2902961 [PHOENIX]

MINI MCR-RTD-UI-NC;
2902961
型号: 2902961
厂家: PHOENIX CONTACT    PHOENIX CONTACT
描述:

MINI MCR-RTD-UI-NC

文件: 总14页 (文件大小:283K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MINI MCR-RTD-UI-NC  
Temperature transducers for resistance thermome-  
ters and remote resistance-type sensors  
Data sheet  
105446_en_00  
© PHOENIX CONTACT 2013-01-14  
1
Description  
Configurable 3-way isolated temperature transducer. The de- Features  
vice is suitable for the connection of resistance thermometers  
Configurable 3-way temperature transducer  
Configurable via DIP switches for Pt 100 and Pt 1000  
(IEC 751)  
Extended functionality configurable with free software  
Approval for Ex-zone 2 (nA)  
Screw or spring-cage connection can be provided  
and remote resistance-type sensors in 2, 3 and 4-wire con-  
nection technology.  
The measured values are converted into a linear current or  
voltage signal.  
The device can either be configured via DIP switches or, with  
extended functionality, via the S port using the software (FDT/  
DTM).  
The device supports fault monitoring.  
WARNING: Correct usage in potentially explosive areas  
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided  
here during installation and observe the information in the "Safety regulations and installation notes".  
Make sure you always use the latest documentation.  
It can be downloaded from the product at www.phoenixcontact.net/products.  
This data sheet is valid for all products listed on the following page:  
MINI MCR-RTD-UI-NC  
2
Table of contents  
1
Description .............................................................................................................................. 1  
Table of contents..................................................................................................................... 2  
Ordering data .......................................................................................................................... 3  
Technical data ......................................................................................................................... 4  
Safety regulations and installation notes.................................................................................. 6  
2
3
4
5
5.1  
5.2  
Installation notes ................................................................................................................. 6  
Installation in the Ex area (zone 2)............................................................................................ 6  
6
Installation ............................................................................................................................... 7  
6.1  
6.2  
6.3  
6.4  
6.5  
6.6  
Connection notes ................................................................................................................ 7  
Structure ........................................................................................................................... 7  
Block diagram..................................................................................................................... 7  
Power supply...................................................................................................................... 8  
Assembly........................................................................................................................... 8  
Connecting the wires ............................................................................................................ 9  
7
8
Fault monitoring FM............................................................................................................... 10  
