2901486 [PHOENIX]

Off-Delay Relay, Momentary, 24VDC (Coil), 0.3s Adj Min, 300s Adj Max, DIN-Rail Mount,;
2901486
型号: 2901486
厂家: PHOENIX CONTACT    PHOENIX CONTACT
描述:

Off-Delay Relay, Momentary, 24VDC (Coil), 0.3s Adj Min, 300s Adj Max, DIN-Rail Mount,

继电器
文件: 总8页 (文件大小:156K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
ETD-BL-1T-OFF-CC- 10S  
Timer relay with off delay (with control contact) and  
adjustable time  
Data sheet  
103617_en_03  
© PHOENIX CONTACT - 2013-09-16  
Features  
1
Description  
Compact timer relay in 6.2 mm housing for controlling time  
6.2 mm narrow housing  
With off delay (with control contact)  
Adjustable time  
Easy and accurate time setting  
Supply voltage 24 V DC  
Output: A floating PDT  
sequences.  
The time is set on the front of the device using a labeled  
thumbwheel, which is recessed to protect against accidental  
modification. A screwdriver is used to change the settings  
(blade width 2.5 mm).  
The compact timer relays are available with different time  
ranges as well as with a screw, spring-cage, and push-in  
connection.  
WARNING: Correct usage in potentially explosive areas  
The module is a category 3 item of electrical equipment. Follow the instructions provided here during  
installation and observe the safety instructions.  
Never carry out work when voltage is present.  
Make sure you always use the latest documentation.  
It can be downloaded from the product at phoenixcontact.net/products.  
This data sheet is valid for all products listed on the following page:  
ETD-BL-1T-OFF-CC- 10S  
2
Ordering data  
Description  
Type  
Order No.  
Pcs. / Pkt.  
Timer relay with screw connection  
Time range 0.1...10 s  
ETD-BL-1T-OFF-CC- 10S  
ETD-BL-1T-OFF-CC-300S  
ETD-BL-1T-OFF-CC- 30MIN  
ETD-BL-1T-OFF-CC-300MIN  
2917450  
2917463  
2917467  
2917489  
1
1
1
1
Time range 3...300 s  
Time range 0.3...30 min  
Time range 3...300 min  
Timer relay with spring-cage connection  
Time range 0.1...10 s  
ETD-BL-1T-OFF-CC- 10S-SP  
ETD-BL-1T-OFF-CC-300S-SP  
ETD-BL-1T-OFF-CC- 30MIN-SP  
ETD-BL-1T-OFF-CC-300MIN-SP  
2917612  
2917625  
2917638  
2917641  
1
1
1
1
Time range 3...300 s  
Time range 0.3...30 min  
Time range 3...300 min  
Timer relay with Push-in connection  
Time range 0.1...10 s  
ETD-BL-1T-OFF-CC- 10S-PT  
ETD-BL-1T-OFF-CC-300S-PT  
ETD-BL-1T-OFF-CC- 30MIN-PT  
ETD-BL-1T-OFF-CC-300MIN-PT  
2901485  
2901486  
2901487  
2901488  
1
1
1
1
Time range 3...300 s  
Time range 0.3...30 min  
Time range 3...300 min  
3
Technical data  
Input data  
Input voltage range  
24 V DC (19,2 V DC ...30 V DC)  
Time setting range  
ETD-BL-1T-OFF-CC- 10S  
ETD-BL-1T-OFF-CC-300S  
ETD-BL-1T-OFF-CC- 30MIN  
ETD-BL-1T-OFF-CC-300MIN  
0.1 s ... 10 s  
3 s ... 300 s  
0.3 min ... 30 min  
3 min ... 300 min  
ETD-BL-1T-OFF-CC- 10S-SP  
ETD-BL-1T-OFF-CC-300S-SP  
ETD-BL-1T-OFF-CC- 30MIN-SP  
ETD-BL-1T-OFF-CC-300MIN-SP  
0.1 s ... 10 s  
3 s ... 300 s  
0.3 min ... 30 min  
3 min ... 300 min  
ETD-BL-1T-OFF-CC- 10S-PT  
ETD-BL-1T-OFF-CC-300S-PT  
ETD-BL-1T-OFF-CC- 30MIN-PT  
ETD-BL-1T-OFF-CC-300MIN-PT  
0.1 s ... 10 s  
3 s ... 300 s  
0.3 min ... 30 min  
3 min ... 300 min  
Function  
OFF-CC: Off delay with control contact  
Setting accuracy  
Repeat accuracy  
Nominal current typ.  
2.5 % (of scale end value)  
0.5 % (From the measuring range final value)  
15 mA (Relay ON)  
7 mA (Relay OFF)  
Output data  
Contact type  
1 floating PDT  
Output fuse  
6.3 A (fast-blow)  
Switching capacity  
1500 VA (6 A / 250 V AC)  
Control contact  
Control contact  
Non-floating, terminals A1-B1  
min. 50 ms  
Control pulse length  
103617_en_03  
PHOENIX CONTACT  
2
ETD-BL-1T-OFF-CC- 10S  
General data  
Mechanical service life  
Service life, electrical  
Operating mode  
Degree of protection  
Pollution degree  
Surge voltage category  
Rated insulation voltage  
Impulse withstand voltage  
Inflammability class according to UL 94  
Mounting  
7
Approx. 2 x 10 cycles  
5
