P  
O
R
l
NIN  
R
DO  
AN  
T
N
O
T
5
D
.1  
5
IN  
E
P
S
.
2
www. TALLE  
A
R
R
ATE WHEN ENE  
5
.
3
W
P
S
D
phoenIN  
-
Z
4
.
1
O
4
NE  
contact RG  
2
IZE  
.
UP  
ix  
2
AT  
D
Save the set value by setting DIP switches S1-1 and S1-  
5 back to OFF.  
4
I-  
.
3
D
U
R
.
com  
R
E
-
X
-
IN  
DO  
MCR  
C
A
+
M
Pressing buttons S2 and S3 simultaneously for > 3 seconds  
resets the cable compensation.  
3
.
.
4
5
2
.
2
.
3
4
5
Switch position DIP-S1  
1
2
3
4
5
6
7
8
Figure 8  
No. LED  
LED status indicators  
Color Description  
ON OFF OFF OFF ON  
OFF OFF OFF  
9.7  
Automatic potentiometer adjustment  
(teach-in)  
6
PWR Green  
ON  
Supply voltage  
Indicates the readiness for opera-  
tion of the temperature trans-  
ducer if supply voltage is avail-  
able.  
The temperature transducer is  
configured without device supply  
via programming adapter IFS-  
USB-PROG-ADAPTER.  
Set the teach-in by setting DIP switch S1-6 to ON.  
Set potentiometer to start of range.  
Press the S2 button.  
Set potentiometer to end of range.  
Press the S3 button.  
Save the new measuring range by setting  
DIP switch S1-6 back to OFF.  
7
8
DAT  
ERR  
Green  
Red  
No function at present  
Error  
Pressing buttons S2 and S3 simultaneously for > 3 seconds  
resets both values.  
Switch position DIP-S1  
ON  
Module error  
Flashing Service mode active  
(1.2 Hz)  
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF ON OFF OFF  
flashing  
(2.4 Hz)  
Line fault  
9.8  
Manual acknowledgement of switching  
outputs (latch function)  
9
DO  
Yellow  
ON  
Switching output 1  
Switching output active  
Set manual acknowledgment by setting DIP switch S1-  
7 to ON.  
Press buttons S2 and S3 simultaneously for > 3 sec-  
onds.  
Reset DIP switch S1-7 to OFF.  
Switch position DIP-S1  
1
2
3
4
5
6
7
8
OFF OFF OFF OFF OFF OFF ON OFF  
104601_en_04  
PHOENIX CONTACT 22  
MACX MCR-EX-T-UI-UP...  
the various operating functions that can be selected are  
shown in the display.  
10 Password  
The device is protected by means of a four-digit password  
set in the factory in order to prevent impermissible changes  
to the configuration.  
When active, the SIL functionality is displayed in  
the start screen.  
Default setting: 1111  
Example: Display of SIL ON  
For safety-related applications, the password set  
in the factory must always be changed.  
INPUT 1  
If the password is lost, it is not possible to reset it.  
In this case, please contact Phoenix Contact.  
SIL  
OK  
If, however, only data from the device is to be displayed or  
the device is to be used in non-safety-related applications,  
the password can be deactivated.  
Example: Display of SIL OFF  
Setting: 0000  
The device can be accessed either via the IFS-OP-UNIT  
(Order No.: 2811899) or via a service PC with connected  
programming adapter IFS-USB-PROG-ADAPTER (Order  
No.: 2811271) and the IFS-CONF configuration software.  
INPUT 1  
OK  
Further information on configuration with the  
IFS-OP-UNIT or the IFS-CONF configuration  
software can be found in the relevant user manu-  
al.  
For safety reasons, the SIL function cannot be  
switched on again via the IFS-OP-UNIT operator  
interface.  
WARNING: If Functional Safety is activated by a  
reconfiguration or changes are made to the active  
Functional Safety configuration, the rules under  
Installation and startup must be observed.  
SIL can be switched off/deactivated via the SIL  
OFF menu item.  
To reactivate/switch on the SIL function, PC-  
based configuration software, e.g., IFS-CONF is  
required.  
WARNING: Limitations on safety-related ap-  
plications  
Only 4 ... 20 mA, limited programming of output  
current in the event of line faults  
(2 mA IOut 3.6 mA or IOut 21 mA)  
If no input is entered for five minutes during con-  
figuration, the configuration is ended and any un-  
saved data will be lost.  
WARNING: Once new configuration data has  
been written, the device performs a warm start  
that changes the properties of the device. The fol-  
lowing control device must be adapted to these  
modifications.  
NOTE: Transfer and activate the configuration af-  
ter the password has been changed.  
11 Flow chart, operator interface  
Configuration with the IFS-OP-UNIT  
If you wish to use the MACX MCR-EX-T-UI-UP in combina-  
tion with the IFS-OP-UNIT and with the IFS-OP-CRADLE,  
104601_en_04  
PHOENIX CONTACT 23  
MACX MCR-EX-T-UI-UP...  
11.1 Menu structure  
Input 1  
Input 2  
Input Diff  
Output  
only 2 x RTD2  
and differential measurement  
only 2 x RTD2  
Modul-  
information  
Diagnostic  
OK  
OK / ESC  
OK / ESC  
OK / ESC  
OK / ESC  
OK / ESC  
Settings  
Backlight  
Language  
Configure  
Input  
Input Conf  
CJ on/off  
CJ Value  
Temp-Unit  
Filter  
OK / ESC  
Output  
OK / ESC  
Outp. Conf  
Check  
B/LB  
Reset Cor.  
Err.handl.  
2W-Comp.C1  
2W-Comp.C2  
OK / ESC  
Switch  
OK / ESC  
Switch 1  
On-Delay  
Off-Delay  
Acknowled.  
Linebreak  
Shorted  
OK / ESC  
OK / ESC  
OK / ESC  
Service  
Password  
Save Conf  
Backup  
Restore  
Reset SW1  
Change PW  
SIL OFF  
Reset  
OK / ESC  
OK / ESC  
Save  
Transfer  
Password  
Activate  
OK / ESC  
Restart  
Modul  
104601_en_04  
PHOENIX CONTACT 24  
MACX MCR-EX-T-UI-UP...  
11.2 Key for start screen  
Display of input and output signals, module and diagnostic information.  
Display of the actual value of input 1  
Input 1  
Display of the actual value of input 2, only if a second RTD is configured with the 2-wire connection  
