PSR-PS21  
SIL coupling relay  
Data sheet  
106253_en_02  
© PHOENIX CONTACT 2015-07-14  
1
Description  
Intended Use  
Features  
The PSR-PS21 SIL coupling relay can be used for power  
adaptation and electrical isolation in high and low-demand  
applications up to SIL 2 according to IEC 61508 as well as  
EN 61511.  
Using this module, circuits are interrupted in a safety-ori-  
ented manner.  
The safety relay is equipped with an enabling current path  
and a confirmation current path that drop out without delay  
according to stop category 0 in accordance with  
EN 60204-1.  
By filtering the controller test pulses, premature failure of the  
safety relays is prevented.  
SIL 2 coupling relay for safety-related switching off  
Can be used in high and low-demand applications  
Approved for Class I, Zone 2 applications  
Easy proof test:  
- Active error acknowledgment via A1  
- Visually on the device  
- Evaluation of the force-guided N/C contact  
Integrated DCS test pulse filter  
Low inrush current  
1 undelayed enabling current path  
1 undelayed confirmation current path  
1 digital signal output  
Fixed screw connection  
6.8 mm housing width  
Controller-specific Termination Carrier available on re-  
quest  
If an error occurs inside the module, the internal device input  
impedance is affected. As such with compatible, safe sys-  
tems, the test pulses sent from the controller may be dis-  
rupted and the error can be reported back to the corre-  
sponding digital output without any additional wiring effort.  
WARNING: Risk of electric shock  
Observe the safety instructions in the corresponding section!  
Make sure you always use the latest documentation.  
It can be downloaded from the product at phoenixcontact.net/products.  
This data sheet is valid for all products listed on the following pages.  
 
PSR-PS21  
2
Table of contents  
1
Description .............................................................................................................................. 1  
Table of contents..................................................................................................................... 2  
Ordering data .......................................................................................................................... 3  
Technical data ......................................................................................................................... 3  
Safety notes............................................................................................................................. 6  
2
3
4
5
5.1  
5.2  
Installation in the Ex area (class I, zone 2).................................................................................. 7  
Installation in areas with a danger of dust explosions .................................................................... 7  
6
7
Basic circuit diagram ............................................................................................................... 8  
Derating................................................................................................................................... 8  
7.1  
7.2  
7.3  
Vertical mounting position...................................................................................................... 8  
Horizontal mounting position .................................................................................................. 8  
Mounting position with module front at the top............................................................................. 9  
8
9
Load curve............................................................................................................................... 9  
Ohmic load ........................................................................................................................ 9  
8.1  
Operating and indication elements ........................................................................................ 10  
9.1  
9.2  
Connection versions........................................................................................................... 10  
Connection assignment....................................................................................................... 10  
10  
11  
12  
13  
14  
Mounting and connection ...................................................................................................... 11  
Startup................................................................................................................................... 11  
Proof test ............................................................................................................................... 11  
Calculating the power dissipation .......................................................................................... 12  
Application examples ............................................................................................................ 13  
14.1 Application example 1 - SIL 2................................................................................................ 13  
15  
Revision history ..................................................................................................................... 14  
106253_en_02  
PHOENIX CONTACT  
2
 
