S8PS-15024C [OMRON]
Power Supply Module;型号: | S8PS-15024C |
厂家: | OMRON ELECTRONICS LLC |
描述: | Power Supply Module |
文件: | 总16页 (文件大小:346K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Switching Power Supply
S8PS
Compact DIN-Rail Mounting
Industrial Power Supplies with
Capacities Up to 600 W
D Models range from 50 W to 600 W.
D Universal input: voltage range
100 to 240 VAC.
D Power Factor Correction (PFC) on all models.
D UL508 approval on 100-W and
150-W models.
D DIN-rail mounting brackets provided
(except with 600-W model).
D Protection-ON alarm indicators
(300-W and 600-W models).
D UL, CSA, VDE, and CE approved.
D 3-year warranty.
Ordering Information
Stock Note: Shaded models are normally stocked.
J OPEN-FRAME TYPE
Output
Part number
Rated input voltage Power ratings
Voltage
Current
Front-mounting
bracket
DIN-rail mounting
bracket
100 to 240 VAC
50 W
5 V
10 A
S8PS-05005
S8PS-05012
S8PS-05024
S8PS-10024
S8PS-15024
S8PS-05005D
S8PS-05012D
S8PS-05024D
S8PS-10024D
S8PS-15024D
12 V
24 V
24 V
24 V
4.2 A
2.1 A
4.5 A
6.5 A
100 W
150 W
J COVERED TYPE
Stock Note: Shaded models are normally stocked.
Output
Part number
Rated input voltage Power ratings
Voltage
Current
Front-mounting
bracket
DIN-rail mounting
bracket
100 to 240 VAC
50 W
5 V
10 A
S8PS-05005C
S8PS-05012C
S8PS-05024C
S8PS-10024C
S8PS-15024C
S8PS-05005CD
S8PS-05012CD
S8PS-05024CD
S8PS-10024CD
S8PS-15024CD
12 V
24 V
24 V
24 V
4.2 A
2.1 A
4.5 A
6.5 A
100 W
150 W
102
Switching Power Supply S8PS
J ENCLOSED TYPE
Stock Note: Shaded models are normally stocked.
Output
Voltage
24 V
Part number
Rated input voltage
100 to 240 VAC
Power ratings
Current
14 A
Front-mounting bracket
S8PS-30024C
DIN-rail mounting bracket
300 W
600 W
S8PS-30024CD
---
24 V
27 A
S8PS-60024C
J MODEL NUMBER LEGEND
S8PS-
1
2
3
1. Power Ratings
2. Output Voltage
3. Configuration
050: 50 W
100: 100 W
150: 150 W
300: 300 W
600: 600 W
05: 5 V
12: 12 V
24: 24 V
C: Covered type with Front-mounting Bracket
D: Open-frame type with DIN Rail Mounting Bracket
CD: Covered type with DIN Rail Mounting Bracket
None: Open-frame type with Front-mounting Bracket
J ACCESSORIES (SOLD SEPARATELY)
Stock Note: Shaded models are normally stocked.
Description
Length
Width
Part number
PFP-50N
DIN-rail (See Dimensions section for details.)
0.5 m (1.64 ft)
1 m (3.28 ft)
1 m (3.28 ft)
7.3 mm (0.29 in)
7.3 mm (0.29 in)
16 mm (0.63 in)
PFP-100N
PFP-100N2
Specifications
Item
50 W
100 W
150 W
300 W
600 W
Efficiency (typical)
Life expectancy (See Note 3.)
74 to 80% (depends on the model)
10 yrs. min. (used at 40qC at the rated input with a 50% load, standard installation)
Input
Voltage
100 to 240 VAC (85 to 264 VAC)
47 to 63 Hz
Frequency
Current (See Note 1.)
0.9 or 0.45 A
max.
1.8 or 0.9 A max. 2.7 or 1.4 A max. 5.4 or 2.7 A max. 10 or 5 A max.
Power factor (See Note 1.)
0.95 TYP.
Leakage current
(See Note 1.)
0.5 or 1.0 mA max.
Inrush current (25qC, cold start) 25 or 50 A max.
(See Note 1.)
(This table continues on the next page.)
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Mean Time Between Failures is calculated according to the probability of accidental device failures, and indicates reliability of
devices. Therefore, it does not necessarily represent a life of the product.
3. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40qC and a
load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be
noted that the life expectancy of the fan built into the 600-W model is not included.
4. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
103
Switching Power Supply S8PS
Specifications Table
Item
–
continued from previous page
50 W
100 W
150 W
300 W
600 W
Output
Voltage adjustment range
Ripple (See Note 1.)
–5% to 10%
2% (p–p) max.
Input variation influence
Load variation influence
Temperature variation influence (See Note 1.)
Rise time
0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)
0.8% max. (with rated input, 0 to 100% load)
0.05%/qC max.
1,000 ms max. (up to 90% of output voltage at rated output voltage/current)
20 ms min.
Hold time (See Note 1.)
Additional functions
Overload protection
105% min., voltage trailing intermittent operation
(With the 600-W model, output is turned OFF at 5 s min.)
Overvoltage protection
Overheat protection
Yes
No
No
No
Yes
Protection-ON alarm indicator
Parallel operation
Yes (Red)
Yes, 2 units max.
Characteristics
Cooling method
Natural air-cooling
Fan
Ambient temperature
Operating
Storage
See the derating curve in the Engineering Data section. (with no condensation or
icing)
–25qC to 65qC (-13qF to 149qF) with no condensation or icing
Ambient humidity
Dielectric strength
25% to 85%
3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
100 M: min. (between all output and input/GR terminals at 500 VDC)
10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions
2
300 m/s (approx. 30G), 3 times each in rX, rY, and rZ directions
Yes (green)
Electromagnetic interference
EMC
Conforms to FCC Class B, EN50081-1
(EMI):
EN50081-1
EN55022 class B
EN55022 class B
EN61000-3-2
Emission Enclosure:
Emission AC Mains:
Harmonic Current:
(EMS):
EN50082-2
Immunity ESD:
EN61000-4-2: 4-kV contact discharge (level 2)
8-kV air discharge (level 3)
Immunity RF-interference:
ENV50140:
10 V/m (80 MHz to 1 GHz) (level 3)
10 V (0.15 to 80 MHz) (level 3)
Immunity Conducted Disturbance: ENV50141:
Immunity Burst:
Immunity Surge:
EN61000-4-4: 2-kV power-line (level 3)
2-kV output line (level 4)
EN61000-4-5: between 3-kV lines
between 4.5-kV line and FG
Approved standards
UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Mean Time Between Failure (MTBF) See Note 2. 135,000 hrs min.
Weight (See Note 4.) 400 g max.
60,000 hrs min.
700 g max. 900 g max. 2,200 g max. 3,500 g max.
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Mean Time Between Failures is calculated according to the probability of accidental device failures, and indicates reliability of
devices. Therefore, it does not necessarily represent a life of the product.
3. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40qC and a
load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be
noted that the life expectancy of the fan built into the 600-W model is not included.
4. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)
104
Switching Power Supply S8PS
Engineering Data
J DERATING CURVE
Open-frame Type
Covered Type
50- to 150-W Models
Forced air-cooling;
600-W Model
50- to 150-W Models
Forced air-cooling
50- to 150-W Models
Natural air-cooling
50- to 150-W Models
Natural air-cooling
Ambient temperature (qC)
Ambient temperature (qC)
Note: 1. The derating curve shown is for standard installation. The derating curve depends on mounting direction of the Power Supply.
3
2. Forced air-cooling must be provided with an air volume of 1 m /mm min.
J STANDARD INSTALLATION
50-W Type
20 mm min. 20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
20 mm min.
100/150-W Type
30 mm min.
30 mm min.
20 mm min.
20 mm min.
30 mm min.
30 mm min.
20 mm min.
20 mm min.
300-W Type
20 mm min.
20 mm min.
30 mm min.
30 mm min.
600-W Type
20 mm min.
20 mm min.
20 mm min.
20 mm min.
105
Switching Power Supply S8PS
J OVERLOAD PROTECTION
50- to 300-W Models
The Power Supply has an overload protection function that
protects the load and the power supply from possible
damage by overcurrent. When the output current rises above
a set value (105% of the rated output current), the protection
function is triggered, decreasing the output voltage. When
the output current falls within the rated range, the overload
protection function is automatically cleared.
Intermittent
operation
600-W Models
If an excessive current flows for 5 s or more, the output will
be turned OFF and simultaneously protection-ON alarm
indicator will be lit. To reset the S8PS, turn OFF the input
voltage, leave the S8PS for at least three minutes, and then
apply the input voltage again.