Configuration......................................................................................................................... 11  
8.1  
8.2  
8.3  
Configuration via DIP switches.............................................................................................. 11  
Connectable sensors.......................................................................................................... 11  
Configuration via software (FDT/DTM) .................................................................................... 14  
9
Diagnostic indicator............................................................................................................... 14  
105446_en_00  
PHOENIX CONTACT  
2
MINI MCR-RTD-UI-NC  
3
Ordering data  
Description  
Type  
Order No.  
Pcs. / Pkt.  
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-NC  
ductor resistance thermometers and resistance-type sensors. Can be con-  
figured via DIP switches or, with extended functionality, using the software.  
Screw connection, standard configuration.  
2902849  
1
Configurable temperature transducer for the connection of 2, 3, and 4-con- MINI MCR-RTD-UI-SP-NC  
ductor resistance thermometers and resistance-type sensors. Can be con-  
figured via DIP switches or, with extended functionality, using the software.  
Spring-cage connection, standard configuration.  
2902850  
1
Accessories  
Type  
Order No.  
2811271  
Pcs. / Pkt.  
1
Programming adapter with USB interface, for programming with software. IFS-USB-PROG-ADAPTER  
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply  
the supply voltage to the T-connector. The FM power terminal block offers  
the additional function of monitoring in combination with the fault monitor-  
ing module. Screw connection.  
MINI MCR-SL-PTB-FM  
2902958  
1
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply  
the supply voltage to the T-connector. The FM power terminal block offers  
the additional function of monitoring in combination with the fault monitor-  
ing module. Spring-cage connection.  
MINI MCR-SL-PTB-FM-SP  
MINI MCR-SL-FM-RC-NC  
MINI MCR-SL-FM-RC-SP-NC  
2902959  
2902961  
2902962  
1
1
1
The fault monitoring module is used to evaluate and report group errors  
from the fault monitoring system and to monitor the supply voltages. The  
error is reported via an N/O contact. Screw connection, standard configu-  
ration.  
The fault monitoring module is used to evaluate and report group errors  
from the fault monitoring system and to monitor the supply voltages. The  
error is reported via an N/O contact. Spring-cage connection, standard  
configuration.  
DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be ME 6,2 TBUS-2 1,5/5-ST-3,81 GN  
snapped onto NS 35/... DIN rails according to EN 60715  
2869728  
2866983  
2811268  
10  
1
DIN rail power supply unit, primary-switched mode, slim design, output:  
24 V DC / 1.5 A  
MINI-SYS-PS-100-240AC/24DC/1.5  
Eight MINI analog signal converters with screw connection method can be MINI MCR-SL-V8-FLK 16-A  
connected to a control system using a system adapter and system cabling  
with a minimum of wiring and very low error risk.  
1
MINI analog multiplexer, generates one analog output from 8 analog input MINI MCR-SL-MUX-V8-FLK 16  
signals, for MINI analog module with screw connection.  
2811815  
2308111  
2810272  
1
Fold up transparent cover for MINI MCR modules with additional labeling MINI MCR DKL  
option using insert strips and flat Zack marker strip 6.2 mm  
10  
10  
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL-LABEL  
MINI MCR-DKL  
105446_en_00  
PHOENIX CONTACT  
3
MINI MCR-RTD-UI-NC  
4
Technical data  
Input  