PSR-PS21  
3
Ordering data  
Description  
Type  
Order No.  
Pcs. / Pkt.  
Coupling relay for SIL 2 high- and low-demand applications, couples digital PSR-PS21-1NO-1NC-24DC-SC  
output signals to the I/O, 1 enabling current path, 1 confirmation current  
path, 1 digital signal output, safe state off applications, test pulse filter, fixed  
screw terminal block  
2700357  
1
4
Technical data  
Hardware/firmware version  
HW/FW  
00/-- (The technical data and safety characteristics are valid as of the specified  
HW/FW version.)  
Input data  
Rated control supply voltage U  
24 V DC -15 % / +10 %  
typ. 45 mA  
S
Rated control supply current I  
Supply voltage  
S
24 V DC -15 % / +10 % (Diagnostic supply voltage U )  
D
Input current  
6 mA (at 21-A2 for U ; depending on load + 100 mA at M1 and 22)  
D
Typical inrush current  
400 mA (t < 10 s at U )  
s
2.5 A (t < 20 s at U )  
D
Power consumption at U  
Filter time  
typ. 1.08 W  
S
max. 2 ms (at A1-A2; test pulse width)  
100 ms (at A1-A2; test pulse rate)  
Typical starting time with U  
Typical release time with U  
Recovery time  
< 100 ms (when controlled via A1)  
< 35 ms (when controlled via A1)  
500 ms  
s
s
Maximum switching frequency  
Operating voltage display  
Status display  
1 Hz  
1 x yellow LED  
2 x green LEDs  
Indication  
1 x red LED  
Protective circuit  
Surge protection Suppressor diode  
Polarity reversal protection for rated control supply voltage and diagnostic supply  
voltage  
Output data  
Contact type  
1 enabling current path  
1 confirmation current path  
Contact material  
AgSnO (enabling current path)  
2
AgCuNi, + Au (confirmation current path)  
Minimum switching voltage  
Maximum switching voltage  
10 V AC/DC (N/O contact)  
20.4 V DC (N/C contact)  
250 V AC/DC (N/O contact)  
26.4 V DC (N/C contact)  
Nominal current  
6 A (N/O contact)  
Limiting continuous current  
6 A (N/O contact)  
100 mA (N/C contact)  
Maximum inrush current  
Inrush current, minimum  
Sq. Total current  
6 A (N/O contact)  
100 mA (N/C contact)  
3 mA (N/O contact)  
1 mA (N/C contact)  
2
36 A (see to derating)  
106253_en_02  
PHOENIX CONTACT  
3
PSR-PS21  
Output data  
Switching capacity min.  
Mechanical service life  
Output fuse  
30 mW  
6
10 x 10 cycles  
6 A gL/gG (N/O contact)  
4 A gL/gG (for low-demand applications)  
150 mA fast blow (Confirmation current path)  
Alarm outputs  
Number of outputs  
Voltage  
1 (digital, PNP)  
22 V DC (U - 2 V)  
D
Current  
max. 100 mA  
Maximum inrush current  
Short-circuit protection  
500 mA (t = 1 ms at U )  
s
no  
General data  
Relay type  
Electromechanically forcibly guided, dust-proof relay.  
Nominal operating mode  
Degree of protection  
100% operating factor  
IP20  
Min. degree of protection of inst. location  
Mounting type  
IP54  
DIN rail mounting  
Mounting position  
vertical, horizontal, with front of module upward  
See derating curve  
6.8 x 93.1 x 102.5 mm  
PBT yellow  
Assembly instructions  
Dimensions (W/H/D)  
Type of housing  
Clearances and creepage distances between the power circuits  
Rated insulation voltage  
Rated surge voltage/insulation  
DIN EN 50178, EN 60079-15  
250 V AC  
Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, confir-  
mation current path, signal output to the enabling current path; 4 kV/basic insula-  
tion between all current paths and housing  
Pollution degree  
2
Surge voltage category  
III  
Connection data  
Connection method  
Screw connection  
0.2 mm² ... 2.5 mm²  
0.2 mm² ... 2.5 mm²  