method.  
Input 2  
Input Diff  
Output  
Display of the actual value of the differential measurement with 2 x RTD with the 2-wire connection  
method.  
Display of the actual value of the analog output  
Modul-  
information  
Display of module information (order designation, firmware version, config version)  
Module diagnostics (simulation, module error, I/O error)  
Diagnostic  
11.3 Key for SETTINGS - MENU  
The active configuration is read out from the module.  
Settings  
Backlight  
Language  
Setting for the background illumination (on, off, autodim)  
Setting for the menu language (English, German)  
11.4 Key for SETTINGS - Configure  
Configuration of input, output, fault behavior and switching outputs  
Configure  
104601_en_04  
PHOENIX CONTACT 25  
MACX MCR-EX-T-UI-UP...  
11.5 Key for SETTINGS - Service  
Access to the menu items of the service area  
Service  
Password  
Save Conf  
Reset SW1  
Change PW  
Input of a 4-digit numeric password in order to open the service area  
(if the password is 0000, the password prompt is switched off)  
Access to the menu items for the backup and restore functionality of the module configuration  
Resets switching output 1 when it is snapped on (latching behavior)  
Changes the set password  
(change only becomes effective when the configuration has been transmitted to the module and acti-  
vated)  
Changes the setting from SIL ON to SIL OFF.  
SIL OFF  
NOTE: It is only possible to switch on the SIL function via PC-based configuration software,  
e.g., IFS-CONF.  
Resets the IFS-OP-UNIT and the connected module.  
Reset  
Backup  
Restore  
Saves the active configuration of the connected, compatible module in the IFS-OP-UNIT operator inter-  
face (copy function)  
Transmits the saved module configuration from the internal memory of the IFS-OP-UNIT operator inter-  
face to the connected module (copy function).  
Then activate the configuration by selecting Yes in the Activate menu item.  
11.6 Key for SETTINGS - Save  
Access to the menu items for the transmission and activation of the module configuration  
Save  
Transmits the configuration from the IFS-OP-UNIT operator interface to the connected module  
Transfer  
Password  
Activate  
Input of a 4-digit numeric password in order to transmit the configuration  
(if the password is 0000, the password prompt is switched off).  
Activation of the module configuration (Yes/No)  
Following activation, the module performs a warm start.  
104601_en_04  
PHOENIX CONTACT 26  
MACX MCR-EX-T-UI-UP...  
11.7 Key for input  
Access to the menu items for the configuration of the input  
Input  
(see “Key for input configuration (analog input)” on page 27)  
11.7.1 Key for input configuration (analog input)  
Setting for the dependent parameters of the input mode, sensor type, start and end of range, associated  
inputs, switching behavior, switching points  
Input Conf  
CJ on/off  
CJ Value  
Temp-Unit  
Filter  
Cold junction compensation with TC + CJ and TC + CJ ext. (on, off)  
Correction of the cold junction value with CJ = On,  
specification of the cold junction value with CJ = Off (-20 ... 65 K).  
Setting for the temperature unit (°C, °F)  
Setting for the filter factor (1 ... 10)  
Setting for the cable resistance for RTD 2-wire connection method, channel 1 (0 ... 50 ).  
Setting for the cable resistance for RTD 2-wire connection method, channel 2 (0 ... 50 ).  
2W-Comp.C1  
2W-Comp.C2  
Configuration selection, input configuration  
Input Conf  
Input Configuration  
ESC  
OK  
OK  
Y
OK  
OK  
OK  
ESC  
OK  
Varialble RTD  
Base  
Input Conf  
Sensortype  
RTD Base  
RStart IN1  
REnd IN1  
N
Mode= 2x RTD2  
OK  
OK  
OK  
Y
OK  
OK  
Difference  
RStart IN2  
REnd IN2  
Difference  
Diff RStart  
Diff REnd  
N
Mode= TC + CJ extern  
OK  
Y
OK  
OK  
OK  
OK  
OK  
OK  
Varialble RTD  
Base  
CJ Sensor  
CJ RTDBase  
Con. IN AO  
Con. IN SW1  
Mode SW1  
SPL SW1  
SPH SW1  
N
Input Conf  
104601_en_04  
PHOENIX CONTACT 27  
MACX MCR-EX-T-UI-UP...  
Setting for the sensor mode  
Input Conf  
Sensortype  
RTD Base  
RStart IN1  
REnd IN1  
RStart IN2  
REnd IN2  
Difference  
(RTD4, RTD3, RTD2, 2 x RTD2, TC + CJ, TC + CJ ext., potentiometer, mV).  
Setting for the sensor type depending on sensor mode  
(Pt, Ni, CU, KTY..., USER, for more see “Order key” on page 6).  
RTD basic resistance for sensor types with a variable basic resistance  
(e.g., when 100 is selected, the basic resistance is 100 )  
Start of range for input 1 depending on sensor type, e.g., -50°C (°C, °F, , %, mV).  
End of range for input 1 depending on sensor type, e.g., 150°C (°C, °F, , %, mV)  
Start of range for input 2 depending on sensor type and only for 2 x RTD with 2-wire connection method,  
e.g., -50°C (°C, °F, ).  
End of range for input 2 depending on sensor type and only for 2 x RTD with 2-wire connection method,  
e.g., 150°C (°C, °F, )  
Setting for the differential measurement only for 2 x RTD with 2-wire connection method and not resis-  
tance  
(off, differential, absolute value differential)  
Start of range for differential, only with differential and absolute value differential (°C, °F)  
End of range for differential, only with differential and absolute value differential (°C, °F)  
Sensor type of the cold junction, only with TC + CJ ext.  
Diff RStart  
Diff REnd  
CJ Sensor  
CJ RTDBase  
Con. IN AO  
Con. IN SW1  
Mode SW1  
SPL SW1  
