S8PS-15024C [OMRON]

Power Supply Module;
S8PS-15024C
型号: S8PS-15024C
厂家: OMRON ELECTRONICS LLC    OMRON ELECTRONICS LLC
描述:

Power Supply Module

文件: 总16页 (文件大小:346K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Switching Power Supply  
S8PS  
Compact DIN-Rail Mounting  
Industrial Power Supplies with  
Capacities Up to 600 W  
D Models range from 50 W to 600 W.  
D Universal input: voltage range  
100 to 240 VAC.  
D Power Factor Correction (PFC) on all models.  
D UL508 approval on 100-W and  
150-W models.  
D DIN-rail mounting brackets provided  
(except with 600-W model).  
D Protection-ON alarm indicators  
(300-W and 600-W models).  
D UL, CSA, VDE, and CE approved.  
D 3-year warranty.  
Ordering Information  
Stock Note: Shaded models are normally stocked.  
J OPEN-FRAME TYPE  
Output  
Part number  
Rated input voltage Power ratings  
Voltage  
Current  
Front-mounting  
bracket  
DIN-rail mounting  
bracket  
100 to 240 VAC  
50 W  
5 V  
10 A  
S8PS-05005  
S8PS-05012  
S8PS-05024  
S8PS-10024  
S8PS-15024  
S8PS-05005D  
S8PS-05012D  
S8PS-05024D  
S8PS-10024D  
S8PS-15024D  
12 V  
24 V  
24 V  
24 V  
4.2 A  
2.1 A  
4.5 A  
6.5 A  
100 W  
150 W  
J COVERED TYPE  
Stock Note: Shaded models are normally stocked.  
Output  
Part number  
Rated input voltage Power ratings  
Voltage  
Current  
Front-mounting  
bracket  
DIN-rail mounting  
bracket  
100 to 240 VAC  
50 W  
5 V  
10 A  
S8PS-05005C  
S8PS-05012C  
S8PS-05024C  
S8PS-10024C  
S8PS-15024C  
S8PS-05005CD  
S8PS-05012CD  
S8PS-05024CD  
S8PS-10024CD  
S8PS-15024CD  
12 V  
24 V  
24 V  
24 V  
4.2 A  
2.1 A  
4.5 A  
6.5 A  
100 W  
150 W  
102  
Switching Power Supply S8PS  
J ENCLOSED TYPE  
Stock Note: Shaded models are normally stocked.  
Output  
Voltage  
24 V  
Part number  
Rated input voltage  
100 to 240 VAC  
Power ratings  
Current  
14 A  
Front-mounting bracket  
S8PS-30024C  
DIN-rail mounting bracket  
300 W  
600 W  
S8PS-30024CD  
---  
24 V  
27 A  
S8PS-60024C  
J MODEL NUMBER LEGEND  
S8PS-  
1
2
3
1. Power Ratings  
2. Output Voltage  
3. Configuration  
050: 50 W  
100: 100 W  
150: 150 W  
300: 300 W  
600: 600 W  
05: 5 V  
12: 12 V  
24: 24 V  
C: Covered type with Front-mounting Bracket  
D: Open-frame type with DIN Rail Mounting Bracket  
CD: Covered type with DIN Rail Mounting Bracket  
None: Open-frame type with Front-mounting Bracket  
J ACCESSORIES (SOLD SEPARATELY)  
Stock Note: Shaded models are normally stocked.  
Description  
Length  
Width  
Part number  
PFP-50N  
DIN-rail (See Dimensions section for details.)  
0.5 m (1.64 ft)  
1 m (3.28 ft)  
1 m (3.28 ft)  
7.3 mm (0.29 in)  
7.3 mm (0.29 in)  
16 mm (0.63 in)  
PFP-100N  
PFP-100N2  
Specifications  
Item  
50 W  
100 W  
150 W  
300 W  
600 W  
Efficiency (typical)  
Life expectancy (See Note 3.)  
74 to 80% (depends on the model)  
10 yrs. min. (used at 40qC at the rated input with a 50% load, standard installation)  
Input  
Voltage  
100 to 240 VAC (85 to 264 VAC)  
47 to 63 Hz  
Frequency  
Current (See Note 1.)  
0.9 or 0.45 A  
max.  
1.8 or 0.9 A max. 2.7 or 1.4 A max. 5.4 or 2.7 A max. 10 or 5 A max.  
Power factor (See Note 1.)  
0.95 TYP.  
Leakage current  
(See Note 1.)  
0.5 or 1.0 mA max.  
Inrush current (25qC, cold start) 25 or 50 A max.  
(See Note 1.)  