26 ... 12  
Conductor cross section, solid  
Conductor cross section, stranded  
Conductor cross section AWG/kcmil  
Stripping length  
12 mm  
Screw thread  
M3  
Ambient conditions  
Ambient temperature (operation)  
Ambient temperature (storage/transport)  
Max. permissible relative humidity (operation)  
Max. permissible humidity (storage/transport)  
Maximum altitude  
-40 °C ... 65 °C (observe derating)  
-40 °C ... 85 °C  
75 % (on average, 85% infrequently, non-condensing)  
75 % (on average, 85% infrequently, non-condensing)  
max. 2000 m (Above sea level)  
Shock  
15g  
2g  
Vibration (operation)  
Conformance / approvals  
Conformance  
CE-compliant  
Approvals  
UL, USA / Canada ( E140324 )  
cULus  
106253_en_02  
PHOENIX CONTACT  
4
PSR-PS21  
Conformance / approvals  
UL, USA / Canada ( E360692 )  
Shipbuilding  
Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X  
GL applied for  
to SIL 2  
Functional Safety in accordance with IEC 61508  
Safety data  
Stop category according to IEC 60204  
0
Safety parameters for IEC 61508 - High demand  
Equipment type  
Type A  
HFT  
SIL  
0
2 (< 15% of the overall SIL)  
-9  
PFH  
8.8 x 10 (4 A DC13; 5 A AC15; 8760 switching cycles/year)  
d
Demand rate  
< 12 Months  
240 Months  
240 Months  
Proof test interval  
Duration of use  
For use in high-demand applications, the diagnostics function must be implemented via the confirmation current path.  
Alternative illustration of the device as 1001 structure for process customers  
Equipment type  
Type A  
HFT  
0
SIL  
2 (< 15% of the overall SIL)  
99.18 %  
Safe Failure Fraction (SFF)  
SD  
494.66 FIT  
79.10 FIT  
SU  
DD  
494.66 FIT  
8.80 FIT  
DU  
Total  
MTBF  
PFH  
1077.22 FIT  
91.65 Years  
-9  
8.8 x 10 (4 A DC13; 5 A AC15; 8760 switching cycles/year)  
Safety parameters for IEC 61508 - Low demand  
Equipment type  
Type A  
HFT  
SIL  
0
2 (< 15% of the overall SIL)  
-3  
PFD  
1.34 x 10  
avg  
Proof test interval  
Duration of use  
20 Months  
240 Months  
Alternative illustration of the device as 1001 structure for process customers  
Equipment type  
Type A  
HFT  
0
SIL  
2 (< 15% of the overall SIL)  
81.2 %  
Safe Failure Fraction (SFF)  
SD  
0 FIT  
SU  
794.1 FIT  
0 FIT  
DD  
DU  
183.8 FIT  
977.9 FIT  
99 Years  
Total  
MTBF  
-4  
PFD  
8.06 x 10 (For T1 = 1 year)  
avg  
106253_en_02  
PHOENIX CONTACT  
5
PSR-PS21  
5
Safety notes  
WARNING: danger due to magnetic inter-  
ference!  
Do not use the device in the vicinity of strong  
magnetic fields (e.g., caused by transformers  
or magnetic iron). The magnetic field strength  
of the environment must not exceed 30 A/m.  
WARNING: Risk of electric shock  
During operation, parts of electrical switching  
devices carry hazardous voltages.  
Before working on the switching device, dis-  
connect the power.  
Please observe the safety regulations of elec-  
trical engineering and industrial safety and lia-  
bility associations!  
Disregarding these safety regulations may re-  
sult in death, serious personal injury or dam-  
age to equipment.  
Startup, mounting, modifications, and up-  
grades should only be carried out by a skilled  
electrical engineer!  
NOTE: Risk of damage to equipment due  
to noise emissions  
When operating relay modules the operator  
must meet the requirements for noise emis-  
sion for electrical and electronic equipment  
(EN 61000-6-4) on the contact side and, if re-  
quired, take appropriate measures.  
NOTE: Risk of damage to equipment due  
to noise emissions  