Note: Do not continue using the S8PS with the output termi-
nals short-circuited or the overcurrent condition con-
tinued, otherwise the internal elements of the S8PS
may be damaged or broken.
Rating
Output current (%)
J OVERVOLTAGE PROTECTION
The Power Supply has an overvoltage protection function
that protects the load and the Power Supply from possible
damage by overvoltage. When the output voltage rises
above a set value (120% of the rated output voltage), the
protection function is triggered, shutting OFF the output
voltage. If this occurs, reset the Power Supply by turning it
OFF for 1 minute min. and then turning it ON again.
Rated
output
voltage
300- and 600-W Models
If voltage that is 115% of the rated output voltage or above is
output, the output voltage will be turned OFF and
simultaneously protection-ON alarm indicator will be lit. To
reset the S8PS, turn OFF the input voltage, leave the S8PS
for at least one minute and then apply the input voltage
again.
0 V
J OVERHEAT PROTECTION FUNCTION
600-W Model Only
If the internal temperature of the S8PS rises excessively as a
result of fan failure or any other reason, the overheat protection
circuit will be triggered to protect the internal elements of the
S8PS and simultaneously a protection-ON alarm indicator will be
lit. To reset the S8PS turn OFF the input voltage, leave the S8PS
for at least one minute and then apply the input voltage again.
106
Switching Power Supply S8PS
J INRUSH CURRENT, START UP TIME, HOLD TIME
Input ON
AC input
Input OFF
voltage
Inrush current on input application
AC input
current
96.5%
90%
Output
voltage
Rise time
(1,000 ms max.)
Hold time
(20 ms min.)
Operation
J BLOCK DIAGRAMS
S8PS-050jjjj (50 W)
Rectifier
AC(L)
Fuse
+V
Noise filter
INPUT
DC OUT
–V
AC(N)
Inrush current
Harmonic Smooth-
Rectifier/
smoothing
circuit
protection circuit
current
control
ing
Drive control
circuit
Overload
detection circuit
Detector
Overvoltage
detection circuit
107
Switching Power Supply S8PS
S8PS-10024jj (100 W)
S8PS-15024jj (150 W)
S8PS-30024jj (300 W)
Rectifier
AC(L)
Fuse
+V
–V
Noise filter
INPUT
DC OUT
AC(N)
Harmonic
current
control
Smooth-
ing
Inrush current
protection circuit
Rectifier/
smoothing
circuit
Control circuit
Overload
detection circuit
Detector
Overvolltage-
detection circuit
S8PS-60024C (600 W)
DC OUT
Rectifier/
smoothing
circuit
Control circuit
Fan
Detector
Overcurrent
detection
Overvoltage
detection circuit
Overheat
detection
108
Switching Power Supply S8PS
Dimensions
Unit: mm (inch)
J FRONT-MOUNTING BRACKET TYPE
Note: For instructions on how to install the front-mounting brackets, refer to the a subsequent section: FRONT-MOUNTING BRACKETS.
S8PS-050jj (50 W)
S8PS-050jjjC (50 W)
40
(1.57)
127 (5)
11.5 max.
3.5
72
85
(3.35)
7
10
8.6
Five, M4
terminal screws
117 (4.6)
117
3.5 dia.
3.5 dia.
5
3.5
20
14
28
28
24
Three, M3
depth: 6 max.
100 (3.94)
12.5
S8PS-10024 (100 W)
S8PS-10024C (100 W)
50
(1.97)
11.5 max.
145 (5.71)
4.5
78
92
(3.62)
7
10
8.6
Five, M4 terminal screws
135 (5.31)
135
4.5 dia.
Mounting holes (also on
opposite side)
4.5 dia.
4.5
25
15
28
27.5
Three, M4
depth: 6 max.
100 (3.94)
12.5
109
Switching Power Supply S8PS
S8PS-15024 (150 W)
S8PS-15024C (150 W)
50
(1.97)
163 (6.42)
11.5 max.
4.5
78
92
(3.62)
7
10
8.6
Five, M4 terminal screws
153 (6.02)
153
4.5 dia.
Mounting holes (also on
opposite side)
5
4.5 dia.
4.5
25
15
28
27.5
Three, M4 (depth: 6 max.)
100 (3.94)
S8PS-30024C (300 W)
Eight, M4
depth: 8 max.,
(also for the
opposite side)
175 (6.89)
14
Seven, M4 terminal screws
92
(3.62)
50
(1.97)
10
8.6
21
150 (5.91)
110 (4.33)
13
Four, M4
depth: 8 max.