(This table continues on the next page.)  
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)  
2. Mean Time Between Failures is calculated according to the probability of accidental device failures, and indicates reliability of  
devices. Therefore, it does not necessarily represent a life of the product.  
3. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40qC and a  
load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be  
noted that the life expectancy of the fan built into the 600-W model is not included.  
4. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)  
103  
Switching Power Supply S8PS  
Specifications Table  
Item  
continued from previous page  
50 W  
100 W  
150 W  
300 W  
600 W  
Output  
Voltage adjustment range  
Ripple (See Note 1.)  
–5% to 10%  
2% (p–p) max.  
Input variation influence  
Load variation influence  
Temperature variation influence (See Note 1.)  
Rise time  
0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)  
0.8% max. (with rated input, 0 to 100% load)  
0.05%/qC max.  
1,000 ms max. (up to 90% of output voltage at rated output voltage/current)  
20 ms min.  
Hold time (See Note 1.)  
Additional functions  
Overload protection  
105% min., voltage trailing intermittent operation  
(With the 600-W model, output is turned OFF at 5 s min.)  
Overvoltage protection  
Overheat protection  
Yes  
No  
No  
No  
Yes  
Protection-ON alarm indicator  
Parallel operation  
Yes (Red)  
Yes, 2 units max.  
Characteristics  
Cooling method  
Natural air-cooling  
Fan  
Ambient temperature  
Operating  
Storage  
See the derating curve in the Engineering Data section. (with no condensation or  
icing)  
–25qC to 65qC (-13qF to 149qF) with no condensation or icing  
Ambient humidity  
Dielectric strength  
25% to 85%  
3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)  
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)  
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)  
Insulation resistance  
Vibration resistance  
Shock resistance  
Output indicator  
100 M: min. (between all output and input/GR terminals at 500 VDC)  
10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions  
2
300 m/s (approx. 30G), 3 times each in rX, rY, and rZ directions  
Yes (green)  
Electromagnetic interference  
EMC  
Conforms to FCC Class B, EN50081-1  
(EMI):  
EN50081-1  
EN55022 class B  
EN55022 class B  
EN61000-3-2  
Emission Enclosure:  
Emission AC Mains:  
Harmonic Current:  
(EMS):  
EN50082-2  
Immunity ESD:  
EN61000-4-2: 4-kV contact discharge (level 2)  
8-kV air discharge (level 3)  
Immunity RF-interference:  
ENV50140:  
10 V/m (80 MHz to 1 GHz) (level 3)  
10 V (0.15 to 80 MHz) (level 3)  
Immunity Conducted Disturbance: ENV50141:  
Immunity Burst:  
Immunity Surge:  
EN61000-4-4: 2-kV power-line (level 3)  
2-kV output line (level 4)  
EN61000-4-5: between 3-kV lines  
between 4.5-kV line and FG  
Approved standards  
UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.  
Mean Time Between Failure (MTBF) See Note 2. 135,000 hrs min.  
Weight (See Note 4.) 400 g max.  
60,000 hrs min.  
700 g max. 900 g max. 2,200 g max. 3,500 g max.  
Note: 1. 100% load for rated input voltage (100 VAC or 200 VAC)  
2. Mean Time Between Failures is calculated according to the probability of accidental device failures, and indicates reliability of  
