Thermomagnetic circuit breaker
for mounting on a DIN rail
Data sheet
100695_en_03
© PHOENIX CONTACT 2012-03-09
t [s]
1
Description
Single or multi-position thermomagnetic circuit breaker with
lever actuation, DIN rail mounting, trip-free mechanism that
cannot be influenced, various characteristic curves, all-pole
tripping.
100
①
②
10
The circuit breakers meet the requirements of circuit breaker
standard EN 60934 (IEC 60934): S-type, TM.
1
Typical areas of application are telecommunications
systems, power supply units, industrial switchgear and
control systems, and rail vehicles.
The ideal characteristic curve shown here illustrates the
curve of the thermomagnetic trigger characteristic. The time-
delayed tripping protects the thermal part of the
characteristic curve against overload. The magnetic part of
the circuit breaker responds without delay to high overload
and short-circuit currents and trips within a few milliseconds.
0,1
0,01
1
2
4
6 810
20
Multiples of the nominal current
Figure 1
Ideal characteristic curve
① Thermal tripping range
② Magnetic tripping range
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
This data sheet is valid for all products listed on the following page:
TMC
2
Ordering data
Thermomagnetic circuit breaker
Description
Type
TMC... (see order key)
Order No.
Pcs./Pkt.
6
Thermomagnetic circuit breaker,
with universal foot for mounting on
3or 4
Accessories
Description
Type
EB 80-12
Order No.
3009338
Pcs./Pkt.
1
Insertion bridge, insulated, 80-pos.
(I : 50 A)
max
(For central supply I : 80 A)
N
Zack marker strip, 10-section, for labeling the center of the terminal block
ZB 6
See CLIPLINE catalog
UniCard sheets, for labeling terminal blocks using a Zack marker strip
groove, 96-section, can be labeled with BLUEMARK and CMS-P1-PLOTTER,
color: white
UC-TM 5
0818108
10
Screwdriver
SZS 0,6X3,5
1205053
10
2.1
Type
Order key
Main
Characteristic
curves
Auxiliary
contact versions
Nominal
current
current paths
TMC
1 Single-pos.
2 Two-pos.
3 Three-pos.
F1 Thermal 1.05 x I ... 1.4 x I ,
100 Single-pos.: 1 N/O contact
200 Single-pos.: 1 N/C contact
0.2 A
0.3 A
0.4 A
0.5 A
0.6 A
0.8 A
1 A
2.5 A
3 A
4 A
5 A
6 A
N
N
magnetic 2 x I ... 4 x I DC (fast-blow),
N
N
only for DC applications
M1 Thermal 1.05 - 1.4 I ,
120 Two-pos.: 1 N/O contact, 1 N/C
contact
N
122 Three-pos.: 1 N/O contact, 2 N/C
magnetic
6 x I ... 12 x I AC,
N
N
contacts
7.8 x I ... 15.6 x I DC
8 A
N
N
(medium-blow)
10 A
12 A
15A
16A
1.2 A
2A
Ordering example
TMC with 1-pos. main current path, one N/O contact,
medium-blow characteristic curve, and a nominal current of
2 A: TMC 1 M1 100 2A
3
Technical data
Technical data
Nominal voltage
250 V AC (65 V DC),
3 433 V AC (50/60 Hz)
Nominal current range
Auxiliary circuit
0.2 A ... 16 A, see order key
240 V AC (65 V DC), 1 A
Service life
10,000 cycles with 1 x I , inductive
N
Ambient temperature
Insulation coordination (IEC 60664)
Dielectric strength
-30°C ... +60°C (T 60)
2.5 kV/2, increased insulation in the actuation area
Actuation area
3000 V AC test voltage
3000 V AC test voltage
1500 V AC test voltage
> 100 M (500 V DC)
Main to auxiliary circuit
Position to position
Insulation resistance
100695_en_03
PHOENIX CONTACT
2
TMC
Technical data
Switching capacity I
cn
TMC...0,2 A ... TMC...5 A
TMC...6 A ... TMC...16 A
Characteristic curve F1 and M1
400 A
800 A
2500 A (at 32 V DC)
Switching capacity I (UL 1077)
N
I = 0.2 A ... 16 A
N
1 and 2-pos.