100
(3.94)
150 (5.91)
5
13
110
Switching Power Supply S8PS
Unit: mm (inch)
S8PS-60024C (600 W)
Seven, M4
depth: 8 max.
Eight, M4
depth: 8 max.,(also
for the opposite side)
170 (6.69)
10
8.6
179 (7.05)
60
(2.36)
92
(3.62)
16
31
160 (6.30)
Four, M4
depth: 8 max.,
(opposite side
only)
14
Four, M4
depth: 8 max.
100
(3.94)
45
(1.77)
12
150 (5.91)
100 (3.94)
34
J FRONT-MOUNTING BRACKETS
50-W Models
Using the Mounting Bracket
11
1.5
9
Attach the Mounting Bracket to the panel and loosely tighten the two screws. Insert
the projected parts of the Bracket (b) to the square holes of the power supply (a).
Then securely tighten the screws.
4.6
15
Two,
3.5 dia.
74
4.6
60
5
20
31.5
Mounting Holes
11
4.7
15
Two, M3
60
20.5
20
Mounting Bracket
111
Switching Power Supply S8PS
100/150-W Models
Appearance and
Using the Mounting Bracket
Dimensions with Mounting Bracket
Mounting Dimensions
Mounting Bracket
Mounting Bracket
6.5
11
5 dia.
115
(4.53)
max.
105
23.5
38
Mounting Bracket
1.5
Two, 5 dia.
30
300/600-W Models
Appearance and Mounting Dimensions
10 dia.
R2.5
30
15
7.5
7.5
145 (5.71)
160 (6.30)
Two,
5 dia.
92 (3.62)
48
(1.89)
32
(1.26)
Dimensions with Mounting Bracket – 300-W models
Using the Mounting Bracket
Note: Mounting screws for the Power Supply Unit are provided.
300-W models
145
(5.71)
80
Note: Mount the Unit 21.6 mm away from the mounting surface in
order to provide air ventilation on the rear side.
(3.15)
Four, M4
600-W models
Dimensions with Mounting Bracket – 600-W models
145
(5.71)
Note: Mount the Unit 28 mm away from the mounting surface in
order to provide air ventilation on the rear side.
140 (5.51)
Four, M4
112
Switching Power Supply S8PS
J DIN-RAIL MOUNTING TYPE
Note: DIN-Rail Mounting Bracket is attached to the Power Supply Unit when the Unit is shipped.
S8PS-050jjD (50 W)
S8PS-050jjjCD (50 W)
40
(1.57)
9.1
127 (5)
3.5
46
85
(3.35)
72
10
8.6
7
5
117
132.6 (5.22)
)
S8PS-10024D (100 W)
S8PS-10024CD (100 W)
50
(1.97)
9.1
145 (5.71)
4.5
92
(3.62)
78
46
10
8.6
7
5
135 (5.31)
150.6 (5.93)
x.)
S8PS-15024D (150 W)
S8PS-15024CD (150 W)
50
(1.97)
9.1
11.5
max.
163 (6.42)
4.5
92
(3.62)
78
46
10
8.6
153 (6.02)
168.6 (6.64)
.)
113
Switching Power Supply S8PS
Unit: mm (inch)
S8PS-30024CD (300 W)
14
17.8
175 (6.89)
92
(3.62)
10
8.6
46
(1.81)
189.3 (7.45)
110 (4.33)
ith
de:
max.)
J DIN-RAIL (ORDER SEPARATELY)
PFP-100N2
PFP-100N/
PFP-50N
16
7.3r0.15
4.5
4.5
27
29.2
1.5
27r0.15
24
35r0.3
35r0.3
15 25
25
25
25 15
15 25
25
25
25
1
1
10
10
10
10
15
5 *
1,000
500*
1,000
* For PFP-50N
114
Switching Power Supply S8PS
Installation
J 50-W MODELS
J 100-/150-W MODELS
4
5
4
5
1
3
2
1
3
2
J 300-W MODELS
J 600-W MODELS
1
5 4
4
5
6
2
3
1
6
2
3
1. DC Output Terminals: Connect the load lines to these terminals.
2. Input Terminals: Connect the input lines to these terminals.
Note: A fuse is inserted into the AC (L) side.
3. Ground Terminal (GR): Connect a ground line to this terminal.
4. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON.
5. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%.
6. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for
a 600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected.