devices. Therefore, it does not necessarily represent a life of the product.  
3. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40qC and a  
load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be  
noted that the life expectancy of the fan built into the 600-W model is not included.  
4. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)  
104  
Switching Power Supply S8PS  
Engineering Data  
J DERATING CURVE  
Open-frame Type  
Covered Type  
50- to 150-W Models  
Forced air-cooling;  
600-W Model  
50- to 150-W Models  
Forced air-cooling  
50- to 150-W Models  
Natural air-cooling  
50- to 150-W Models  
Natural air-cooling  
Ambient temperature (qC)  
Ambient temperature (qC)  
Note: 1. The derating curve shown is for standard installation. The derating curve depends on mounting direction of the Power Supply.  
3
2. Forced air-cooling must be provided with an air volume of 1 m /mm min.  
J STANDARD INSTALLATION  
50-W Type  
20 mm min. 20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
100/150-W Type  
30 mm min.  
30 mm min.  
20 mm min.  
20 mm min.  
30 mm min.  
30 mm min.  
20 mm min.  
20 mm min.  
300-W Type  
20 mm min.  
20 mm min.  
30 mm min.  
30 mm min.  
600-W Type  
20 mm min.  
20 mm min.  
20 mm min.  
20 mm min.  
105  
Switching Power Supply S8PS  
J OVERLOAD PROTECTION  
50- to 300-W Models  
The Power Supply has an overload protection function that  
protects the load and the power supply from possible  
damage by overcurrent. When the output current rises above  
a set value (105% of the rated output current), the protection  
function is triggered, decreasing the output voltage. When  
the output current falls within the rated range, the overload  
protection function is automatically cleared.  
Intermittent  
operation  
600-W Models  
If an excessive current flows for 5 s or more, the output will  
be turned OFF and simultaneously protection-ON alarm  
indicator will be lit. To reset the S8PS, turn OFF the input  
voltage, leave the S8PS for at least three minutes, and then  
apply the input voltage again.  
Note: Do not continue using the S8PS with the output termi-  
nals short-circuited or the overcurrent condition con-  
tinued, otherwise the internal elements of the S8PS  
may be damaged or broken.  
Rating  
Output current (%)  
J OVERVOLTAGE PROTECTION  
The Power Supply has an overvoltage protection function  
that protects the load and the Power Supply from possible  
damage by overvoltage. When the output voltage rises  
above a set value (120% of the rated output voltage), the  
protection function is triggered, shutting OFF the output  
voltage. If this occurs, reset the Power Supply by turning it  
OFF for 1 minute min. and then turning it ON again.  
Rated  
output  
voltage  
300- and 600-W Models  
If voltage that is 115% of the rated output voltage or above is  
output, the output voltage will be turned OFF and  
simultaneously protection-ON alarm indicator will be lit. To  
reset the S8PS, turn OFF the input voltage, leave the S8PS  
for at least one minute and then apply the input voltage  
again.  
0 V  
J OVERHEAT PROTECTION FUNCTION  
600-W Model Only  
If the internal temperature of the S8PS rises excessively as a  