Configurable/programmable  
Yes  
Sensor type  
Pt, Ni, Cu sensors  
Approx. 200 µA  
25 (Per cable)  
Sensor input current  
Max. permissible overall conductor resistance  
Linear resistance measuring range  
Temperature measuring range  
Measuring range span  
0 ... 4000 (Minimum measuring span: 10% of the selected measuring range)  
-200 °C ... 850 °C (Range depending on the sensor type)  
min. 50 K  
Connection method  
2, 3, 4-wire  
Output  
Voltage output signal  
0 V ... 10 V  
10 V ... 0 V  
0 V ... 5 V  
1 V ... 5 V  
Max. voltage output signal  
Current output signal  
Approx. 12.3 V  
0 mA ... 20 mA  
4 mA ... 20 mA  
20 mA ... 0 mA  
20 mA ... 4 mA  
Max. current output signal  
Configurable/programmable  
Load/output load voltage output  
Ripple  
24.6 mA  
Yes  
10 kΩ  
< 20 mV  
PP  
Load/output load current output  
500 (at 20 mA)  
Supply  
Supply voltage range  
9.6 V DC ... 30 V DC (The T connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order  
No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a  
35 mm DIN rail according to EN 60715))  
Typical current consumption  
Power consumption  
< 27 mA (at 24 V DC)  
700 mW (at I  
= 20 mA, 9.6 V DC, load 500 )  
OUT  
Diagnostic and status indicators  
Status display  
LED red  
General data  
Transmission error resistance thermometer  
0.1% * 350 K / set measuring range; 0.1% > 350 K (Pt/Ni)  
0.3% * 200 K / set measuring range; 0.3% > 200 K (Cu)  
Transmission error resistance-type sensor  
Maximum temperature coefficient  
Step response (0–99%)  
2 Ω  
0.01 %/K  
Typ. 200 ms (2-wire)  
Typ. 500 ms (3-wire)  
Typ. 500 ms (4-wire)  
Electrical isolation  
Basic insulation according to EN 61010  
Surge voltage category  
Mounting position  
II  
Any  
Degree of protection  
Pollution degree  
IP20  
2
Rated insulation voltage  
50 V AC/DC  
105446_en_00  
PHOENIX CONTACT  
4
MINI MCR-RTD-UI-NC  
General data [...]  
Test voltage, input/output/supply  
Dimensions W / H / D  
Type of housing  
1.5 kV (50 Hz, 1 min.)  
6.2 mm / 93.1 mm / 102.5 mm  
PBT green  
Connection data  
Screw connection  
0.2 mm² ... 2.5 mm²  
0.2 mm² ... 2.5 mm²  
12 mm  
Spring-cage conn.  
Conductor cross section, solid  
Conductor cross section, stranded  
Stripping length  
0.2 mm² ... 2.5 mm²  
0.2 mm² ... 2.5 mm²  
8 mm  
Ambient conditions  
Ambient temperature (operation)  
Ambient temperature (storage/transport)  
Permissible humidity (operation)  
-20 °C ... 65 °C  
-40 °C ... 85 °C  
5 % ... 95 % (no condensation)  
Conformance with EMC Directive 2004/108/EC  
Noise immunity according to EN 61000-6-2  
When being exposed to interference, there may be minimal deviations.  
Noise emission according to EN 61000-6-4  
Conformance / approvals  
Conformance  
CE-compliant  
ATEX  
II 3 G Ex nA IIC T4 Gc X  
UL 508 Recognized applied for  
UL, USA / Canada  
UL, USA / Canada  
Shipbuilding  
Class I, Div. 2, Groups A, B, C, D T5 applied for  
GL applied for  
105446_en_00  
PHOENIX CONTACT  
5
MINI MCR-RTD-UI-NC  
5
Safety regulations and installation notes  
5.1  
Installation notes  
5.2  
Installation in the Ex area (zone 2)  
The category 3 device is suitable for installation in the  
zone 2 potentially explosive area. It fulfills the require-  
ments of EN 60079-0:2009 and EN 60079-15:2010.  
Observe the specified conditions for use in potentially ex-  
plosive areas.  
The device must be installed in a housing (control or dis-  
tributor box) which meets the requirements of EN 60079-  
15 and provides at least IP54 (EN 60529) degree of pro-  
tection.  
During installation and when connecting the supply and  
signal circuits, observe the requirements of EN 60079-  
