PLC-…24UC/1/S/H  
PLC-…24UC/1/S/L  
PLC INTERFACE With Switch and Integrated  
Power Contact Relay  
INTERFACE  
Data Sheet  
101460_en_04  
© PHOENIX CONTACT - 03/2008  
inserted in the bridge shafts. They eliminate the need for  
complicated and time-consuming loop bridges.  
1
Description  
The 6.2 mm PLC-…24UC/1/S… PLC INTERFACE module  
supports "Manual", "Zero", and "Automatic" functions. The  
load can be switched directly using the module.  
1.3  
Additional Advantages  
Environmentally friendly, cadmium-free power contact  
material for loads up to 250 V AC/6 A  
1.1  
Switching Function  
Integrated input/protective circuit  
Depending on the version, the switch can be operated either  
by hand or using a screwdriver.  
A floating contact provides confirmation for the "Automatic"  
switching state.  
Safe isolation according to DIN EN 50178  
Spring-cage and screw connection types available  
6 kVrms electrical isolation between coil and contact  
Floating confirmation contact for "Automatic" switching  
state  
1.2  
Optimum Use of Plug-In Bridges  
The PLC INTERFACE module achieves maximum  
efficiency with the user-friendly FBST plug-in bridge system.  
The PLC-…24UC/1/S… makes effective use of the bridging  
options for the A1/A2 connection on the coil side, for the  
supply at connection 13 on the contact side, and for the  
manual input at connection M. Especially effective here are  
the 500 mm long color-insulated continuous plug-in bridges  
that can easily be cut to the required length and quickly  
Make sure you always use the latest documentation.  
It can be downloaded at www.download.phoenixcontact.com.  
A conversion table is available on the Internet at  
www.download.phoenixcontact.com/general/7000_en_00.pdf.  
This data sheet is valid for all products listed on the following page:  
PLC-…24UC/1/S…  
2
Ordering Data  
PLC INTERFACE With Switch (Operation by Hand)  
Description  
PLC INTERFACE with switch (operation by hand) and integrated power  
contact relay for "Manual", "Zero", and "Automatic" functions, with screw  
connection, for mounting on 3  
Type  
PLC-RSC- 24UC/1/S/H  
Order No.  
2982236  
Pcs./Pck.  
10  
PLC INTERFACE with switch (operation by hand) and integrated power  
contact relay for "Manual", "Zero", and "Automatic" functions, with spring-cage  
connection, for mounting on 3  
PLC-RSP- 24UC/1/S/H  
2982249  
10  
PLC INTERFACE With Switch (Operation Using a Screwdriver)  
Description Type  
PLC INTERFACE with switch (operation using a screwdriver) and integrated PLC-RSC- 24UC/1/S/L  
power contact relay for "Manual", "Zero", and "Automatic" functions, with  
screw connection, for mounting on 3  
Order No.  
2834876  
Pcs./Pck.  
10  
PLC INTERFACE with switch (operation using a screwdriver) and integrated PLC-RSP- 24UC/1/S/L  
power contact relay for "Manual", "Zero", and "Automatic" functions, with  
spring-cage connection, for mounting on 3  
2834889  
10  
For the protection of input and output, inductive loads must be dampened with an effective protective circuit.  
Accessories  
Description  
Insulating plate  
Type  
PLC-ATP BK  
Order No.  
2966841  
Pcs./Pck.  
25  
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages  
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for  
potential bridging) and for safe isolation between adjacent modules.  
For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com.  
101460_en_04  
PHOENIX CONTACT  
2
 
PLC-…24UC/1/S…  
3
Technical Data  
Input Data  
Input voltage U  
24 V AC/DC, 50 Hz ... 60 Hz  
See "Operating Voltage Range" on page 4  
11 mA  
N
Permissible range (with reference to U  
Typical input current at U  
Input circuit  
)
N
N
Yellow LED, bridge rectifier  
Output Data  
Contact type  
Contact material  
Maximum switching voltage  
Minimum switching voltage  
Limiting continuous current  
Maximum inrush current  
Minimum switching current  
Maximum shutdown power  
Single contact, 1 N/O contact  
Silver tin oxide AgSnO  
250 V AC/DC  
12 V AC/DC  
6 A  
On request  
10 mA  
1
Ohmic load τ = 0 ms  
24 V DC 140 W  
48 V DC 20 W  
60 V DC 18 W  
110 V DC 23 W  
220 V DC 40 W  
250 V AC 1500 VA  
120 mW  
Minimum switching power  
1
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules  
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.  
General Data  
Rated insulation voltage  
250 V AC  
6 kV  
Impulse voltage withstand level  
Ambient temperature range  
Operation  
-25°C ... 60°C  
Storage/transport  
-20°C ... 85°C  
Nominal operating mode  
100% operating factor  
Inflammability class according to UL 94 (housing)  
Air and creepage distances between the circuits  
Standards/specifications  
V0  
DIN EN 50178/VDE 0160 (safe isolation, reinforced insulation I/O)  
IEC 60664, IEC 60664 A, DIN VDE 0110, DIN EN 50155/VDE 0115-200 (in  
relevant parts), IEC 60255/DIN VDE 0435 (in relevant parts)  
Pollution degree  
2
Surge voltage category  
Mounting position  
III  
Any  
Mounting  
Can be aligned without spacing  
Conductor cross-section  
Solid, with screw connection  
Stranded, with screw connection  
Solid, with spring-cage connection  
Stranded, with spring-cage connection  
Stripping length  
2
2
0.14 mm ... 2.5 mm (26 - 14 AWG)  
2
2
0.14 mm ... 1.5 mm (26 - 14 AWG)  
2
2
0.2 mm ... 2.5 mm (24 - 14 AWG)  
0.2 mm ... 1.5 mm (24 - 14 AWG)  
2
2
Screw connection  
10 mm  
Spring-cage connection  
Dimensions (W x H x D)  
Housing material  
8 mm  
6.2 mm x 94 mm x 80 mm  
Polybutylene terephthalate PBT, non-reinforced, green  
101460_en_04  
PHOENIX CONTACT  
3
PLC-…24UC/1/S…  
Confirmation  
"Automatic" mode, floating  
30 V AC/DC / 50 mA, maximum  
2 V AC/DC / 1 mA, minimum  
Approvals  
CE  
c
UL/CUL  
GL  
Applied for  
Planned  
4
Application Example  
6
Operating Voltage Range  
U
U
VCC  
1,4  
1,3  
1,2  
1,1  
1
N
+ -  
A
A1  
A2  
UN= 24 V DC / 24 V AC  
CTL2  
0,9  
0,8  
0,7  
B
A
O
M
20 25 30 35 40 45 50 55 60 65  
C]  
T
[
°
CTL1  
M
U
13  
General Conditions  
14  
Direct alignment in the block, all devices 100% operating  
factor, horizontal or vertical mounting.  
Curve A  
Maximum permissible continuous voltage Umax with limiting  
continuous current on the contact side  
5
Block Diagram  
Curve B  
A2  
Minimum permissible relay operate voltage Uop following  
pre-excitation  
13  
M
0
14  
A1  
2(CTL)  
1(CTL)  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0  
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300  
www.phoenixcontact.com  
101460_en_04  
4

相关型号:

2834973

REL-IR/LDP-220DC/4X21AU
PHOENIX

2835

85 MHz differential notch filter
KR

2835121

Modular Terminal Block, 2.5mm2
PHOENIX

2835510

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

2835510TL

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

2835511

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

28355110

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

28355110TL

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

28355111

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

28355116

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

2835516

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES

28355210

Series 55 Universal Zero-Insertion-Force DIP Test Socket
ARIES