result of fan failure or any other reason, the overheat protection  
circuit will be triggered to protect the internal elements of the  
S8PS and simultaneously a protection-ON alarm indicator will be  
lit. To reset the S8PS turn OFF the input voltage, leave the S8PS  
for at least one minute and then apply the input voltage again.  
106  
Switching Power Supply S8PS  
J INRUSH CURRENT, START UP TIME, HOLD TIME  
Input ON  
AC input  
Input OFF  
voltage  
Inrush current on input application  
AC input  
current  
96.5%  
90%  
Output  
voltage  
Rise time  
(1,000 ms max.)  
Hold time  
(20 ms min.)  
Operation  
J BLOCK DIAGRAMS  
S8PS-050jjjj (50 W)  
Rectifier  
AC(L)  
Fuse  
+V  
Noise filter  
INPUT  
DC OUT  
–V  
AC(N)  
Inrush current  
Harmonic Smooth-  
Rectifier/  
smoothing  
circuit  
protection circuit  
current  
control  
ing  
Drive control  
circuit  
Overload  
detection circuit  
Detector  
Overvoltage  
detection circuit  
107  
Switching Power Supply S8PS  
S8PS-10024jj (100 W)  
S8PS-15024jj (150 W)  
S8PS-30024jj (300 W)  
Rectifier  
AC(L)  
Fuse  
+V  
–V  
Noise filter  
INPUT  
DC OUT  
AC(N)  
Harmonic  
current  
control  
Smooth-  
ing  
Inrush current  
protection circuit  
Rectifier/  
smoothing  
circuit  
Control circuit  
Overload  
detection circuit  
Detector  
Overvolltage-  
detection circuit  
S8PS-60024C (600 W)  
DC OUT  
Rectifier/  
smoothing  
circuit  
Control circuit  
Fan  
Detector  
Overcurrent  
detection  
Overvoltage  
detection circuit  
Overheat  
detection  
108  
Switching Power Supply S8PS  
Dimensions  
Unit: mm (inch)  
J FRONT-MOUNTING BRACKET TYPE  
Note: For instructions on how to install the front-mounting brackets, refer to the a subsequent section: FRONT-MOUNTING BRACKETS.  
S8PS-050jj (50 W)  
S8PS-050jjjC (50 W)  
40  
(1.57)  
127 (5)  
11.5 max.  
3.5  
72  
85  
(3.35)  
7
10  
8.6  
Five, M4  
terminal screws  
117 (4.6)  
117  
3.5 dia.  
3.5 dia.  
5
3.5  
20  
14  
28  
28  
24  
Three, M3  
depth: 6 max.  
100 (3.94)  
12.5  
S8PS-10024 (100 W)  
S8PS-10024C (100 W)  
50  
(1.97)  
11.5 max.  
145 (5.71)  
4.5  
78  
92  
(3.62)  
7
10  
8.6  
Five, M4 terminal screws  
135 (5.31)  
135  
4.5 dia.  
Mounting holes (also on  
opposite side)  
4.5 dia.  
4.5  
25  
15  
28  
27.5  
Three, M4  
depth: 6 max.  
100 (3.94)  
12.5  
109  
Switching Power Supply S8PS  
S8PS-15024 (150 W)  
S8PS-15024C (150 W)  
50  
(1.97)  
163 (6.42)  
11.5 max.  
4.5  
78  
92  
(3.62)  
7
10  
8.6  
Five, M4 terminal screws  
153 (6.02)  
153  
4.5 dia.  
Mounting holes (also on  
opposite side)  
5
4.5 dia.  
4.5  
25  
15  
28  
27.5  
Three, M4 (depth: 6 max.)  
100 (3.94)  
S8PS-30024C (300 W)  
Eight, M4  
depth: 8 max.,  
(also for the  
opposite side)  
175 (6.89)  
14  
Seven, M4 terminal screws  
92  
(3.62)  
50  
(1.97)  
10  
8.6  
21  
150 (5.91)  
110 (4.33)  
13  
Four, M4  
depth: 8 max.  
100  
(3.94)  
150 (5.91)  
5
13  
110  
Switching Power Supply S8PS  
Unit: mm (inch)  
S8PS-60024C (600 W)  
Seven, M4  
depth: 8 max.  
Eight, M4  
depth: 8 max.,(also  
for the opposite side)  
170 (6.69)  
10  
8.6  
179 (7.05)  
60  
(2.36)  
92  
(3.62)  
16  
31  
160 (6.30)  
Four, M4  
depth: 8 max.,  
(opposite side  
only)  
14  
Four, M4  
depth: 8 max.  
100  
(3.94)  
45  
(1.77)  