WARNING: Risk of automatic machine re-  
start!  
For emergency stop applications, the ma-  
chine must be prevented from restarting auto-  
matically by a higher-level control system.  
This is a Class A product. In a domestic envi-  
ronment it may cause radion inteference, in  
which case the user may be required to take  
adequate measures.  
Only use power supply units with safe isola-  
tion and SELV / PELV in accordance with EN  
50178/VDE 0160 (SELV / PELV).  
Protective covers must not be removed when  
operating electrical switching devices.  
WARNING: Danger due to faulty devices!  
NOTE: Electrostatic discharge!  
The devices may be damaged following an er-  
ror and correct operation can no longer be en-  
sured.  
In the event of an error, replace the device im-  
mediately.  
Repairs to the device, especially if the hous-  
ing must be opened, may only be carried out  
by the manufacturer or authorized persons.  
Otherwise the warranty is invalidated.  
The device contains components that can be  
damaged or destroyed by electrostatic dis-  
charge. When handling the device, observe  
the necessary safety precautions against  
electrostatic discharge (ESD) according to  
EN 61340-5-1 and EN 61340-5-2.  
WARNING: Risk due to incorrect installa-  
tion  
For reliable operation, the safety relay must  
be installed in housing protected from dust  
and humidity (IP54).  
Carry out wiring according to the application.  
Refer to the “Application examples” section  
for this.  
WARNING: Risk due to welded relay con-  
tacts  
A suitable and effective protective circuit is to  
be provided for inductive loads. This is to be  
implemented parallel to the load and not par-  
allel to the switch contact.  
106253_en_02  
PHOENIX CONTACT  
6
PSR-PS21  
5.1  
Installation in the Ex area (class I, zone 2)  
WARNING: Explosion hazard  
Ambient temperature in hazardous areas  
(class I, zone 2)  
Observe the derating curves.  
Observe the special temperature conditions according to  
the rating plate.  
The device should be installed in a housing  
(control or distributor box) that fulfills the re-  
quirements of EN 60079-15:2010  
(IEC 60079-15:2010 4th ED.) and at least  
IP54 (EN/ IEC 60529) degree of protection.  
NO-contact  
DO-contact  
250 V AC / 24 V DC  
6 A, Resistive  
24 V DC  
100 mA  
Resistive  
Output  
B300, R300  
WARNING: Explosion hazard  
Ambient  
Temperature  
-20 °C to 65 °C  
The device must be used in no more than a  
pollution degree 2 environment as defined by  
EN/ IEC 60664-1.  
5.2  
Installation in areas with a danger of dust  
explosions  
WARNING: Explosion hazard  
WARNING: Explosion hazard  
The device is not designed for use in atmo-  
spheres with a danger of dust explosions.  
When installing and connecting the supply  
and signal circuits observe the requirements  
of EN/ IEC 60079-14. Only devices suitable  
for operation in Ex zone 2 and the conditions  
at the application site may be connected to  
the circuits in zone 2.  
In potentially explosive areas, only connect  
and disconnect cables when the power is dis-  
connected.  
WARNING: Explosion hazard  
The device must be stopped and immediately  
removed from the Ex area if it is damaged or  
was subject to an impermissible load or  
stored incorrectly or if it malfunctions.  
106253_en_02  
PHOENIX CONTACT  
7
PSR-PS21  
6
Basic circuit diagram  
7
Derating  
7.1  
Vertical mounting position  
A1  
21  
13  
40  
36  
PSR-PS21  
ERR  
PWR  
K1  
30  
K1  
DGN  
20  
10  
24V DC  
16  