RTD basic resistance of the cold junction, only with TC + CJ ext.  
Associated input of the analog output (input 1, input 2, differential), appears only in sensor mode 2 x RTD2  
(2 x RTD 2-wire connection method)  
Associated input of the switching output (input 1, input 2, differential), appears only in sensor mode 2 x  
RTD2 (2 x RTD 2-wire connection method)  
Mode of switching output (0 ... 7)  
(see “Switching output” on page 16)  
Setpoint low of switching output (appears only if mode > 3)  
(see “Switching output” on page 16).  
Setpoint high of switching output (appears only if mode > 1)  
(see “Switching output” on page 16)  
SPH SW1  
104601_en_04  
PHOENIX CONTACT 28  
MACX MCR-EX-T-UI-UP...  
11.8 Key for output  
Access to the menu items for the configuration of the output  
Output  
(see “Key for output configuration (analog output)” on page 29)  
11.8.1 Key for output configuration (analog output)  
Setting for the dependent parameters of the analog output – mode, start and end of range, display of cor-  
rection values, fault behavior (OR, UR, LB, KS)  
Outp. Conf  
Check  
B/LB  
Monitoring of output load/short circuit (Yes/No), only configurable with SIL = OFF  
Resets the correction values of the output  
Reset Cor.  
Configuration selection, output configuration  
Outp. Conf  
Output Configuration  
OK / ESC  
OK  
OK  
OK  
OK  
Outp. Conf  
RangeStart  
RangeEnd  
Corr. Start  
Corr. End  
ESC  
OK  
OK  
OK  
OK  
Outp. Conf  
Overrange  
Underrange  
Linebreak  
Shorted  
Start of range for output – setting only possible with SIL = OFF, 4 mA (0 ... 20 mA, -10 ... 10 V)  
End of range for output – setting only possible with SIL = OFF, 20 mA (0 ... 20 mA, -10 ... 10 V)  
Display of the start correction value for the analog output (mA, V)  
RangeStart  
RangeEnd  
Corr.Start  
Corr.End  
Display of the end correction value for the analog output (mA, V)  
Analog output value when overrange NE43 Upsc. / NE43 Downsc.  
Overrange  
Underrange  
Linebreak  
Shorted  
(Configurable for fault behavior = freely definable)  
Analog output value for underrange NE43 Upsc. / NE43 Downsc.  
(Configurable for fault behavior = freely definable)  
Analog output value in the event of line break NE43 Upsc. / NE43 Downsc.  
(Configurable for fault behavior = freely definable)  
Analog output value in the event of a short circuit on the line NE43 Upsc. / NE43 Downsc.  
(Configurable for fault behavior = freely definable)  
104601_en_04  
PHOENIX CONTACT 29  
MACX MCR-EX-T-UI-UP...  
11.9 Key for error handling  
Setting for the fault behavior (NE43 increasing, NE43 decreasing, freely definable)  
Err.handl.  
11.10 Key for switch  
Access to the menu items for setting the switching output  
Switch  
Access to the menu items for setting the switching output  
Setting for the switch-on delay for the switching output (0 ... 10 s)  
Setting for the off delay for the switching output (0 ... 10 s)  
Manually acknowledge switching output (latching) (Yes/No)  
Switch 1  
On-Delay  
Off-Delay  
Acknowled.  
Linebreak  
Shorted  
Behavior for switching output in the event of an error - line break (on, off, no response)  
Behavior for switching output in the event of an error - short circuit (on, off, no response).  
12 IFS-OP-UNIT operator interface  
error codes  
The following error codes are shown directly in the display  
of the IFS-OP-UNIT operator interface when they occur.  
Error code  
Description  
Error 0  
Copy error  
Module type in the IFS-OP-UNIT is differ-  
ent from the connected module.  
Error 1,2,3  
Checksum error  
Please contact Phoenix Contact.  
104601_en_04  
PHOENIX CONTACT 30  
MACX MCR-EX-T-UI-UP...  
13.2 Configuring the user characteristic curve  
13 Configuration with the service PC  
Freely configurable user characteristic curve for  
individual adaptation of resistance temperature  
detectors (RTD) and thermocouples (TC).  
When making changes to the configuration data, use the  
IFS-CONF software  
(free download: www.phoenixcontact.net/catalog).  
The user characteristic curve is created with the PC-based  
IFS-CONF software and stored in the temperature trans-  
ducer.  
Information on configuration, parameterization  
and service options (e.g., online monitoring) and  
their execution can be found in the online help of  
the software and in the associated user manuals  
of the DTMs (Device Type Manager).  
The user characteristic curve is either selected  
with the IFS-CONF or with the IFS-OP-UNIT soft-  
ware.  
Connect the device and PC with the help of the IFS-  
USB-PROG-ADAPTER programming adapter (Order  
No. 2811271).  
14 Comparison of safety data  
3
.
1
2
.
1
1
.
1
WARNING: Explosion hazard  
3
3
.
2
2
8
2
5
2
B
.
l
2
o
m
Ex  
b
1
.
e
2
rg  
M
A
C
,
T
G
empera  
e
rtmure  
y
Supp  
X
Compare the safety data before connecting a de-  
vice located in the intrinsically safe area to the  
MACX MCR-EX-T-UI-UP....  
Ord  
a
M
n
CR  
3
2
l
.
.
... y  
3
4V  
V
N
EX  
o
2
.
.:  
(
o
l
tage  
3
286565  
T
U
20%  
2
3
T
ransducer  
0
1
V
.
...+  
3
U
P
A
I
:
D
C
UP  
m
=
10%  
C
/
4
253  
,
V
50  
N
=
H
1,5  
z/  
I
60  
nput  
W
/Ex  
H
z
)
R
T
T
D
emperaturmessumformer  
,
T
A
0
C
na  
,
m
l
V
og  
,
P
A
V
o
2
Out  
/
t
i
0
,
U
1
m
R
m
=
25  
U
3
1
N
C
=
0
m
V
.
1
30  
3
3
.
.
D
0,5  
V
1
2
3
.
1
2
2
i
(
g
A
Z
2
2
i
one  
1
.
.
ta  
1
.
2
3
3
1
l
2)  
1
Out  
1
4
2
(30  
.
1
T
Safety data for the  
V
A
2
U
o
u
amb  
.
2
Ma 20°  
)
C
t
2
.
3
Io  
/
...+  
O
U
T
u
t
1
G
N
D
x.  
V