Approx. 2 x 10 cycles at ohmic load, 1000 VA  
100% operating factor  
IP20  
2 (according to EN 50178)  
III, safe isolation (according to EN 50178)  
300 V AC (According to EN 50178)  
6 kV (According to EN 50178)  
V0  
on standard DIN rail NS 35 in accordance with EN 60715  
Mounting position  
Width  
Any  
6.2 mm  
Height  
80 mm  
Depth  
86 mm  
Type of housing  
Color  
Polyamide PA, self-extinguishing  
green  
Connection data Screw connection  
Conductor cross section, solid  
Conductor cross section, stranded  
AWG  
0.14 mm² ... 2.5 mm²  
0.14 mm² ... 2.5 mm²  
30 ... 12  
Stripping length  
8 mm  
Tightening torque  
0.6 Nm ... 0.8 Nm / 5 lb in ... 7 lb in  
Connection data Spring-cage conn.  
Conductor cross section, solid  
Conductor cross section, stranded  
AWG  
0.14 mm² ... 2.5 mm²  
0.14 mm² ... 2.5 mm²  
26 ... 12  
Stripping length  
8 mm  
Connection data Push-in conn.  
Conductor cross section, solid  
Conductor cross section, stranded  
AWG  
0.14 mm² ... 2.5 mm²  
0.14 mm² ... 2.5 mm²  
26 ... 14  
Stripping length  
8 mm  
Ambient conditions  
Ambient temperature (operation)  
Ambient temperature (storage/transport)  
Permissible humidity (operation)  
-20 °C ... 65 °C  
-25 °C ... 80 °C  
15 % ... 85 %  
Conformance / approvals  
Conformance  
CE-compliant  
ATEX  
X II 3 G Ex nA nC IIC T4 Gc X  
UL/C-UL listed UL 508  
GL EMC 1 C  
UL, USA / Canada  
GL (not for ETD-BL-...-PT)  
103617_en_03  
PHOENIX CONTACT  
3
ETD-BL-1T-OFF-CC- 10S  
Conformance with EMC Directive 2004/108/EC  
Noise immunity  
EN 61000-6-2  
EN 61000-6-4  
When being exposed to interference, there may be minimal deviations.  
Noise emission  
Conformance with LV directive 2006/95/EC  
Electronic equipm. for electrical power installations according to  
EN 50178  
4
Block diagram  
B1  
12 14  
A1 +  
t
A2 –  
11  
U = 24 V DC  
103617_en_03  
PHOENIX CONTACT  
4
ETD-BL-1T-OFF-CC- 10S  
5
Safety regulations and installation notes  
WARNING: Risk of electric shock  
Never carry out work when voltage is present.  
Installation notes  
The category 3 device is suitable for installation in the zone 2 potentially explosive area. It fulfills the  
requirements of EN 60079-0:2009 and EN 60079-15:2010.  
NOTE: Installation, operation and maintenance may be carried out only by qualified electricians. Follow the  
specified installation instructions. When installing and operating the device, the applicable safety directives  
(including national safety directives), accident prevention regulations, as well as general technical regulations,  
must be observed. The technical data should be taken from this data sheet and the certificates (conformity  
assessment, other possible approvals).  
NOTE: Do not open the device or make changes to it. Do not repair the device yourself, replace it with an  
equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for any  
damage due to violation of the described regulations.  
NOTE: The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for a clean and dry  
environment. Do not subject the device to any load that exceeds the described limits.  
WARNING: Explosion hazard  
The device has not been designed for use in potentially dust-explosive atmospheres.  
Installation in Ex area (zone 2)  
NOTE: Please observe the requirements defined for use in potentially explosive atmospheres!  
WARNING: Explosion hazard  
The device should be installed in a housing (control or distributor box) that fulfills the requirements of  
EN 60079-15 and at least IP54 (EN 60529) degree of protection.  
WARNING: Explosion hazard  
When installing and connecting the supply and signal circuits observe the requirements of EN 60079-14. Only  
devices suitable for operation in Ex zone 2 and the conditions at the application site may be connected to the  
circuits in zone 2.  
WARNING: Explosion hazard  
Cables may be connected and disconnected in potentially explosive areas only when power is disconnected.  
WARNING: Explosion hazard  