14. Devices may only be connected to circuits in zone 2 if  
they are suitable for operation in Ex zone 2 and for the  
prevailing conditions at the place of use.  
In potentially explosive areas, terminals may only be  
snapped onto or off the DIN rail connector and wires may  
only be connected or disconnected when the power is  
switched off.  
The device must be stopped and immediately removed  
from the Ex area if it is damaged, has been subjected to  
an impermissible load, has been stored incorrectly, or if it  
malfunctions.  
You can download the latest documents for these devic-  
es from www.phoenixcontact.net/products.  
Installation, operation, and maintenance may only be car-  
ried out by qualified electricians. Follow the installation in-  
structions described. When installing and operating the  
device, the applicable regulations and safety directives  
(including national safety directives), as well as general  
technical regulations, must be observed. The technical  
data is provided in this package slip and on the certifi-  
cates (conformity assessment, additional approvals  
where applicable).  
It is not permissible to open or modify the device. Do not  
repair the device yourself but replace it with an equivalent  
device. Repairs may only be carried out by the manufac-  
turer. The manufacturer is not liable for damage resulting  
from violation.  
The IP20 degree of protection (IEC 60529/EN 60529) of  
the device is intended for use in a clean and dry environ-  
ment. Do not subject the device to any load that exceeds  
the described limits.  
The device is not designed for use in atmospheres with a  
danger of dust explosions.  
105446_en_00  
PHOENIX CONTACT  
6
MINI MCR-RTD-UI-NC  
6.3  
Block diagram  
6
Installation  
6.1  
Connection notes  
Sensor / Field  
IN  
OUT  
PLC / DCS  
S-Port  
NOTE: Electrostatic discharge!  
OUT U,I  
The device contains components that can be  
damaged or destroyed by electrostatic dis-  
charge. When handling the device, observe the  
necessary safety precautions against electro-  
static discharge (ESD) according to EN 61340-  
5-1 and EN 61340-5-2.  
+
1
2
3
1
5
5
6
active  
passive  
GND 1  
6
2
ϑ
ϑ
ϑ
+24V  
+
7
3
4
4
GND 2  
8
FM  
6.2  
Structure  
GND 2  
+24V  
2
3
4
Zone 2  
5
1
Figure 2  
Block diagram  
–RTD–UI-NC  
32825 Blomberg, Germany  
V
...0  
0
1
,
A
m
–No.: 29 02 84  
MINI MCR  
O
9
Donotseperate  
rd.  
)0  
0...(4  
,
2
V
0
...1  
0
,
V
RTD Signal Conditioner  
)...5  
(1  
0
Sens
Field  
,
A
m
0
whenenergized  
6
Warning  
4°...+149°F  
)...2  
(4  
IN:  
RTD IEC 751, GOST 6651, DIN 43760  
0
:
T
1
U
9,6...30VDC  
O
20°...+65°C  
/
1
ort  
-P  
S
2
3
ϑ
ϑ
ϑ
T
amb  
2
,I  
U
e
T
U
O
3
5
activ  
+
PLC / CS  
1
D
5
N
4
-
G
4
6
-
II  
3
G
passive  
6
24V  
+
Ex nA II  
C
T4 Gc X  
7
FM  
+
2
D
N
G
GND  
2
11  
9
8
-
+24V  
1
0
8
ON  
S1  
S2  
OFF  
1
7
w.phoenixcontact.com  
Serial No.  
10  
8
Figure 1  
Structure  
1. Input: resistance thermometer and remote resistance-  
type sensor  
2. Cover  
3. Diagnostics LED  
4. S-PORT  
5. Groove for ZBF 6 zack marker strip  
6. Output: Standard signals  
7. Supply voltage  
8. Connection for DIN rail connector  
9. Universal snap-on foot for EN DIN rails  
10. DIP switch S1  
11. DIP switch S2  
105446_en_00  
PHOENIX CONTACT  
7
MINI MCR-RTD-UI-NC  
6.4  
Power supply  
6.5  
Assembly  
NOTE: Never connect the supply voltage di-  
B
A
rectly to the DIN rail connector. It is not permit-  
ted to draw power from the DIN rail connector  
or from individual modules.  
Supply via the MINI Analog Module  
Where the total current consumption of the aligned modules  
does not exceed 400 mA, the power can be supplied directly  
at the connection terminal blocks of the module.  
C
E
A
D
B
Figure 4  
Mounting and removing  
w.interface.phoenixcontact.com  
XXXXXXXX  
o.  
N
Serial  
Mount the module on a 35 mm DIN rail according to EN  
60715.  
When using the DIN rail connector, first place it into the  
DIN rail (see A – C). It is used to bridge the power supply.  
It is also absolutely vital that you snap the module and the  
DIN rail connector into position in the correct direction:  
the snap-on foot should be at the bottom and the connec-  
tor on the left.  
Figure 3  
Spring-cage connection  
A 400 mA fuse should be connected upstream.  
Supply via a Power Terminal Block  
The MINI MCR-SL-PTB-FM power terminal block (Order No.  
2902958) or the MINI MCR-SL-PTB-FM-SP power terminal  
block (Order No. 2902959), which are the same shape, are  
used to feed the supply voltage to the DIN rail connector.  
We recommend connecting a 2.5 A slow-blow fuse (e.g.,  
SIBA 179 120.2,5 20x5).  
Supply via a system power supply unit  
The system power supply unit with 1.5 A output current con-  
nects the DIN rail connector to the supply voltage and can  
therefore be used to supply several modules from the mains.  
MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.  
2866983)  
Potentially explosive areas:  
MINI-PS-100-240AC/24DC/1.5/EX (Order No. 2866653)  
105446_en_00  
PHOENIX CONTACT  
8
MINI MCR-RTD-UI-NC  
6.6  
Connecting the wires  
The module is available in two connection versions:  
Screw terminal blocks (for MINI MCR-RTD-UI-NC)  
"Spring-cage terminal blocks (for MINI MCR-RTD-UI-SP-  
NC)  
Screw connection:  
B
A
w.interface.phoenixcontact.com  
XXXXXXXX  
No.  
Serial  
Figure 5  
Screw connection  
Insert the wire into the corresponding connection terminal  
block.  
Use a screwdriver to tighten the screw in the opening  
above the connection terminal block.  
Spring-cage connection:  
A
B
w.interface.phoenixcontact.com  
XXXXXXXX  
o.  
N
Serial  
Figure 6  
Spring-cage connection  
Insert a screwdriver into the opening above the connec-  
tion terminal block.  
Insert the wire into the corresponding connection terminal  
block.  
105446_en_00  
PHOENIX CONTACT  
9
MINI MCR-RTD-UI-NC  
7
Fault monitoring FM  
Detected errors on the signal input or in the device are re-  
ported via the DIN rail connector to the MINI MCR-SL-FM-  
RC-NC (Order No. 2902961) or MINI MCR-SL-FM-RC-SP-  
NC (Order No. 2902962), which are the same shape. The  
module reports the error centrally via an N/C contact.  
In one group, a fault monitoring module is only required once.  
Individual evaluation of the up to 80 Phoenix Contact isolation  
amplifiers can be omitted.  
The fault monitoring module can also be used to monitor the  
supply voltage.  
For the behavior of the fault monitoring contact for the dif-  
ferent DIP switch configurations, please refer to the table.  
Error response  
Fault monitoring: N/C contact  
Measuring range Measuring range Cable break  
Short-circuit  
overrange  
activated  
underrange  
deactivated  
activated  
A
B
C
D
activated  
activated  
activated  
deactivated  
activated  
deactivated  
activated  
activated  
deactivated  
activated  
activated  
deactivated  
deactivated  
activated  
deactivated  
deactivated  
activated  
NE43  
Upscale  
Downscale  
0 mA  
Upscale/downscale  
Module error  
Invalid DIP switch configuration  
Activated (error is always reported)  
Activated (error is always reported)  
105446_en_00  
PHOENIX CONTACT 10  
MINI MCR-RTD-UI-NC  
8
Configuration  
8.1  
Configuration via DIP switches  
The modules have the standard configuration:  
At delivery, all DIP switches are in the "OFF" position.  
Configure the DIP switches according to the planned applica-  
tion using the configuration tables.  
DIP switch S1 is used to specify the configuration method,  
connection method, output signal range, and measuring  
range start value.  
DIP switch S2 is used to specify the measuring range final  
value, sensor type (Pt 100/Pt 1000, IEC 751), an the error  
contact behavior.  
Sensor Pt 100 IEC 751  
3-wire  
-50...150°C  
Output 4...20 mA  
Error evaluation according to NE43 (downscale)  
Fault monitoring contact reacts to all errors  
The module can also be configured with the  
supply voltage not connected.  
8.2  
Connectable sensors  
Sensor Standard  
type  
Measuring range  
Smallest measuring  
range span  
Pt 100  
Pt 200  
Pt 500  
IEC 751 = GOST 6651-2009 (= 0.00385)  
IEC 751 = GOST 6651-2009 (= 0.00385)  
IEC 751 = GOST 6651-2009 (= 0.00385)  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-200°C ... +850°C  
-60°C ... +250°C  
-60°C ... +250°C  
-180°C ... +200°C  
-180°C ... +200°C  
-50°C ... +180°C  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
50 K  
Pt 1000 IEC 751 = GOST 6651-2009 (= 0.00385)  
Pt 100 GOST 6651-2009 (= 0.00391)  
Pt 1000 GOST 6651-2009 (= 0.00391)  
Pt 100 JIS C1604-1997  
Pt 1000 JIS C1604-1997  
Ni 100 DIN 43760  
Ni 1000 DIN 43760  
Cu 50  
Cu 100  
Cu 53  
GOST 6651-2009 (= 1.428)  
GOST 6651-2009 (= 1.428)  
GOST 6651-2009 (= 1.426)  
Customer-specific characteristic curves  
105446_en_00  
PHOENIX CONTACT 11  
MINI MCR-RTD-UI-NC  
Configuration tables  
= ON DIP S1  
1
2
3
4
5
6
7
8
Connection technology  
Analog output signal  
Configuration via software  
2-wire  
3-wire  
4-wire  
0...20 mA  
20...0 mA  
4...20 mA  
20...4 mA  
0...10 V  
10...0 V  
0...5 V  
1...5 V  
Start temperature  
0°C  
-10°C  
-20°C  
-30°C  
-40°C  
-50°C  
-100°C  
-150°C  
32°F  
14°F  
-4°F  
-22°F  
-40°F  
-58°F  
-148°F  
-238°F  
Measuring range final value  
= ON  
DIP S2  
DIP S2  
1
2
3
4
5
6
1
2
3
4
5
6
7
8
9
0
0°C  
5°C  
32°F  
41°F  
160°C  
320°F  
329°F  
338°F  
347°F  
356°F  
365°F  
374°F  
383°F  
392°F  
410°F  
428°F  
446°F  
464°F  
482°F  
500°F  
518°F  
536°F  
554°F  
572°F  
617°F  
662°F  
707°F  
752°F  
797°F  
842°F  
887°F  
932°F  
1022°F  
1112°F  
1202°F  
1292°F  
1562°F  
165°C  
170°C  
175°C  
180°C  
185°C  
190°C  
195°C  
200°C  
210°C  
220°C  
230°C  
240°C  
250°C  
260°C  
270°C  
280°C  
290°C  
300°C  
325°C  
350°C  
375°C  
400°C  
425°C  
450°C  
475°C  
500°C  
550°C  
600°C  
650°C  
700°C  
850°C  
10°C  
15°C  
20°C  
25°C  
30°C  
35°C  
40°C  
45°C  
50°C  
55°C  
60°C  
65°C  
70°C  
75°C  
80°C  
85°C  
90°C  
95°C  
100°C  
105°C  
110°C  
115°C  
120°C  
125°C  
130°C  
135°C  
140°C  
145°C  
150°C  
155°C  
50°F  
59°F  
68°F  
77°F  
86°F  
95°F  
104°F  
113°F  
122°F  
131°F  
140°F  
149°F  
158°F  
167°F  
176°F  
185°F  
194°F  
203°F  
212°F  
221°F  
230°F  
239°F  
248°F  
257°F  
266°F  
275°F  
284°F  
293°F  
302°F  
311°F  
105446_en_00  
PHOENIX CONTACT 12  
MINI MCR-RTD-UI-NC  
Fault evaluation  
Analog OUT  
= ON  
DIP S2  
7
8
9
0
0...20 mA 20...0  
4...20  
20...4  
0...10 V 10...0 V 0...5 V 1...5 V  
21 mA 21 mA 21 mA 10.5 V 10.5 V 5.25 V 5.25 V  
mA  
mA  
mA  
A Cable break  
Overrange  
21 mA  
20.5 mA 20.5 mA 20.5 mA 20.5 mA 10.25 V 10.25 V 5.125 V 5.125 V  
Underrange  
Short circuit  
B Cable break  
Overrange  
Underrange  
Short circuit  
C Cable break  
Overrange  
Underrange  
Short circuit  
D Cable break  
Overrange  
0 mA  
0 mA  
21 mA  
0 mA  
0 mA  
4 mA  
4 mA  
4 mA  
4 mA  
0 V  
0 V  
0 V  
0 V  
0 V  
0 V  
1 V  
1 V  
21 mA 21 mA 21 mA 10.5 V  
10.5 V 5.25 V 5.25 V  
20.5 mA 20.5 mA 20.5 mA 20.5 mA 10.25 V 10.25 V 5.125 V 5.125 V  