A2  
M1  
22  
14  
0,09  
Figure 1  
Block diagram  
55  
0
10  
20  
30  
40  
50  
60  
70  
Key:  
TA [°C]  
Figure 2  
Derating curve - vertical mounting position with  
connected modules  
Designation Explanation  
A1  
+24 V control input with active error ac-  
knowledgment  
Expanded ambient temperature range (with no distance): up  
to +65 °C  
A2  
0 V (GND)  
Conditions:  
M1  
21  
22  
Signal output (PNP)  
+24 V diagnostics input  
Diagnostic output +24 V  
Enabling current path, undelayed  
Max. rated control supply voltage  
24 V DC  
Max. total current of the enabling current path 1 A2  
13/14  
7.2  
Horizontal mounting position  
Confirmation current path 21/22 (N/C contact)  
is not an electrically isolated current path and  
may only be connected to a maximum voltage  
of 26.4 V in relation to A2.  
40  
36  
30  
20  
10  
4
0
10  
20  
30  
40  
50  
60  
70  
TA [°C]  
Figure 3  
Derating curve - horizontal mounting position  
with connected modules  
Expanded ambient temperature range (with no distance): up  
to +65 °C  
Conditions:  
Max. rated control supply voltage  
24 V DC  
Max. total current of the enabling current path 250 mA2  
106253_en_02  
PHOENIX CONTACT  
8
PSR-PS21  
7.3  
Mounting position with module front at the top  
8
Load curve  
8.1  
Ohmic load  
40  
36  
1000  
30  
20  
10  
25  
500  
200  
100  
50  
0,16  
0
55  
10  
20  
30  
40  
50  
60  
70  
20  
TA [°C]  
10  
0,1  
0,2  
0,5  
1
2
5
10  
IDC [A]  
Figure 4  
Derating curve - mounting position with module  
front at the top and aligned modules  
Figure 5  
Relay load curve - ohmic load  
Expanded ambient temperature range (with no distance): up  
to +65 °C  
Conditions:  
Max. rated control supply voltage  
24 V DC  
Max. total current of the enabling current path 250 mA2  
106253_en_02  
PHOENIX CONTACT  
9
PSR-PS21  
9
Operating and indication elements  
9.1  
Connection versions  
1
2
Fixed screw connection  
Snap-on foot for DIN rail mounting  
The year the device was constructed can be  
found underneath the CE designation on the  
housing.  
1
APP  
RO  
V
ALS  
H
W
/
FW  
:
S
00/  
er  
i
a
--  
l N  
o
.
xxxxxxxxxx  
2
W
arn  
rn  
wwh  
i
n
h
g -  
eenn  
R
W
Do  
PPWR  
o
not  
ggiizz  
t
ener seper  
per  
ate  
ee  
dd!!  
G
.K  
H
& CO  
b
m
G
T
AC  
asse  
y
n
a
8
m
arktstr  
g, Ger  
m
IX CONT  
er  
l
PHOEN  
b
m
o
achs  
l
AWG 26-12  
0,2-2,5 mm2  
F
32825  
B
14  
R
W
P
0,5-0,6 Nm  
5-7 lb In  
12 mm  
Figure 6  
Connection versions  
Figure 7  
Year of manufacture of the device  
9.2  
Connection assignment  
Figure  
Designation  
Explanation  
22  
21  
A2  
A1  
Diagnostic output +24 V  
+24 V diagnostics input  
0 V (GND)  
2 2  
2 1  
A 2  
A 1  
+24 V control input with active error acknowledgment  
PWR  
Power LED (yellow)  
PWR  
K1  
ERR  
DGN  
Status indicator safety circuit; LED (green)  
Error LED (red)  
Diagnostics LED (green)  
K1  
ERR  
DGN  
PS 21  
13/14  
M1  
Enabling current path, undelayed  
Signal output (PNP)  
1 3  
1 4  
M 1  
106253_en_02  
PHOENIX CONTACT 10  
PSR-PS21  
10 Mounting and connection  
12 Proof test  
Mount the module on a 35 mm DIN rail according to  
EN 60715.  
In the proof test, you check the individual relay channels.  
1. Deactivate A1/A2.  
2. Apply the 24 V DC diagnosis power supply to con-  
tact 21.  
If the green DGN-LED lights up, the module is functional.  
(Apply 24 V DC to signal output M1.)  
If the red ERR LED lights up, replace the module.  
(Apply 0 V DC to signal output M1. Error acknowledgment  