The device must be stopped and immediately removed from the Ex area if it is damaged or was subject to an  
impermissible load or stored incorrectly or if it malfunctions.  
You can download the latest documents at www.phoenixcontact.net/products.  
103617_en_03  
PHOENIX CONTACT  
5
ETD-BL-1T-OFF-CC- 10S  
6
Structure  
1
2
3
Knurled wheel for setting the time  
LED U/t (green): Supply voltage and adjustable time  
LED R (yellow): Output relay  
A1+  
A1+  
A1+  
A2-  
A2–  
A2–  
F
ON  
A
ET  
R
O
I
O
t
T
a
t
m
2
I
m
17  
37  
9
I
E
W
n
12  
a
2
I
2
14  
D
T
AC  
n
X
1
s
ON  
+
0
12  
w
1, 2  
3
e
14  
x10%  
1
1
12  
R
14  
11  
7
Installation  
WARNING: Risk of electric shock  
Never carry out work when voltage is present.  
The module can be snapped onto all 35 mm DIN rails according to EN 60715.  
UL requirement: Use copper cables approved for at least 75°C.  
Power supply  
The module is supplied with 24 V of DC voltage.  
103617_en_03  
PHOENIX CONTACT  
6
ETD-BL-1T-OFF-CC- 10S  
8
Time setting  
The time can be adjusted variably using a screwdriver (blade  
width 2.5 mm). The value set on the knurled wheel multiplied  
by 10 gives the percentage set value of the time end value.  
A1+  
A2-  
B1  
Example:  
Time end range of the time relay = 10 s  
1
Setting on the knurled wheel = 6  
6 x 10 % = 60 %  
Time end range of the time relay = 10 s 60 % of 10 s = 6 s  
+
1
According to the setting of the knurled wheel (1...10), you can  
also read the time directly from the "Time setting for different  
time setting ranges" table.  
6
x10%  
R
11  
14  
12  
Time settings for various time setting ranges:  
Position 0.1 - 10 s 3 - 300 s  
0.3 - 30 min  
time [minutes]  
3 - 300 min  
time [minutes]  
Knurled wheel time [seconds] time [seconds]  
0
1
0,1  
1
3
30  
0,3  
3
3
30  
2
2
60  
6
60  
3
3
90  
9
90  
4
5
6
7
8
9
10  
4
5
6
7
8
9
10  
120  
150  
180  
210  
240  
270  
300  
12  
15  
18  
21  
24  
27  
30  
120  
150  
180  
210  
240  
270  
300  
The following table shows some examples: All intermediate values (e. g. 1.5) can be adjusted.  
The smallest adjustable time is reached at position "0". No time can be set between "10" and "0". This area is  
identified with a quickly flashing geed LED.  
103617_en_03  
PHOENIX CONTACT  
7
ETD-BL-1T-OFF-CC- 10S  
9
Diagnostics  
The LEDs indicate the following error states:  
LED U/t (green, backlighting of the knurled wheel)  
Flashes: Voltage is present, the set time is elapsing  
Flashing quickly: Undefined time range between "10" and "0" adjusted  
On: Voltage is present, the set time has elapsed  
LED R (yellow)  
On: The output relay has picked up  
Off: The output relay is dropped  
10 Connection example  
+
24 VDC  
A1+  
A2–  
B1  
11  
12 14  
11  
14  
12  
11 Function  
OFF-CC: With off delay with control contact  
Supply voltage U must be applied permanently to the device  
(green LED U/t lights up). When control contact A1-B1  
closes, the output relay picks up (yellow LED R lights up). If  
control contact A1-B1 opens, the set time t starts running  
(green LED U/t flashes). After time t has elapsed (green LED  
U/t lights up) the output relays drop out (yellow LED R is not  
lit). If the control contact is closed again before time t elapses,  
the elapsed time is deleted and restarted with the next cycle.  
U
LED U/t  
A1 - B1  
LED R  
t
< t  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany  
phoenixcontact.com  
103617_en_03  
8

相关型号:

2901538

RAD-PT100-4-IFS
PHOENIX

2901540

RAD-PT100-4-IFS
PHOENIX

2901541

RAD-PT100-4-IFS
PHOENIX

2901543

BRIDGE- 2-3M
PHOENIX

2901604

Round cable - VIP-CAB-FLK14/AXIO/0,14/0,5M
PHOENIX

2901605

VIP-CAB-FLK14/AXIO/0 14/1 0M
PHOENIX

2901606

VIP-CAB-FLK14/AXIO/0 14/1 5M
PHOENIX

2901607

Round cable - VIP-CAB-FLK14/AXIO/0,14/2
PHOENIX

2901608

VIP-CAB-FLK14/AXIO/0 14/2 5M
PHOENIX

2901609

VIP-CAB-FLK14/AXIO/0 14/3 0M
PHOENIX

2901610

VIP-CAB-FLK14/AXIO/0 14/4 0M
PHOENIX

2901611

VIP-CAB-FLK14/AXIO/0 14/6 0M
PHOENIX