65°C  
A
4
3
U
.1  
(30  
V
D
...+  
C
O
O
O
/
3
a
V
=
.2  
l
ues  
D
°
6,0  
I
3
)
9°  
F
.
3
1
=
=
4
7,  
P
C
4
m
Field devices:  
Temperature transducers:  
Ui, Ii, Pi, Li, Ci  
Uo, o, Po, Lo, Co  
A
11  
see  
μc  
m
m
W
anua  
WA  
S
-POR  
R
l
NIN  
DO  
AN  
T
G
S
N
O
T
5
D
.1  
5
IN  
E
P
S
.
2
www. TALLE  
A
I
R
D
ATE  
W
Z
5
.
3
PWR  
phoenIN  
HEN ENE  
4
.
1
O
4
NE  
conta  
.
2
UP  
ix  
AT  
D
2
ct RG  
4
I
.
3
IZE  
D
U
.
com  
RR  
E
-
The values for Uo, Io, Po, Lo and Co can be found under  
“Safety data according to ATEX for intrinsically safe circuits”  
on page 8.  
-
IN  
DO  
MCR  
C
A
+
M
3
.
.
4
5
2
2
3
.
.
4
5
Requirements for intrinsic safety (simple circuits):  
Ui Uo  
Ii Io  
Figure 9  
IFS-USB-PROG-ADAPTER  
Changes to the configuration and parameterization data can  
be made during operation with a connected Ex measuring  
circuit as well as in a disconnected state.  
Pi Po  
Li + Lc Lo  
Ci + Cc Co  
(Lc and Cc depend on the cables/lines used).  
13.1 System requirements  
IBM PC or compatible computer with 400 MHz or higher  
with at least 256 Mbyte RAM  
At least 15 Mbyte available hard disk space  
Free USB interface, at least USB 1.1.  
Screen resolution of 1024 x 768 pixels  
Windows 2000 SP4, Windows XP SP2  
The drivers for the IFS-USB-PROG-ADAPTER  
USB programming adapter are installed automat-  
ically.  
104601_en_04  
PHOENIX CONTACT 31  
MACX MCR-EX-T-UI-UP...  
Connection example 3:  
15 Application examples  
15.1 Current output  
Input:  
Thermocouple with external or without in-  
ternal cold junction compensation or volt-  
age input  
Connection example 1:  
Output:  
Current output (4 ... 20 mA) on passive safe  
controller  
Input:  
4-wire RTD  
Output:  
Current output (4 ... 20 mA) on passive safe  
controller  
OUT  
IN  
Sensor / Field  
PLC / DCS  
4.3  
GND 3.3  
OUT 3.2  
OUT  
IN  
I
4.2  
4.1  
Sensor / Field  
PLC / DCS  
UOUT 3.1  
4.3  
GND 3.3  
OUT 3.2  
2.3  
2.2  
2.1  
ϑ
I
4.2  
4.1  
UOUT 3.1  
2.3  
2.2  
2.1  
5.3  
5.2  
5.1  
NC 1.3  
TC  
-
1.2  
Power  
24V ...230V AC/DC  
=
mV  
+
1.1  
5.3  
5.2  
5.1  
NC 1.3  
1.2  
Zone 0,1,2  
Power  
24V ...230V AC/DC  
1.1  
Zone 20,21,22  
Zone 0,1,2  
15.2 Voltage output  
Connection example:  
Zone 20,21,22  
Connection example 2:  
Input:  
Potentiometer  
Input:  
Thermocouple with internal cold junction  
compensation  
Output:  
Voltage output (-10 ... 10 V) on passive  
controller  
Use the MACX MCR-EX-CJC cold junction  
compensation connector provided (Order No.  
2925002).  
OUT  
IN  
Sensor / Field  
PLC / DCS  
Poti  
4.3  
GND 3.3  
OUT 3.2  
Output:  
Current output (4 ... 20 mA) on passive safe  
controller  
I
4.2  
4.1  
U OUT 3.1  
2.3  
2.2  
2.1  
OUT  
IN  
Sensor / Field  
PLC / DCS  
5.3  
5.2  
5.1  
NC 1.3  
1.2  
4.3  
GND 3.3  
TC  
-
Power  
24V ...230V AC/DC  
I
OUT 3.2  
OUT 3.1  
4.2  
4.1  
1.1  
+
U
2.3  
2.2  
2.1  
Zone 0,1,2  
Zone 20,21,22  
5.3  
5.2  
5.1  
NC 1.3  
1.2  
Power  
24V ...230V AC/DC  
1.1  
Zone 0,1,2  
Zone 20,21,22  
104601_en_04  
PHOENIX CONTACT 32  
MACX MCR-EX-T-UI-UP...  
15.3 Switching output  
Connection example:  
Input:  
3-wire RTD  
Output:  
Voltage output (-10 ... 10 V) on passive  
controller  
Switching  
output:  
Dependent on selected switching behavior  
OUT  
IN  
Sensor / Field  
PLC / DCS  
4.3  
GND 3.3  
I
OUT 3.2  
OUT 3.1  
4.2  
4.1  
ϑ
2.3  
2.2  
2.1  
DI  
24 V  
5.3  
5.2  
5.1  
NC 1.3  
1.2  
Power  
24V ...230V AC/DC  
1.1  
Zone 0,1,2  
Zone 20,21,22  
104601_en_04  
PHOENIX CONTACT 33  
Appendix - Safety-related applications (SIL 2)  
Appendix  
A1 Safety-related applications (SIL 2)  
Valid hardware and firmware versions  
NOTE: Only those devices with SIL designa-  
tion and device firmware with revision 0.92 or  
higher are certified for SIL 2.  
NOTE: The evaluation unit following the measur-  
ing transducer (e.g., safety-related PLC) must  
recognize these states and correspondingly con-  
trol the actuator as the final link in the safety chain.  
SIL regulations apply to the following modules:  
With the REL versions, an additional signal is generated,  
which is compared with up to two specified switching thresh-  
olds. When the first threshold is reached, the safety relay is  
switched on without confirmation contact and when the sec-  
ond threshold is reached, it is switched off. Depending on  
the application, the safety for the switching output is imple-  
mented by either the series or parallel connection of relays  
2 and 3, a fuse connected in series, and by monitoring the  
calculated switching value. In the event of deviations of  
more than 5%, the device switches to the safe state. The  
safe state in this case is an uncontrolled relay.  
The hardware is also continuously monitored. If an internal  
failure is detected, the measuring transducer also switches  
to the safe state (current output < 3.6 mA or > 21 mA or un-  
controlled relay).  
The transition to the safe state always takes place within the  
internal failure detection time of 50 s.  
The measuring transducer is released (restarted) by switch-  
ing off the supply voltage and switching it back on again, by  
resetting the transducer via the serial interface, or by activat-  
ing the “Restart” option during configuration. The integrated  
startup tests are then performed. If the error is still present,  
it will be detected during these tests. If it is still present, the  
measuring transducer switches back to the safe state.  
Designation  
Standard configuration  
MACX MCR-T-UI-UP  
Order No.  
28 11 394  
28 11 860  
28 11 378  
28 11 828  
28 65 654  
29 24 689  
28 65 751  
29 24 799  
MACX MCR-T-UI-UP-SP  
MACX MCR-T-UIREL-UP  
MACX MCR-T-UIREL-UP-SP  
MACX MCR-EX-T-UI-UP  
MACX MCR-EX-T-UI-UP-SP  
MACX MCR-EX-T-UIREL-UP  
MACX MCR-EX-T-UIREL-UP-SP  
Order configuration  
MACX MCR-T-UI-UP-C  
28 11 873  
28 11 970  
28 11 514  
28 11 831  
28 11 763  
29 24 692  
28 65 722  
29 24 809  
MACX MCR-T-UI-UP-SP-C  
MACX MCR-T-UIREL-UP-C  
MACX MCR-T-UIREL-UP-SP-C  
MACX MCR-EX-T-UI-UP-C  
MACX MCR-EX-T-UI-UP-SP-C  
MACX MCR-EX-T-UIREL-UP-C  
MACX MCR-EX-T-UIREL-UP-SP-C  
The safety-related temperature transducers listed above  
from the MACX MCR(-EX)-T-... series have been evaluated  
by exida Certification S.A. via a Full Assessment in accor-  
dance with IEC 61508 Ed.1.0 to SIL 2.  
Certificate number: Phoenix Contact 100134C P0019  
C001.  
In addition to the safety functions, there are also monitoring  
functions for the input and the current output.  
Evaluation  
Failures which are detected in the measuring transducer  
and to which the transducer responds by switching to the  
safe state are safe failures (λs).  
A1.1 Safety function and safety requirements  
The safety-related measuring transducers are used for the  
acquisition of a sensor signal (RTD, TC sensors, resistance-  
type sensors, mV sources), that is converted into a scaled  
signal and from which a standardized “life zero” current sig-  
nal is generated. The entire conversion is continuously mon-  
itored to a maximum transmission error of 5%. In the event  
of greater deviations, the device switches to the safe state.  
The safe state is an output signal of either < 3.6 mA or > 21  
mA.  
Failures where the measuring transducer does not follow a  
change of input signal or generates an output signal that de-  
viates from the intended value by more than ±5%, are eval-  
uated as dangerous failures (λd).  
Both safe (λs) and dangerous (λd) failures can be detected  
by diagnostic measures. Detected dangerous failures (λdd)  
are handled in the same way as safe failures.  
The monitoring functions refer to events whose cause is  
detected and reported outside of the device.  
en Version 04  
PHOENIX CONTACT A-1  
Appendix - Safety-related applications (SIL 2)  
Summary:  
A1.2.1 Failure rates: MACX MCR(-EX)-T-UIREL-UP  
(-SP)(-C)  
Safety/monitor- Output sig- Safe  
ing function  
Reason  
nal range state  
Input:  
RTD 3-wire connection method  
Safety function  
4 ... 20 mA < 3.6 mA; Deviation  
Output:  
Switching output 2 and 3 (redundant)  
or  
> 5%  
Type B device (according to EN 61508-2)  
Safety Integrity Level (SIL) 2  
HFT = 0  
> 21 mA  
Relay is  
not con-  
trolled  
1oo1d architecture  
Input  
monitoring  
4 ... 20 mA 2 - 3.6  
Line fault input  
λSD  
0
λSU  
λDD  
λDU  
SFF  
94%  
DCD  
mA; >  
2.34 *  
5.43*  
0.43 *  
21 mA  
10-7  
10-7  
10-7  
92 %  
Output monitoring 4 ... 20 mA = 0 mA  
Line fault out-  
put  
0 FIT  
234 FIT 543 FIT 43 FIT  
The total failure rate is: 1.34 * 10-6  
Together with the actual signal transmission, continuous  
checks and diagnostic functions are performed in the mea-  
suring transducers in order to detect faulty behavior.  
The MTBF (Mean Time Between Failures) is therefore  
85 years.  
The probability of a dangerous failure per hour for “continu-  
ous demand” mode and the average probability of failure of  
the specified function for “low demand” mode are deter-  
mined from the error rate:  
The internal failure monitoring time (diagnostics test in-  
terval) is the time taken to carry out and repeat these tests in  
full. Random hardware faults are detected during this time.  
PFDavg values  
The internal failure monitoring time is 50 seconds.  
T[PROOF] =  
PFDavg  
1 year  
2 years  
5 years  
A1.2 Safety integrity requirements  
=
2.88 * 10-4  
4.67 * 10-4  
1.01 * 10-3  
PFH* = 4.3 * 10-8/h  
The calculation is performed assuming a checking interval  
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a  
test coverage (CPT) of 95% and a life time (LT) of 10 years.  
On the basis of the value determined for the average proba-  
bility of failure PFDavg, the checking interval can be in-  
creased to up to 5 years.  
As a result of the multiple connection options,  
only two device types are considered in the con-  
figurations for “RTD 3-wire” or “mV” in the follow-  
ing. They represent all configurations with a  
variable resistance at the input terminals or volt-  
age or thermocouple inputs and always indicate  
the most conservative case. The two device types  
are:  
1. MACX MCR(-EX)-T-UI-UP(-SP)(-C)  
The values are valid under the following conditions:  
2. MACX MCR(-EX)-T-UIREL-UP(-SP)(-C)  
The failure rates of the components used remain con-  
stant throughout the period of use.  
FIT (Failure In Time)  
1 FIT is 1 failure in 109 hours  
The propagation of failures by the device in the system  
is not taken into consideration.  
The repair time (replacement) is 24 hours.  
The failure rates of the external power supply unit are  
not taken into consideration.  
The average temperature at which the device is to be  
used is 40°C. In this case, normal industrial conditions  
are assumed.  
The specified failure rates are based on an average am-  
bient temperature of 40°C. For an average ambient  
temperature of 60°C, the failure rates must be multiplied  