115
Switching Power Supply S8PS
Precautions
WARNING
!
J PARALLEL OPERATION
Do not touch the S8PS or heat radiation fin while the
power is being supplied or immediately after the power is
turned OFF. Otherwise, a skin burn may result from the
hot Switching Power Supply or radiator.
Only 300- and 600-W models can be in parallel operation
provided that they are operated under 90% of the ratings. Do not
operate any other models in parallel.
Make sure that the thickness and the length of all wires
connected to the load are the same to ensure that the wires will
have no voltage drop differences.
J MOUNTING
x
When mounting the power supply, allow space for adequate
air flow around it – to improve and maintain the reliability of
the power supply over a long period of time. The power sup-
ply is designed to dissipate heat through natural air-flow.
+ V
INPUT
– V
x
x
Omron recommends mounting the power supply to a metal
plate.
+ V
Forced air-cooling is recommended.
INPUT
– V
J GENERATING OUTPUT VOLTAGE (r)
An output of r can be generated by using two Power Supplies as
shown below, because the Power Supply produces a floating
output.
J FAN REPLACEMENT
The service life of the fan is approximately 50,000 hours (at
25qC). The service life varies, however, depending on the
ambient temperature or other surrounding environmental
conditions such as dust. As a preventive maintenance measure,
replace the fan within two years if it is used at an ambient
temperature of 40qC.
+ V
INPUT
INPUT
Input
– V
Fans are available as replacements.
Model: S82Y-JFAN
+ V
– V
J SERIES OPERATION
Only models with power ratings of 100/150 W allow series
operation.
As shown in the following diagram, the output voltage from each
Switching Power Supply can be added.
+V
INPUT
–V
Fan Set:
+V
Fan (above), four M4 x 35 sems screws, instruction sheet, and
packing case>
INPUT
–V
Replace the fan as shown in the following illustration.
116
Switching Power Supply S8PS
ꢔꢙꢙꢅꢚꢛ !"ꢓꢛꢜ"ꢓꢅꢓ#ꢜ$"ꢅꢔ%!ꢅꢛ"ꢅ ꢛꢙꢙꢛ !&!%ꢓꢍꢅ&ꢂꢅꢑꢂꢐ'ꢕꢏꢈꢅꢎꢖꢁꢁꢖꢎꢕꢈꢕꢏ(ꢅꢖꢐꢈꢂꢅꢖꢐꢑꢇꢕ()ꢅꢘꢖ'ꢖꢘꢕꢅꢃ*ꢅ+,ꢍ-
ꢀꢁꢂꢀꢃꢄꢀꢃꢅꢆꢇꢃꢈ
ꢀꢁꢂꢀꢃꢄꢈꢆꢈꢉꢔꢂꢀꢃꢇꢉꢕꢄꢆꢆꢉ
ꢜꢐꢕꢅꢗꢂꢎꢎꢕꢏꢑꢕꢅꢚꢏꢖ'ꢕ
ꢀꢁꢂꢀꢃꢄꢉꢊꢃꢊꢋꢊꢌꢄꢇꢃꢉꢍ
22,ꢅ ꢖꢁꢐꢕꢏꢅꢔ'ꢕꢐ3ꢕ
ꢀꢁꢂꢃꢄꢁꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢂꢎ
ꢒꢓꢔꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢂꢎꢋꢂꢕꢖ
ꢗꢄꢐꢄꢘꢄꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢄ
ꢓꢑꢇꢄ3ꢎꢃ3ꢏ7)ꢅꢛꢙꢅꢝ/489
&ꢂꢏꢂꢐꢈꢂ)ꢅꢜꢐꢈꢄꢏꢖꢂꢅ 45ꢅ,62
ꢒꢎꢖꢅꢒꢎꢗꢅꢖꢘꢙꢙ
ꢎꢏꢐꢅꢑꢒꢐꢅꢐꢎꢐꢓ
1ꢂꢏꢅꢒꢓꢅꢈꢕꢑꢇꢐꢖꢑꢄꢁꢅ(3ꢉꢉꢂꢏꢈꢅꢂꢏꢅꢂꢈꢇꢕꢏꢅꢖꢐ:3ꢖꢏꢖꢕ(ꢊ
ꢒꢙꢙꢅꢓꢓꢐꢅꢐꢖꢐꢐ
Cat No. GC PS6
2/03
Specifications subject to change without notice
Printed in USA
117
Switching Power Supply S8PS
相关型号: