2907753 [PHOENIX]
DC-DC Regulated Power Supply Module, 1 Output, 480W, Hybrid, PACKAGE-4;![2907753](http://pdffile.icpdf.com/pdf2/p00281/img/icpdf/2907753_1675802_icpdf.jpg)
型号: | 2907753 |
厂家: | ![]() |
描述: | DC-DC Regulated Power Supply Module, 1 Output, 480W, Hybrid, PACKAGE-4 |
文件: | 总10页 (文件大小:143K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Active QUINT single redundancy module for DIN rail mounting, protective coating, input: 12 - 24 V DC, output:
12 - 24 V DC/1 x 40 A, incl. mounted UTA 107/30 universal DIN rail adapter
Product Description
Active redundancy module for superior system availability and maximum operational reliability. QUINT S-ORING enables the separate structuring of
a redundant system. In combination with the new QUINT POWER power supply, the redundant system is monitored continuously.
Your advantages
Consistent redundancy up to the load
Input voltage and decoupling section monitored on a permanent basis
Save energy by decoupling with MOSFET
Protection against surge voltages in excess of 30 V DC at the output
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4055626231914
582.700 g
85049091
China
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
Technical data
Dimensions
Width
32 mm
Height
130 mm
125 mm
122 mm
130 mm
Depth
Width with alternative assembly
Height with alternative assembly
09/17/2019 Page 1 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Technical data
Dimensions
Depth with alternative assembly
35 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Climatic class
-40 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
-40 °C ... 85 °C
≤ 100 % (at 25 °C, non-condensing)
3K3 (in acc. with EN 60721)
2
Degree of pollution
Installation height
≤ 5000 m (> 2000 m, observe derating)
Input data
Nominal input voltage range
Input voltage range
12 V DC ... 24 V DC
8 V DC ... 26 V DC
40 A
Current consumption
Nominal input current
40 A (-40 °C ... 60 °C)
Output data
Output voltage range
8 V DC ... 26 V DC
40 A
Nominal output current (IN)
Static Boost (IStat.Boost
)
45 A
Dynamic Boost (IDyn.Boost
)
60 A (5 s)
Selective Fuse Breaking (ISFB
)
215 A (15 ms)
60 °C ... 70 °C (2.5%/K)
No
Derating
Connection in series
Protection against overvoltage at the output (OVP)
Power loss nominal load max.
≤ 28.8 V DC
6.5 W (IOUT = 40 A)
6 W (IOUT = 40 A)
General
Net weight
Efficiency
0.4 kg
typ. 99 % (12 V DC)
typ. 99.2 % (24 V DC)
III
Protection class
Degree of protection
MTBF (IEC 61709, SN 29500)
IP20
> 13486000 h (25 °C)
> 7314000 h (40 °C)
> 3379000 h (60 °C)
horizontal DIN rail NS 35, EN 60715
Mounting position
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active
components, 50 mm vertically
Assembly instructions
09/17/2019 Page 2 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Technical data
General
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm
vertically bottom
Connection data, input
Connection method
Screw connection
0.5 mm²
16 mm²
0.5 mm²
16 mm²
20
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
6
10 mm
M4
Screw thread
Connection data, output
Connection method
Screw connection
0.5 mm²
16 mm²
0.5 mm²
16 mm²
20
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
6
10 mm
M4
Screw thread
Connection data for signaling
Connection method
Push-in connection
0.2 mm²
1.5 mm²
0.2 mm²
1.5 mm²
24
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Stripping length
16
8 mm
Standards and Regulations
Electromagnetic compatibility
Noise emission
Conformance with EMC Directive 2014/30/EU
Additional basic standard EN 61000-6-5 (immunity in power station)
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2
(industrial), and EN 61000-6-5 (power station equipment zone )
Noise immunity
Standards/regulations
Contact discharge
EN 61000-4-2
4 kV (Test Level 2)
09/17/2019 Page 3 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Technical data
Standards and Regulations
Standards/regulations
Frequency range
EN 61000-4-3
80 MHz ... 1 GHz
Test field strength
Frequency range
10 V/m (Test Level 3)
1.4 GHz ... 2 GHz
Test field strength
Standards/regulations
Comments
3 V/m (Test Level 2)
EN 61000-4-4
Criterion B
Standards/regulations
Frequency range
EN 61000-4-6
0.15 MHz ... 80 MHz
10 V (Test Level 3)
Voltage
Conducted noise emission
Standards/regulations
Low Voltage Directive
Standard - Electrical safety
EN 55016 EN 61000-6-4 (Class A)
EN 61000-4-8
Conformance with Low Voltage Directive 2014/35/EC
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
Standard - Safe isolation
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Shipbuilding approval
UL approvals
DNV GL
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D
(Hazardous Location)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Vibration (operation)
ATEX
IECEx
II 3 G Ex nA nC IIC Gc
SIQ 17 ATEX 020 U
Ex nA nC IIC Gc
IECEx SIQ 17.0006U
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
09/17/2019 Page 4 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Dimensional drawing
09/17/2019 Page 5 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Block diagram
Diagram
09/17/2019 Page 6 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Diagram
09/17/2019 Page 7 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Dimensional drawing
Classifications
eCl@ss
eCl@ss 5.0
eCl@ss 5.1
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
eCl@ss 9.0
27371000
27371000
27371000
27371010
27371010
27371010
ETIM
ETIM 5.0
ETIM 6.0
EC000599
EC000599
09/17/2019 Page 8 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Classifications
ETIM
ETIM 7.0
EC000599
39121004
UNSPSC
UNSPSC 13.2
Approvals
Approvals
Approvals
DNV GL / UL Listed / UL Recognized / cUL Recognized / cUL Listed / EAC / cULus Listed / cULus Recognized
Ex Approvals
IECEx / ATEX / UL Listed / cUL Listed / FM Canada approved / FM approved / cULus Listed
Approval details
DNV GL
UL Listed
https://approvalfinder.dnvgl.com/
TAA000011F
FILE E 123528
FILE E 211944
FILE E 211944
FILE E 123528
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
UL Recognized
cUL Recognized
cUL Listed
09/17/2019 Page 9 / 10
https://www.phoenixcontact.com/in/products/2907753
Redundancy module, with protective coating - QUINT4-S-
ORING/12-24DC/1X40/+ - 2907753
Approvals
RU C-
DE.A*30.B.01082
EAC
cULus Listed
cULus Recognized
Accessories
Accessories
Assembly adapter
Assembly adapters - UWA 182/52 - 2938235
Universal wall adapter for securely mounting the device in the event of strong vibrations. The device is screwed
directly onto the mounting surface. The universal wall adapter is attached on the top/bottom.
Assembly adapters - UTA 107/30 - 2320089
Universal DIN rail adapter
Assembly adapters - QUINT-PS-ADAPTERS7/1 - 2938196
Assembly adapter for QUINT-PS... power supply on S7-300 rail
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
09/17/2019 Page 10 / 10