by factor 2.5. Factor 2.5 is based on guide values.  
en Version 04  
PHOENIX CONTACT A-2  
Appendix - Safety-related applications (SIL 2)  
1.2.2 Failure rates: MACX MCR(-EX)-T-UIREL-UP  
(-SP)(-C)  
The average temperature at which the device is to be  
used is 40°C. In this case, normal industrial conditions  
are assumed.  
The specified failure rates are based on an average am-  
bient temperature of 40°C. For an average ambient  
temperature of 60°C, the failure rates must be multiplied  
by factor 2.5. Factor 2.5 is based on guide values.  
Input:  
Voltage input mV  
Output:  
Switching output 2 and 3 (redundant)  
Type B device (according to EN 61508-2)  
Safety Integrity Level (SIL) 2  
HFT = 0  
1.2.3 Failure rates: MACX MCR(-EX)-T-UI-UP(-SP)  
(-C)  
1oo1d architecture  
λSD  
0
λSU  
λDD  
λDU  
SFF  
93%  
DCD  
90%  
Input:  
Output:  
RTD 3-wire connection method  
4 ... 20 mA (current output)  
2.38 *  
5.22*  
0.56 *  
10-7  
10-7  
10-7  
Type B device (according to EN 61508-2)  
Safety Integrity Level (SIL) 2  
HFT = 0  
0 FIT  
238 FIT 522 FIT 56 FIT  
The total failure rate is: 1.34 * 10-6  
The MTBF (Mean Time Between Failures) is therefore  
85 years.  
The probability of a dangerous failure per hour for “continu-  
ous demand” mode and the average probability of failure of  
the specified function for “low demand” mode are deter-  
mined from the error rate:  
1oo1d architecture  
λSD  
0
λSU  
0
λDD  
λDU  
SFF  
94%  
DCD  
94%  
8.05*  
0.43 *  
10-7  
10-7  
0 FIT  
0 FIT  
805 FIT 43 FIT  
The total failure rate is: 1.18 * 10-6  
PFDavg values  
The MTBF (Mean Time Between Failures) is therefore  
97 years.  
The probability of a dangerous failure per hour for “continu-  
ous demand” mode and the average probability of failure of  
the specified function for “low demand” mode are deter-  
mined from the error rate:  
T[PROOF] =  
PFDavg  
PFH* = 5.6 * 10-8/h  
The calculation is performed assuming a checking interval  
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a  
test coverage (CPT) of 95% and a life time (LT) of 10 years.  
On the basis of the value determined for the average proba-  
bility of failure PFDavg, the checking interval can be in-  
creased to up to 5 yearsif the percentage of the device for  
the entire loop is assumed at 10%.  
1 year  
2 years  
5 years  
=
3.67 * 10-4  
5.99 * 10-4  
1.30 * 10-3  
PFDavg values  
T[PROOF] =  
PFDavg  
1 year  
2 years  
5 years  
=
2.95 * 10-4  
4.76 * 10-4  
1.02 * 10-3  
PFH* = 4.3 * 10-8/h  
The calculation is performed assuming a checking interval  
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a  
test coverage (CPT) of 95% and a life time (LT) of 10 years.  
On the basis of the value determined for the average proba-  
bility of failure PFDavg, the checking interval can be in-  
creased to up to 5 years.  
The values are valid under the following conditions:  
The failure rates of the components used remain con-  
stant throughout the period of use.  
The propagation of failures by the device in the system  
is not taken into consideration.  
The repair time (replacement) is eight hours.  
The failure rates of the external power supply unit are  
not taken into consideration.  
The values are valid under the following conditions:  
The failure rates of the components used remain con-  
stant throughout the period of use.  
The propagation of failures by the device in the system  
is not taken into consideration.  
en Version 04  
PHOENIX CONTACT A-3  
Appendix - Safety-related applications (SIL 2)  
The repair time (replacement) is eight hours.  
The failure rates of the external power supply unit are  
not taken into consideration.  
The average temperature at which the device is to be  
used is 40°C. In this case, normal industrial conditions  
are assumed.  
The specified failure rates are based on an average am-  
bient temperature of 40°C. For an average ambient  
temperature of 60°C, the failure rates must be multiplied  
by factor 2.5. Factor 2.5 is based on guide values.  
The values are valid under the following conditions:  
The failure rates of the components used remain con-  
stant throughout the period of use.  
The propagation of failures by the device in the system  
is not taken into consideration.  
The repair time (replacement) is eight hours.  
The failure rates of the external power supply unit are  
not taken into consideration.  
The average temperature at which the device is to be  
used is 40°C. In this case, normal industrial conditions  
are assumed.  
The specified failure rates are based on an average am-  
bient temperature of 40°C. For an average ambient  
temperature of 60°C, the failure rates must be multiplied  
by factor 2.5. Factor 2.5 is based on guide values.  
1.2.4 Failure rates: MACX MCR(-EX)-T-UI-UP(-SP)  
(-C)  
Input:  
Output:  
Voltage input mV  
4 ... 20 mA (current output)  
Type B device (according to EN 61508-2)  
Safety Integrity Level (SIL) 2  
HFT = 0  
A1.3 Configuring an SIL device  
The measuring transducer can be ordered with a standard  
configuration (see 1.) or configured for safety-related appli-  
cations (see 2.), or can be configured by users themselves  
for safety-related applications (see 3.).  
1. The measuring transducers are delivered with a stan-  
dard configuration for safety-related applications with a  
4 - 20 mA output (see order key).  
2. Customer-specific pre-configured devices (-C) can be  