3-pos.
1 and 2-pos.
277 V AC/5000 A
480 V AC/5000 A
65 V DC/2000 A
Degree of protection (IEC 60529)
Actuation area
Connection area
IP30
IP20
Vibration resistance
Characteristic curve F1
Characteristic curve M1
3g (57 Hz ... 500 Hz), ±0.23 mm (10 Hz ... 57 Hz)
53g (57 Hz ... 500 Hz), ±0.38 mm (10 Hz ... 57 Hz)
Test according to IEC 60068-2-6, Test Fc, 10 frequency cycles/axis
Shock resistance
Characteristic curve F1
Characteristic curve M1
25g (11 ms), shock direction 1, 2, 3, 4, 5; 10g (11 ms), shock direction 6
25g (11 ms), shock direction 1, 2, 3, 4, 5; 20g (11 ms), shock direction 6
Test according to IEC 60068-2-27, Test Ea
Corrosion resistance
Humidity test
Weight
96 hours in 5% salt fog
Test according to IE 60068-2-11, Text Ka
240 hours in 95% relative humidity
Test according to IE 60068-2-78, Text Cab
60 g per position, approximately
Technical data according to IEC/DIN VDE
Impulse voltage withstand level
Pollution degree
4 kV
3
2
Auxiliary contact: maximum load current
Maximum cross-section with insertion bridge (solid and stranded)
Surge voltage category
1 A for 2.5 mm
1.5 mm
III
I
2
Insulation material group
Connection capacity
Connection capacity
Solid
Main contact
Auxiliary contact
2
2
2
2
2
2
0.2 mm ... 6 mm
0.2 mm ... 2.5 mm
2
2
Stranded
0.2 mm ... 4 mm
0.2 mm ... 1.5 mm
Connection capacity (stranded with ferrule)
Without plastic sleeve
With plastic sleeve
2
2
2
2
2
0.25 mm ... 4 mm
2
0.25 mm ... 2.5 mm
2
2
0.25 mm ... 2.5 mm
0.25 mm ... 1.5 mm
Two conductors with the same cross-section
Solid and stranded
Stranded with ferrule without plastic sleeve
Stranded with TWIN ferrule with plastic sleeve
2
2
2
2
0.2 mm ... 1 mm
0.2 mm ... 0.75 mm
2
2
2
2
0.2 mm ... 1 mm
0.2 mm ... 0.5 mm
2
2
2
2
0.5 mm ... 2.5 mm
0.5 mm ... 0.75 mm
100695_en_03
PHOENIX CONTACT
3
TMC
Connection capacity (continued)
Stripping length
Main contact
Auxiliary contact
12 mm
12 mm
Internal cylindrical gauge (IEC 60947-1)
Screw thread
A 3
M3
A 1
M3
Tightening torque
0.6 Nm ... 0.8 Nm
0.6 Nm ... 0.8 Nm
General data
Width x length
12.5 mm x 83.5 mm
Height
On NS 35/7.5... DIN rail
On NS 35/15... DIN rail
On NS 32... DIN rail
Insulation material
96 mm
103.5 mm
100.5 mm
PA-F
Inflammability class according to UL 94
Degree of protection (IEC 60529)
Actuation area
V0
IP30
IP20
Connection area
Approvals
Test center
GL, VDE (EN 60934)
UL, CSA
Nominal voltage
Nominal current range
0.1 A ... 32 A
3 433 V AC, 250 V AC, 65 V DC
277 V AC, 277/480 V AC,
3 480 V AC, 65 V DC
0.1 A ... 32 A
...200...
...100...
OFF position
Mains
ON position
Mains
Actuation area
(increased insulation)
SafetyN/C
contact
Mains
Mains
Safety N/O
contact
Installation area
Installation diagram
Figure 3
Figure 2
Circuit diagrams
100695_en_03
PHOENIX CONTACT
4
TMC
Groove for
marking labels
Main contact
Connection terminal block
M3, maximum of 6 mm²
(solid), 0.5 Nm tightening
torque
Auxiliary contact
Connection terminal block M3,
maximum of 1.5 mm² (solid),
0.5 Nm tightening torque
Figure 4
Dimensional drawing (dimensions in mm)
100695_en_03
PHOENIX CONTACT
5
TMC
4
Backup fuse
5
Trigger characteristics
The thermomagnetic circuit breaker is available in
18 nominal current levels and in single and multi-pos.
versions.