0 mA  
0 mA  
21 mA  
20 mA  
0 mA  
21 mA  
0 mA  
20 mA  
0 mA  
0 mA  
0 mA  
0 mA  
3.5 mA 3.5 mA 0 V  
3 mA 3 mA 0 V  
0 V  
0 V  
0 V  
0 V  
0.875 V  
0.75 V  
21 mA 21 mA 21 mA 10.5 V  
20 mA 20 mA 20 mA 10 V  
0 mA  
21 mA 21 mA 21 mA 10.5 V  
0 mA 4 mA 4 mA 0 V  
20 mA 20 mA 20 mA 10 V  
10.5 V 5.25 V 5.25 V  
10 V  
0 V  
5 V  
0 V  
5 V  
1 V  
4 mA  
4 mA  
0 V  
10.5 V 5.25 V 5.25 V  
0 V  
10 V  
0 V  
0 V  
0 V  
5 V  
0 V  
0 V  
1 V  
5 V  
1 V  
1 V  
Underrange  
Short circuit  
0 mA  
0 mA  
4 mA  
4 mA  
4 mA  
4 mA  
0 V  
0 V  
NE43  
(Only OUT = 4...20 mA or 20...4 mA)  
Upscale  
Downscale  
0 mA  
Cable break, overrange, underrange, short circuit  
Cable break, overrange, underrange, short circuit  
Cable break, overrange, underrange, short circuit  
= 21.5 mA  
= 3.5 mA  
= 0 mA  
Up/downscale  
Cable break, short circuit  
Overrange, underrange  
Pt 100 (IEC 751)  
= 3.5 mA  
= 21.5 mA  
Sensor type  
Pt 1000 (IEC 751)  
105446_en_00  
PHOENIX CONTACT 13  
MINI MCR-RTD-UI-NC  
8.3  
Configuration via software (FDT/DTM)  
9
Diagnostic indicator  
The red LED indicates the following error states:  
Use the IFS-USB-PROG-ADAPTER  
(Order No.: 2811271) for connecting the  
device to the PC.  
LED flashes at 2.8 Hz: sensor error or invalid DIP switch  
configuration  
LED flashes at 1.4 Hz: simulation mode  
LED is permanently on: internal device error  
Figure 7  
Connection for programming adapter  
Software configuration provides advantages such as 13 dif-  
ferent sensor types, customer-specific characteristic curves,  
free adjustment of signal output, temperature ranges, and  
error indication.  
The software consists of the FDT framework application and  
a driver (DTM) for every device. The software is available free  
of charge on the Internet at www.phoenixcontact.com.  
Enter the order number of your measuring transducer in  
the search field. The installation packages can be found  
under Downloads.  
If you are already using an FDT framework application,  
only download the DTMs.  
In any other case, download the IFS-CONF software  
package. It contains both the framework application and  
the pre-installed DTMs.  
ANALOG-CONF standard software  
If you do not require an FDT/DTM-based software solu-  
tion, you can use the ANALOG-CONF standard software.  
This software also allows for performing all the settings  
on the device. The software is available free of charge on  
the Internet at www.phoenixcontact.com.  
The USB driver for the programming adapter is  
part of the IFS-CONF, ANALOG-CONF, and of  
the DTM installation package.  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany  
www.phoenixcontact.com  
105446_en_00  
14  

相关型号:

SI9130DB

5- and 3.3-V Step-Down Synchronous Converters

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135LG-T1-E3

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9135_11

SMBus Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9136_11

Multi-Output Power-Supply Controller

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130CG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130LG-T1-E3

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9130_11

Pin-Programmable Dual Controller - Portable PCs

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137DB

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9137LG

Multi-Output, Sequence Selectable Power-Supply Controller for Mobile Applications

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY

SI9122E

500-kHz Half-Bridge DC/DC Controller with Integrated Secondary Synchronous Rectification Drivers

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
VISHAY