delivered for both safety-related applications and “nor-  
mal” usage. Configuration data is shown on a label.  
3. The measuring transducers can also be configured by  
users for both safety-related applications and “normal”  
usage.  
1oo1d architecture  
λSD  
0
λSU  
0
λDD  
λDU  
SFF  
93%  
DCD  
93%  
7.89*  
0.56 *  
10-7  
10-7  
0 FIT  
0 FIT  
789 FIT 56 FIT  
The total failure rate is: 1.19 * 10-6  
The MTBF (Mean Time Between Failures) is therefore  
96 years.  
The probability of a dangerous failure per hour for “continu-  
ous demand” mode and the average probability of failure of  
the specified function for “low demand” mode are deter-  
mined from the error rate:  
The configuration can be read out and changed at any time  
for all devices.  
PFDavg values  
For safety-related applications, the password set  
in the factory must always be changed.  
If the password is lost, it is not possible to change  
the configuration.  
T[PROOF] =  
PFDavg  
PFH* = 5.6 * 10-8/h  
1 year  
2 years  
5 years  
=
3.75 * 10-4  
6.08 * 10-4  
1.31 * 10-3  
In this case, please contact Phoenix Contact.  
The calculation is performed assuming a checking interval  
(TPROOF) of 1 year and a repair time (MTTR) of 24 hours, a  
test coverage (CPT) of 95% and a life time (LT) of 10 years.  
On the basis of the value determined for the average proba-  
bility of failure PFDavg, the checking interval can be in-  
creased to up to 5 years.  
en Version 04  
PHOENIX CONTACT A-4  
Appendix - Safety-related applications (SIL 2)  
Configuring safety-related applications  
A1.4 Installation and startup  
During installation, always observe the package slips  
Connect the device and PC with the help of the IFS-  
USB-PROG-ADAPTER programming adapter (Order  
No. 2811271).  
Designation  
MNR No.  
9055145  
9055147  
9055146  
9055148  
PACKB.MACX MCR-T-UI-UP...  
PACKB.MACX MCR-EX-T-UI-UP...  
PACKB.MACX MCR-T-UIREL-UP...  
PACKB.MACX MCR-EX-T-UIREL-UP...  
Load the IFS-CONF configuration software (free down-  
load at:  
www.phoenixcontact.net/catalog).  
Further information on the FDT frame application (IFS-  
CONF) and the device drivers (DTM) can be found in  
the IFS-CONF user manual.  
The package slip is supplied with the device. It can also be  
downloaded at: www.phoenixcontact.net/catalog.  
Lockable housing with IP54 protection is recommended for  
the installation of the measuring transducer.  
Read out the active configuration.  
Enter the password in the IFS-CONF in the “PIN” hard-  
ware configuration (set to 1111 in the factory).  
Check that the configuration of the measuring transduc-  
er is correct for the intended application.  
Connect the measuring transducer according to the in-  
stallation instructions.  
Make sure that the connected sensor corresponds to  
the configuration.  
Check the functionality of the measuring transducer  
with connected sensor for correct function.  
A calibrated sensor simulator (RTD/TC) and a calibrat-  
ed digital multimeter are necessary for checking the  
measuring transducer.  
Activate/deactivate SIL.  
In the case of “SIL ON”, it is also possible to deactivate the  
Restart after failsafe” item here.  
This means that in the event of a failure, the measuring  
transducer enters the failsafe state according to the safety  
functions, but is not restarted.  
Write the modified configuration data to the measuring  
transducer.  
Check that the new configuration data in the control  
window is correct and confirm with “OK” or “Cancel” if  
not correct.  
Start up the loop and check that it operates correctly.  
A1.5 Notes on operation  
NOTE: Installation, operation, and maintenance  
may only be carried out by qualified specialist per-  
sonnel.  
Only the green LED (PWR) is on during normal operation.  
If a malfunction occurs during operation and the red LED  
(ERR) flashes, there is a line fault. The output current of the  
measuring transducer is between 2 … 3.6 mA or is higher  
than 21.0 mA (in the case of faults in the sensor circuit) or is  
0 mA (in the case of a line break in the output circuit).  
Check all signal lines. The device will automatically switch  
back to normal operation after the fault has been eliminated.  
If a fault occurs during operation and the red LED (ERR) is  
permanently on, the device has switched to the “safe state”  
(output current is less than 2 mA).  
WARNING: If Functional Safety is activated by a  
reconfiguration or changes are made to the active  
Functional Safety configuration, the rules under  
“Installation and startup” must be observed.  
WARNING: Limitations on safety-related ap-  
plications  
Only 4 ... 20 mA, limited programming of output  
current in the event of line faults  
(2 mA IOut 3.6 mA or IOut 21 mA)  
Restart the device in order to return it to normal operation.  
If no PC/laptop has been connected, you can also inter-  
rupt the power supply.  
WARNING: Once new configuration data has  
been written, the device performs a warm start  
that changes the properties of the device. The fol-  
lowing control device must be adapted to these  
modifications.  
Or you can carry out a warm start with the help of the  
configuration software (Service > Reset).  
The measuring transducer should then return to normal op-  
eration. If it does not, the measuring transducer must be re-  
placed.  
WARNING: The device must be write-protected  
to prevent improper use. Write protection is cre-  
ated by assigning a password.  
en Version 04  
PHOENIX CONTACT A-5  
Appendix - Safety-related applications (SIL 2)  
A1.6 Recurring checks (SIL 2)  
Phoenix Contact GmbH & Co KG  
Abteilung Service und Reparatur  
Flachsmarktstr. 8  
The function of the entire safety loop must be checked reg-  
ularly according to EN 61508 and EN 61511. The intervals  
for checking are specified by the intervals of each individual  
device within the safety loop.  
D-32825 Blomberg  
GERMANY  
It is the operator's responsibility to select the type of checks  
and the checking intervals in the specified time period.  
The measuring transducers must be checked at least every  
7 years (maximum proof test interval).  
Checking must be carried out in such a way that the correct  
function of the safety equipment in conjunction with all com-  
ponents can be verified.  
A1.8 Standards (SIL 2)  
The measuring transducers are developed and tested ac-  
cording to the following standards:  
EN 61508:  
2001  
Functional safety of electrical/electronic/  
programmable electronic safety-related  
systems  
EN 61326-1:  
2006  
Electrical equipment for measurement,  
control and laboratory use – EMC re-  
quirements  
Possible procedure for recurring checks for discover-  
ing dangerous and undetected device failures.  
IEC 61326-3-2: Electrical equipment for measurement,  
A calibrated sensor simulator (RTD/TC) and a calibrated  
digital multimeter are necessary for checking the measuring  
transducer.  
2006  
control and laboratory use – EMC re-  
quirements – Part 3-2: Immunity require-  
ments for safety-related systems and for  
equipment intended to perform safety-  
related functions (functional safety) – In-  
dustrial applications with specified elec-  
tromagnetic environment  
Connect the sensor simulator to the input of the mea-  
suring transducer using the appropriate connection  
method.  
Connect the digital multimeter to the output in current  
measuring mode (20 mA range).  
The measuring range limits and intermediate values are  
specified with the sensor simulator.  
The corresponding output values of the measuring trans-  
ducer must be checked on the digital multimeter.  
Line faults (break and short circuit) are to be simulated on  
the input terminals; the configured residual currents are to  
be determined on the output.  
If the function test result is negative, the measuring trans-  
ducer must be taken out of operation and the process put  
into a safe state by other measures.  
A1.7 Repair  
The devices have a long service life, are protected against  
malfunctions, and are maintenance-free. However, if a de-  
vice should fail, send it back to Phoenix Contact immedi-  
ately. The type of malfunction and possible cause must also  
be stated.  
Please use the original packaging or other suitable safe  
packaging when sending devices back for repairs or recali-  
bration.  
en Version 04  
PHOENIX CONTACT A-6  
Appendix - Safety-related applications (SIL 2)  
A1.9 Abbreviations  
Abbreviation  
Meaning  
DCD  
Diagnostic Cov- Diagnostic coverage:  
erage of Dan-  
DCD = λDD/(λDU + λDD)  
gerous Failures  
HFT  
Hardware Fault Hardware Fault Tolerance:  
Tolerance  
Ability of a function unit to con-  
tinue with the execution of a de-  
manded function despite exist-  
ing failures or deviations  
λD  
Rate of Danger- Proportion of dangerous fail-  
ous Failures ures per hour  
λDD  
Rate of Danger- Proportion of detected danger-  
ous Detected  
ous failures per hour  
Failures  
λDU  
Rate of Danger- Proportion of undetected dan-  
ousUndetected gerous failures per hour  
Failures  
λS  
Rate of Safe  
Failures  
Proportion of safe failures per  
hour  
MTBF Mean Time  
Between  
Mean time between consecu-  
tive failures  
Failures  
PFDavg Average  
Probability of  
Failure on  
Average probability of failure on  
demand of a safety function  
Demand  
PFH  
SFF  
Probability of a Probability of failure per hour  
Dangerous  
for the safety function  
Failure per Hour  
Safe Failure  
Fraction  
Proportion of safe failures: Pro-  
portion of failures without the  
potential to set the safety-re-  
lated system to a dangerous or  
impermissible function state  
SIL  
Safety Integrity International standard IEC  
Level  
61508 defines four discrete  
safety integrity levels (SIL 1 to  
4). Each level corresponds to a  
probability range for the failure  
of a safety function. The higher  
the safety integrity level of  
safety-related systems, the  
lower the probability that the  
demanded safety functions will  
not be performed.  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany  
www.phoenixcontact.com  
en Version 04  
A-7  

相关型号:

2924692

MACX MCR-EX-T-UI-UP
PHOENIX

29249

ROTA-CRIMP Hand Crimping Tools
TE

29249-3

ROTA-CRIMP Hand Crimping Tools
TE

29249-5

ROTA-CRIMP Hand Crimping Tools
TE

2925

Dense Wave Division Multiplexing (DWDM)
EMCORE

2925002

Barrier Strip Terminal Block
PHOENIX

29250B102J0-2

Mica Capacitor, Mica, 5000V, 0.001uF
CDE

29250B103JO0

High-Voltage Mica Capacitors Cylindrical Case, High-Current and High-Voltage Circuits
CDE

29250B113GO0

Mica Capacitor, Mica, 5000V, 0.011uF
CDE

29250B113JO0

High-Voltage Mica Capacitors Cylindrical Case, High-Current and High-Voltage Circuits
CDE

29250B470J0-1

Mica Capacitor, Mica, 5000V, 0.000047uF
CDE

29250B562JO0

High-Voltage Mica Capacitors Cylindrical Case, High-Current and High-Voltage Circuits
CDE