12  
150 (5.91)  
100 (3.94)  
34  
J FRONT-MOUNTING BRACKETS  
50-W Models  
Using the Mounting Bracket  
11  
1.5  
9
Attach the Mounting Bracket to the panel and loosely tighten the two screws. Insert  
the projected parts of the Bracket (b) to the square holes of the power supply (a).  
Then securely tighten the screws.  
4.6  
15  
Two,  
3.5 dia.  
74  
4.6  
60  
5
20  
31.5  
Mounting Holes  
11  
4.7  
15  
Two, M3  
60  
20.5  
20  
Mounting Bracket  
111  
Switching Power Supply S8PS  
100/150-W Models  
Appearance and  
Using the Mounting Bracket  
Dimensions with Mounting Bracket  
Mounting Dimensions  
Mounting Bracket  
Mounting Bracket  
6.5  
11  
5 dia.  
115  
(4.53)  
max.  
105  
23.5  
38  
Mounting Bracket  
1.5  
Two, 5 dia.  
30  
300/600-W Models  
Appearance and Mounting Dimensions  
10 dia.  
R2.5  
30  
15  
7.5  
7.5  
145 (5.71)  
160 (6.30)  
Two,  
5 dia.  
92 (3.62)  
48  
(1.89)  
32  
(1.26)  
Dimensions with Mounting Bracket – 300-W models  
Using the Mounting Bracket  
Note: Mounting screws for the Power Supply Unit are provided.  
300-W models  
145  
(5.71)  
80  
Note: Mount the Unit 21.6 mm away from the mounting surface in  
order to provide air ventilation on the rear side.  
(3.15)  
Four, M4  
600-W models  
Dimensions with Mounting Bracket – 600-W models  
145  
(5.71)  
Note: Mount the Unit 28 mm away from the mounting surface in  
order to provide air ventilation on the rear side.  
140 (5.51)  
Four, M4  
112  
Switching Power Supply S8PS  
J DIN-RAIL MOUNTING TYPE  
Note: DIN-Rail Mounting Bracket is attached to the Power Supply Unit when the Unit is shipped.  
S8PS-050jjD (50 W)  
S8PS-050jjjCD (50 W)  
40  
(1.57)  
9.1  
127 (5)  
3.5  
46  
85  
(3.35)  
72  
10  
8.6  
7
5
117  
132.6 (5.22)  
)  
S8PS-10024D (100 W)  
S8PS-10024CD (100 W)  
50  
(1.97)  
9.1  
145 (5.71)  
4.5  
92  
(3.62)  
78  
46  
10  
8.6  
7
5
135 (5.31)  
150.6 (5.93)  
x.)  
S8PS-15024D (150 W)  
S8PS-15024CD (150 W)  
50  
(1.97)  
9.1  
11.5  
max.  
163 (6.42)  
4.5  
92  
(3.62)  
78  
46  
10  
8.6  
153 (6.02)  
168.6 (6.64)  
.)  
113  
Switching Power Supply S8PS  
Unit: mm (inch)  
S8PS-30024CD (300 W)  
14  
17.8  
175 (6.89)  
92  
(3.62)  
10  
8.6  
46  
(1.81)  
189.3 (7.45)  
110 (4.33)  
ith  
de:  
max.)  
J DIN-RAIL (ORDER SEPARATELY)  
PFP-100N2  
PFP-100N/  
PFP-50N  
16  
7.3r0.15  
4.5  
4.5  
27  
29.2  
1.5  
27r0.15  
24  
35r0.3  
35r0.3  
15 25  
25  
25  
25 15  
15 25  
25  
25  
25  
1
1
10  
10  
10  
10  
15  
5 *  
1,000  
500*  
1,000  
* For PFP-50N  
114  
Switching Power Supply S8PS  
Installation  
J 50-W MODELS  
J 100-/150-W MODELS  
4
5
4
5
1
3
2
1
3
2
J 300-W MODELS  
J 600-W MODELS  
1
5 4  
4
5
6
2
3
1
6
2
3
1. DC Output Terminals: Connect the load lines to these terminals.  
2. Input Terminals: Connect the input lines to these terminals.  
Note: A fuse is inserted into the AC (L) side.  
3. Ground Terminal (GR): Connect a ground line to this terminal.  
4. Output Indicator (DC ON): Lights while a Direct Current (DC) output is ON.  
5. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%.  
6. Protection-ON Alarm Indicator: The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for  
a 600-W model) circuit is triggered. This indicator will also be lit when overcurrent (for a 600-W model) is detected.  