via A1 is inactive.)  
Figure 8  
Mounting and removing  
If the diagnostic voltage supply is present and the green  
DGN LED and the red ERR LED are on, replace the module.  
Connect the cables to the connection terminal blocks using  
a screwdriver.  
If the diagnostic voltage supply is present but neither of the  
LEDs specified is on, replace the module.  
B
AWG 26-12  
0,2-2,5 mm2  
Replace the device in the event of an error.  
A
12 mm  
0,5-0,6 Nm  
5-7 lb In  
Figure 9  
Connection of the cables  
For compliance with UL approval, use copper  
wire that is approved up to 60°C/75°C.  
11 Startup  
Apply the rated control supply voltage at terminal blocks A1/  
A2. The PWR LED and K1 LED light up.  
Enabling current path 13/14 closes, and confirmation cur-  
rent path 21/22 opens.  
106253_en_02  
PHOENIX CONTACT 11  
PSR-PS21  
13 Calculating the power dissipation  
The total power dissipation of the safety relay  
is based on the input power dissipation and  
the contact power dissipation for the same  
and for different load currents.  
Input power dissipation  
²
P
Input = UB / (US/IS)  
Contact power dissipation  
With the same load currents:  
²
P
Contact = n IL 25 m  
With different load currents:  
²
²
²
P
Contact = (IL1 + IL2 + ... + ILn ) 25 mΩ  
Total power dissipation  
Total =PInput + PContact  
P
therefore  
²
²
PTotal = UB / (US/IS) + n IL 25 mΩ  
or  
²
²
²
²
PTotal = UB / (US/IS) + (IL1 + IL2 + ... + ILn ) 25 mΩ  
Key:  
Designation Explanation  
P
Power dissipation in mW  
UB  
US  
IS  
n
IL  
Applied operating voltage  
Rated control supply voltage  
Rated control supply current  
Number of enabling current paths used  
Contact load current  
106253_en_02  
PHOENIX CONTACT 12  
PSR-PS21  
14 Application examples  
Data for the application example as 1001 structure  
Equipment type  
HFT  
A
0
Key:  
SIL  
SFF  
SD  
SU  
2
SIS = Safety Instrumented System (safe control)  
81.20 %  
0 FIT  
794.1 FIT  
0 FIT  
DC = Diagnostic Coverage according to IEC 61508  
(line/load diagnostics at DO)  
DI  
= Digital input  
DO = Digital output  
DD  
DU  
183.8 FIT  
Total  
MTBF  
PFDavg  
977.9 FIT  
Applications with the PSR-PS21  
99 years  
14.1 Application example 1 - SIL 2  
8.06 x 10-04 (for T1 = 1 year)  
Low-demand application  
Single-channel control  
Diagnostic supply voltage is present  
SIS  
DC 90%  
DO DO DI  
L
24V  
(
(
A1  
PSR-PS21  
A2  
13  
14  
)21  
)22  
K1  
(
)M1  
M
K1  
M
(N)  
Figure 10  
Application example 1 - SIL 2  
106253_en_02  
PHOENIX CONTACT 13  
PSR-PS21  
15 Revision history  
Version  
00  
01  
Date  
Contents  
First publication  
Info box for application example 1 deleted  
Texts / safety notes for ATEX deleted  
2015-03-10  
2015-04-29  
2015-07-14  
02  
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany  
phoenixcontact.com  
106253_en_02  
14  

相关型号:

2700498

PSR-MC30-2NO-1DO-24DC-SC
PHOENIX

2700499

PSR-MC30-2NO-1DO-24DC-SP
PHOENIX

270050100

Board Connector, 5 Contact(s), 1 Row(s), Male, Straight, Solder/Wire Wrap Terminal,
MOLEX

2700548

PSR-MC34-3NO-1DO-24DC-SP
PHOENIX

2700582

Power/Signal Relay,
PHOENIX

2700622

Visu RT and AX OPC server integrated as standard in all devices
PHOENIX

2700623

Visu RT and AX OPC server integrated as standard in all devices
PHOENIX

2700SM28CAN-T13

Trans Voltage Suppressor Diode
PROTEC

2700SM78CA

POWER BUS VOLTAGE SUPPRESSOR
PROTEC

2700SM78CAN-T13

Trans Voltage Suppressor Diode
PROTEC

2700SM78CA_12

POWER BUS VOLTAGE SUPPRESSOR
PROTEC

2701

Lowpass Filter
KR