NOTE: Use a backup fuse in combination with the
circuit breaker if the maximum switching current
can be exceeded in the event of an error.
The version with the "medium-blow (M1)" trigger
The table lists the maximum switching current, the relevant
internal resistance, and the resulting backup fuse.
characteristic is suitable for AC and DC applications. The
"fast-blow (F1)" characteristic version is suitable for
DC applications.
Nominal
current
NH
backup
fuse
Internal resistance Switching
capacity
The characteristic curves (see page 7) depend on the
ambient temperatures. To avoid early or late disconnection,
the circuit breaker nominal current must be multiplied by a
factor.
F1 (fast- M1
according
blow)
(medium-
blow)
to
for DC
EN 60934
for DC/AC
0.2 A
0.3 A
0.4 A
0.5 A
0.6 A
0.8 A
1 A
1.5 A
2 A
2.5 A
3 A
4 A
5 A
6 A
8 A
10 A
12 A
16 A
Any
Any
Any
Any
Any
39.3
17.5
9.2
6.8
4.2
26.1
11.6
6.6
4.1
3
1.65
1.10
0.47
0.28
0.183
0.124
0.077
0.063
0.045
≤ 0.02
≤ 0.02
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
400 A
800 A
800 A
800 A
800 A
800 A
Ambient temperature
Multiplication factor
-30°C
-20°C
-10°C
0°C
10°C
20°C
30°C
40°C
50°C
60°C
0.76
0.79
0.83
0.88
0.93
1
1.04
1.11
1.19
1.29
Any
Any
2.8
1.6
25 A
25 A
25 A
25 A
25 A
25 A
50 A
50 A
50 A
50 A
50 A
0.78
0.42
0.26
0.18
0.12
0.092
0.054
0.025
0.022
The characteristic curves (see page 7) are also valid for
multi-position devices if all positions have an equal load. For
multi-position devices and only 1-pos. overload, the thermal
tripping limit changes for characteristic curves F1 and M1 to
a maximum of 1.7 x IN.
For DC, the magnetic operate values of the curves are
around factor 1.3 higher.
≤ 0.02 ≤ 0.02
≤ 0.02 ≤ 0.02
Tripping is supported even with high-energy current peaks
< 0.003 s.
NOTE: When mounting several circuit breakers
in rows, observe the mutual warming effect.
When the circuit breakers are loaded
simultaneously, a mutual warming effect occurs,
which has the same effect as an increase in
ambient temperature.
In this case, the nominal current can only be led to 80%.
Alternatively, the load current can be increased by a
multiplication factor and the circuit breaker dimensioned
accordingly.
100695_en_03
PHOENIX CONTACT
6
TMC
5.1
Medium-blow (M1): Nominal value 0.2 A ... 6 A
–
Lower tripping limit: 1.05 x IN
10000
–
–
Lower tripping limit: 1.05 x IN
Upper tripping limit: 1.4 x IN
– 30°C
+ 23°C
10000
1000
100
– 30°C
+ 23°C
1000
+ 55°C
100
10
1
10
1
+ 50°C
0,1
DC
0,1
0,01
0,01
0,001
AC
Multiples of the
nominal current
0,8 1
2
3
4
6
8 10 20 30 50 70 100
Multiples of the
nominal current
0,001
0,8 1
2
3 4 6 8 10
20 30 50 70 100
5.2
Medium-blow (M1): Nominal value 8 A ... 16 A
–
–
Lower tripping limit: 1.05 x IN
Upper tripping limit: 1.4 x IN
10000
– 30°C
+ 23°C
1000
100
+ 55°C
10
1
DC
0,1
AC
0,01
0,001
Multiples of the
nominal current
6 8 10 20 30 50 70 100
0,8 1
2
3
4
5.3
Fast-blow (F1): Nominal value 0.2 A ... 16 A
Only for DC applications.
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
www.phoenixcontact.com
100695_en_03
7