115  
Switching Power Supply S8PS  
Precautions  
WARNING  
!
J PARALLEL OPERATION  
Do not touch the S8PS or heat radiation fin while the  
power is being supplied or immediately after the power is  
turned OFF. Otherwise, a skin burn may result from the  
hot Switching Power Supply or radiator.  
Only 300- and 600-W models can be in parallel operation  
provided that they are operated under 90% of the ratings. Do not  
operate any other models in parallel.  
Make sure that the thickness and the length of all wires  
connected to the load are the same to ensure that the wires will  
have no voltage drop differences.  
J MOUNTING  
x
When mounting the power supply, allow space for adequate  
air flow around it – to improve and maintain the reliability of  
the power supply over a long period of time. The power sup-  
ply is designed to dissipate heat through natural air-flow.  
+ V  
INPUT  
– V  
x
x
Omron recommends mounting the power supply to a metal  
plate.  
+ V  
Forced air-cooling is recommended.  
INPUT  
– V  
J GENERATING OUTPUT VOLTAGE (r)  
An output of r can be generated by using two Power Supplies as  
shown below, because the Power Supply produces a floating  
output.  
J FAN REPLACEMENT  
The service life of the fan is approximately 50,000 hours (at  
25qC). The service life varies, however, depending on the  
ambient temperature or other surrounding environmental  
conditions such as dust. As a preventive maintenance measure,  
replace the fan within two years if it is used at an ambient  
temperature of 40qC.  
+ V  
INPUT  
INPUT  
Input  
– V  
Fans are available as replacements.  
Model: S82Y-JFAN  
+ V  
– V  
J SERIES OPERATION  
Only models with power ratings of 100/150 W allow series  
operation.  
As shown in the following diagram, the output voltage from each  
Switching Power Supply can be added.  
+V  
INPUT  
–V  
Fan Set:  
+V  
Fan (above), four M4 x 35 sems screws, instruction sheet, and  
packing case>  
INPUT  
–V  
Replace the fan as shown in the following illustration.  
116  
Switching Power Supply S8PS  
ꢔꢙꢙꢅꢚꢛ !"ꢓꢛꢜ"ꢓꢅꢓ#ꢜ$"ꢅꢔ%!ꢅꢛ"ꢅ ꢛꢙꢙꢛ !&!%ꢓꢍꢅ&ꢅꢑꢂꢐ'ꢕꢏꢈꢅꢎꢖꢁꢁꢖꢎꢕꢈꢕꢏ(ꢅꢖꢐꢈꢂꢅꢖꢐꢑꢇꢕ()ꢅꢘꢖ'ꢖꢘꢕꢅꢃ*ꢅ+,ꢍ-  
ꢀꢁꢂꢀꢃꢄꢀꢃꢅꢆꢇꢃꢈ  
ꢀꢁꢂꢀꢃꢄꢈꢆꢈꢉꢔꢂꢀꢃꢇꢉꢕꢄꢆꢆꢉ  
ꢜꢐꢕꢅꢗꢂꢎꢎꢕꢏꢑꢕꢅꢚꢏꢖ'ꢕ  
ꢀꢁꢂꢀꢃꢄꢉꢊꢃꢊꢋꢊꢌꢄꢇꢃꢉꢍ  
22,ꢅ ꢖꢁꢐꢕꢏꢅꢔ'ꢕꢐ3ꢕ  
ꢀꢁꢂꢃꢄꢁꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢂꢎ  
ꢒꢓꢔꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢂꢎꢋꢂꢕꢖ  
ꢗꢄꢐꢄꢘꢄꢅꢆꢅꢇꢈꢈꢉꢊꢋꢋꢌꢌꢌꢍꢂꢎꢏꢂꢐꢍꢑꢄ  
ꢓꢑꢇꢄ3ꢎꢃ3ꢏ7)ꢅꢛꢙꢅꢝ/489  
&ꢏꢂꢐꢈꢂ)ꢅꢜꢐꢈꢄꢏꢖꢂꢅ 45ꢅ,62  
ꢒꢎꢖꢅꢒꢎꢗꢅꢖꢘꢙꢙ  
ꢎꢏꢐꢅꢑꢒꢐꢅꢐꢎꢐꢓ  
1ꢂꢏꢅꢒꢓꢅꢈꢕꢑꢇꢐꢖꢑꢄꢁꢅ(3ꢉꢉꢂꢏꢈꢅꢂꢏꢅꢂꢈꢇꢕꢏꢅꢖꢐ:3ꢖꢏꢖꢕ(ꢊ  
ꢒꢙꢙꢅꢓꢓꢐꢅꢐꢖꢐꢐ  
Cat No. GC PS6  
2/03  
Specifications subject to change without notice  
Printed in USA  
117  
Switching Power Supply S8PS  

相关型号:

S8PS-15024CD

Power Supply Module
OMRON

S8PS-15024D

Power Supply Module
OMRON

S8R5B910N1

Directional Coupler, 836MHz Min, 985MHz Max, 0.2dB Insertion Loss-Max
ANAREN

S8RB-8180N

Wire Terminal
MOLEX

S8S3122X16

256K x 16 SDRAM
SAMSUNG

S8S3122X16-TCR1

256K x 16 SDRAM
SAMSUNG

S8S3122X16-TCR2

256K x 16 SDRAM
SAMSUNG

S8T04F

Decoder/Driver, TTL, CDIP16
PHILIPS

S8T04F/883B

Decoder/Driver, TTL, CDIP16
PHILIPS

S8T04F/883C

Decoder/Driver, TTL, CDIP16
PHILIPS

S8T04W

Decoder/Driver, TTL, CDFP16
PHILIPS

S8T04W/883C

Decoder/Driver, TTL, CDFP16
PHILIPS